Extron electronic MLC 62 IR D manual Wiring the Digital Input Port RS Models Only, Mlc

Page 30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Tx

HOST/

CONFIG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GROUND

 

 

 

 

 

 

 

 

 

 

Rx

DIGITAL

INPUT

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

GROUND

RELAYS

N/O

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COMMON

 

 

 

 

 

 

 

 

 

 

2

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GROUND

PORT IR/S

 

 

 

 

 

 

 

Tx/IR

 

 

 

 

 

 

 

 

 

 

 

 

MLC

RS

GROUND

232-RS

 

 

D Rear Panel

 

 

 

 

 

 

 

Tx

 

 

 

 

 

 

 

 

 

 

 

 

X

 

 

 

Power

 

 

 

Supply

 

Pin:

 

 

Ground ( )

3

Ground ( )

 

2

Signal

 

110/220 V

1

 

 

 

 

 

Low Voltage

Motorized

 

 

Screen Control

 

 

Screen

 

 

 

Figure 25. Connecting a Motorized Screen to the Relay Port of an MLC RS D

To connect devices to both relay ports:

1.Connect the ground wires of both devices to pin 3 of the provided 3-pole captive screw connector.

2.Connect the signal wire of one device to pin 2 and the other device to pin 1 of the 3-pole connector.

3.Plug the 3-pole connector into the MLC Relays port.

To define the operation of a relay and associate it with a button or a digital input, use the configuration software (see “Adding relays to buttons” or “Configuring the Digital Input Port” in the “Software-based Configuration” section or the configuration software help for setup procedures).

Wiring the Digital Input Port (RS Models Only)

The Digital Input port on the MLC rear panel lets you connect a switch or sensor to control other devices in the room that are connected to the MLC serial, IR, and relay ports. This port measures two states — high and low — of the connection between the switch or sensor and the connected device. The port accepts 0 to 24 VDC input. The threshold voltages are as follows: a voltage below 1.0 VDC is measured as logic low, and a voltage above 1.5 VDC is measured as logic high.

There is also an internal, +5 VDC, selectable, pull-up resistor for this circuit. If a connected device does not have its own power source and will be powered through the controller, configure this port (via the MLC configuration software) with Input with Pullup as the digital input mode. If the connected device provides its own power, select Input for the digital input mode (see the MLC 60 Series Configuration Program Help File to select the digital input mode).

In addition, you can program actions on this port, so that each time a high or low state is detected, one or more functions are performed. An example of this is front panel lockout, or executive mode (see the configuration software help file to configure the Digital Input port).

To wire the Digital Input connector:

1.Connect the ground port of the input device to pin 2 of a provided 2-pole captive screw connector.

2.Connect the signal port of the input device to pin 1 of the captive screw connector.

3.Plug the wired connector into the MLC rear panel Digital Input connector.

MLC 60 Series MediaLink Controllers • Features, Installation, and Operation

24

Image 30
Contents MLC 60 Series Safety Instructions English FCC Class a Notice Software Commands Conventions Used in this GuideNotifications Contents MLC 60 Series MediaLink Controllers Contents About This Guide About the MLC 60 Series MediaLink ControllersMLC Models MLC 62 RS EU Features Faceplate alternativesVolume adjustment MLC Configuration Software Device Drivers Application DiagramsMLC 62 IR D Controlling a Projector System Requirements ExtronFeatures Installation, Operation Installation OverviewFront and Left Side Panels MLC D Front PanelsMLC 62 D front panels MLC 64 RS VC D front panelMLC 62 RS EU and MLC 62 RS MK Front and Side Panels Controls behind the wallplateFront panel features Buttons Rear Panel Features MLC 60 Series D Models Rear PanelsPort B IR/S Rear Panel Features on MLC 62 RS EU and MLC 62 RS MK Only MLC 64 RS VC D Volume Control Module Rear PanelInstallation Removing and Replacing the FaceplatesRemoving and replacing an MLC D faceplate Removing the Faceplate MLC 60 Series D Models Replacing the MLC 64 volume control knob Removing the MLC 64 Volume Control Module Faceplate Removing and replacing the MLC 62 RS EU and MK faceplatesReplacing Buttons Replacing the Faceplate MLC 62 RS EUWiring for RS-232 Control RS Models Only Connecting to Port a RS-232Connecting to Port B IR/S Wiring for IR Control Wiring the Relays Port RS Models OnlyWiring the Digital Input Port RS Models Only MLCWiring the Host/Config Port Connecting a Two-position Switch to the Digital Input PortWiring the Volume Control Module MLC 64 RS VC D Only Connecting Power to the MLCConfiguring the MLC via the USB Port Connecting a Power Supply to an MLCUSB Port Connection for MLC 62 RS EU and MLC 62 RS MK Page IR Learning IR Learning on an MLC D ModelMounting the MLC 60 Series Controllers Mounting an MLC 62 DMounting an MLC 62 D to an electrical junction box Mounting an MLC 62 D to a Decora Mounting Bracket Mounting an MLC 62 D to a Decora Mounting BracketMounting the MLC 64 RS VC D Mounting an MLC 64 RS VC D to an electrical junction boxMounting an MLC 64 RS VC D to a Decora Mounting Bracket Mounting an MLC 64 D to a Two-gang Decora Mounting BracketMounting the MLC 62 RS EU and the MLC 62 RS MK Mounting the MLC 62 RS EU to an Electrical BoxMounting the MLC EU in a Raceway Using Spacers Optional Mounting the MLC 62 RS MK to an External Electrical BoxMounting the MLC 62 RS EU Using a Spacer Accessing Covered Panel Features After Mounting Accessing the Covered MLC D Front Panel FeaturesLocking Using the Front Panel Buttons Front Panel Security LockoutResetting the MLC Using the Reset Button Resetting to the default configurationResetting to the factory firmware defaults About the MLC Configuration Program Computer System RequirementsInstalling the Configuration Software Downloading and Installing the Software from the WebInstalling the Software from the DVD Starting the Configuration Software Start Options WindowAdd Device Window with Select Model Menu Displayed Accessing the Help File Downloading Drivers Using the Configuration Program Obtaining Device DriversDriver Subscription Window Driver Subscription Download Screen Downloading Drivers from the Disc Drivers Tab and Button on the Software DVD Opening ScreenMLC 60 Device Drivers Page on DVD To download the driver packageTo download a single driver Saving a Single Driver to the ComputerDownloading Drivers from the Web Entering MLC 60 Series Driver Search Criteria Error Responses Host-to-Controller CommunicationsController-initiated Messages Using the Command and Response Table Symbol DefinitionsX2# X2% MLC 60 Series MediaLink Controllers SIS Control Command and Response Table for SIS Commands Command Ascii Command Response Additional DescriptionButton Selection Digital Input Data Port RS models only Front Panel Lockout Executive ModeRelay Functions RS models only Device NamingReset/Erase Information RequestsQuery LED status = Button row 4, second LED = Button row 4, third LEDSpecifications MLC 62 Series SpecificationsControl digital input monitoring port RS models GeneralMLC 62 RS EU EMI/EMC MLC 64 RS VC D Specifications MLC 64 RS D Warranty Part Numbers and Accessories Included Parts Replacement Part NumberIncluded Parts MLC 62 RS EU MLC 64 RS VC D Accessories Accessories Part Number For ModelAsia Middle East USA, Canada, South America Japan Central AmericaEurope, Africa, and the Middle China East Europe