2.3.4.Connection Overview - Error Statistics Aspect
Parameter | Description |
|
| |
Connection | The current connection being displayed out of the total number. | |||
PEX No slave | Pex mode tried to create a cache block and failed - normally a | |||
failed | ||||
| ||||
Server Overruns | A message arrived from the upstream device while the server port | |||
was on hold. Increase the timeout setting in the external device. | ||||
| ||||
Server Hold Timeouts | If an upstream device requests data from a cache where the data | |||
is too old then the data will be refreshed by polling from the | ||||
| downstream device. The response was not received in time. | |||
| A remote device never responded to the FieldServer poll. Either | |||
| the device is not responding, or one of the timeout parameters is | |||
Timeouts | set too low. | Ensure that the device is online and addressed | ||
| correctly and if necessary increase the relevant timeout parameter | |||
| in the CSV file. |
| ||
Checksum Errors | External influences e.g. electrical noise corrupted the data. | |||
Check that communication cables are shielded, not too long and | ||||
| do not run past power cables. |
| ||
Protocol Errors | An external | device responded with unexpected or | unknown | |
messages. Consult the relevant driver manual. |
| |||
|
| |||
Noise | Corrupted or garbage bytes on a communications line. |
| ||
Bad Length | A message that looks Ok, but is of the incorrect length. |
| ||
Bad Node | A | external | ||
device. |
|
| ||
|
|
| ||
Bad Function | E.g. an external device is written to that does not support writes. | |||
No Start | Communications to an external device could not be started. | |||
PLC exception | A variation of a NAK message produced by some protocols. | |||
NAK | A NAK message is received in response to a poll. |
| ||
| Data seems to be continuously arriving from an external device. | |||
| This could be due to a mismatch in baud rates. |
| ||
| Streaming errors are typically produced when: |
| ||
Streaming | 1) The transmitter sends more data than the FieldServer can | |||
process. |
|
| ||
| 2) An unexpectedly long message is received or messages have | |||
| been corrupted so that the end of a previous message cannot be | |||
| detected. |
|
| |
| 3) A message longer than the driver expects has been received. | |||
| A response from an external device arrived before it was | |||
| expected, implying that it is not the response for the poll the | |||
Premature | FieldServer has just sent. This could occur when there are time | |||
delays in communication networks which contain bridges and | ||||
| routers which may delay messages for longer than expected. | |||
| Increase the timeout parameter for the connection to eliminate | |||
| these errors. |
|
| |
Preamble | Characters preceding a message were dropped. |
| ||
IC Timeouts | Too much time between receiving successive bytes in a message. | |||
Address Errors | A driver tried to address a wrong device or a wrong block of data | |||
within an external device. |
| |||
|
| |||
Data Object offline | A poll was received for a node that is offline. |
| ||
Node Offline | An external | device node is offline in response to a | driver or |