Omega CN1166 manual Parameter Function Adjustment Range Default Value

Page 41

Parameter

Function

Adjustment Range

Default

value

 

 

 

 

 

 

 

Process High

If Alarm 2 is a Process High Alarm,

Input Range Minimum

Input

Alarm 2

the value of the process variable at or

to Input Range

Range

 

above which Alarm 2 will be active

Maximum

Maximum

 

(see Figure 2-2)

 

 

 

 

 

 

Process Low

If Alarm 2 is a Process Low Alarm, the

Input Range Minimum

Input

Alarm 2

value of the process variable at or

to Input Range

Range

 

below which Alarm 2 will be active

Maximum

Minimum

 

(see Figure 2-2)

 

 

 

 

 

 

Band Alarm 2

If Alarm 2 is a Band Alarm, the band

0 to input span from

5 units

 

of process variable values, centred on

(program) setpoint

 

 

the (program) setpoint, outside which

 

 

 

the process variable will cause this

 

 

 

alarm to be active (see Figure 2-2)

 

 

 

 

 

 

Deviation

If Alarm 2 is a Deviation Alarm, gives

￿input span from

5 units

Alarm 2

a value above (positive value) or

(program) setpoint

 

 

below (negative value) the (program)

 

 

 

setpoint. If the process variable

 

 

 

deviates from the setpoint by a

 

 

 

margin greater than this value, the

 

 

 

alarm becomes active (see Figure

 

 

 

2-2)

 

 

 

 

 

 

Alarm 2

Defines a hysteresis band on the

1 to 250 units

1 unit

Hysteresis

“safe” side of the Alarm 2 value

 

 

 

 

 

 

Scale Range

For linear inputs only, defines the

0 (xxxx), 1 (xxx.x), 2

1 (xxx.x)

Decimal Point

decimal point position

(xx.xx) or 3 (x.xxx)

 

Position

 

 

 

 

 

 

 

Scale Range

For linear inputs only, defines the

￿1999 to 9999

1000

Maximum

scaled input value when the process

 

 

 

variable input is at its maximum value

 

 

 

 

 

 

Scale Range

For linear inputs only, defines the

￿1999 to 9999

0000

Minimum

scaled input value when the process

 

 

 

variable input is at its minimum value

 

 

 

 

 

 

Manual Control

 

0 (Disabled) or

0

Enable/Disable

 

1 (Enabled)

(Disabled)

 

 

 

 

Setpoint Strategy

Determines whether or not the

0 = not adjustable,

1

 

setpoint is adjustable in the normal

1 = adjustable

 

 

Base Mode display

 

 

 

 

 

 

Communications

Enables/disables changing of

0 (disabled) or

1

Enable/Disable

parameter values via the

1 (Enabled)

(Enabled)

 

communications link

 

 

 

 

 

 

Controller Set-Up

Defines the four-digit code required

0 to 9999

10

Mode Lock Code

to enter the Controller Set-Up Mode

 

 

 

 

 

 

 

 

 

 

O077-2

Volume II

2-5

Image 41
Contents Page Page RAMP/SOAK Profile Volume Operating Instructions Volume Installation & Configuration InstructionsContents PANEL-MOUNTING the Controller Unpacking ProcedureConnections and Wiring Rear Terminal Connections 2 24V Nominal AC/DC Supply Mains Line InputThermocouple Input RTD InputsRemote Run/Hold Input Linear InputsRelay Outputs SSR Drive Outputs11 RS485 Serial Communications Link DC OutputsRemoving the Profile Controller from ITS Housing Internal Links and SwitchesRemoving the Output 2/Output 3 Option PCBs REMOVING/REPLACING the Output 2/OUTPUT 3 Option PCBs Replacing the Instrument in ITS HousingInput Type Selection of Input Type and Output 1 TypeCPU PCB Relay/SSR Drive/Solid State Output Primary Output Output 1 TypeOutput 2 TYPE/OUTPUT 3 Type Hardware Definition Code Entry Into Configuration ModeWit h Hardw are Definit ion Code displayed Configurat ion ModeHardware Definition Code Input/Output Type Selection Option SelectionWit h Hardw are Definit ion Code displayed Configuration Mode ParametersParameter AL1 OFF, AL2 OFF Parameter Page Exit from Configuration Mode Base Mode Program Definition Mode CREATING/EDITING a Program Controller SET-UP ModeModbus Communications Alphabetic IndexDisplay Sequence no Program Running Base ModePutting a Program in Hold Starting a ProgramReleasing a Program from Hold Aborting a ProgramRead Only whilst Program is running/held Display Sequence Program RunningPRE-TUNE Feature RaPID Control FeatureIndication of PRE-TUNE and RaPID Status Engaging Both PRE-TUNE and RaPID FeaturesRaPID Status when Hardware Definition Code has the following significance Viewing the Hardware Definition CodePress till front panel shows Press or to change display to Manual ControlController SET-UP Mode Lower display = Parameter Details Parameter Function Adjustment Range Default ValueON/OFF Parameter Function Adjustment Range Default Value Power Alarm Operation Deviation When this display shows Exit from Controller SET-UP ModeEntry Program Definition Mode CREATING/EDITING a ProgramBasic Guidelines Creating a ProgramTo make a Soak segment Defining Segments Rate ModeDefining Segments Time Mode Program Options T p o i n t Guaranteed Soak BandSegment Event Status Press key To display Exit from Program Define Mode Default Values and Adjustment RangesMessage Formats IntroductionModbus Functions Supported CRC16 Read Coil Status Read n Bits 01/02Force Single Coil Write 1 Bit Read Holding Registers Read n Words 03/04Preset Multiple Registers Write n Words 16 B Preset Single Register Write 1 Word 06 BLoopback Diagnostic Test CRC16 Calculation Error and Exception ResponsesReversed BIT Order Used Bit Parameters Controller Status Byte Parameter NumbersController Parameters Word ParametersInstrument ID Parameters Volume O077-4 Profiler Status Byte Profiler CommandsGeneral Universal InputInput Range Remote RUN/HOLD Input Option Relay OutputSSR Drive/TTL Solid StateTypes Available Relay, SSR drive, solid state and DC Solid State SSR Drive/TTL Loop Control Alarm ControlPerformance Under Reference Conditions PerformanceReference Conditions S077-A Volume Physical EnvironmentalSee Performance Appendix B Summary of Displays Program Define Mode Parameters Configuration Mode Parameters AppendixC RaPID Control Feature AT OFF Alphabetical Index S077-IDX Volume Making a Soak Segment S077-IDX Volume Unpacking Procedure Word Parameters II/4-8