HP Performance Optimized Data Center (POD) 40cp manual Aisle clearances, Cold aisle clearance

Page 13

Aisle clearances

Cold aisle clearance

The maximum protrusion of any installed IT component directly impacts the available cold aisle clearance for removal and replacement of other IT components. Maximum component depth must follow the clear aisle distance calculations. The following figure shows how to calculate this distance.

The maximum rack face-to-cold aisle wall distance is 39.5 inches. In the figure, X represents any protrusion into the cold aisle starting from the rack face of the installed IT component (for example, the bezel). Y represents cold aisle clearance. The cold aisle clearance dictates the maximum depth (D) of any installed IT component. To find the maximum cold aisle clearance, calculate 100.33 cm (39.5 in) - X = Y.

IMPORTANT: As the value for X increases, the value for Y decreases, which also decreases the maximum depth allowed for an installed component.

Illustrated parts catalog 13

Image 13
Contents Abstract Page Contents Periodic maintenance Contacting HP Structural component identification Illustrated parts catalogParts and part number identification Life safety component identification Component Description Electrical power component identificationExternal panel labels Front view shown Callout Electrical safety label Description Control cabinet component identification Electrical safety label DescriptionHP POD 40c NA racks Cooling system component identificationCold aisle clearance Aisle clearancesHot aisle clearance Replaceable componentsSafety considerations Removal and replacement proceduresOperator safety Air filter Fire detection and suppressionRemoving the air filter Replacing the air filter Removing the busway drop box Busway drop boxReplacing the busway drop box Differential pressure sensor Replacing the differential pressure sensor Removing the differential pressure sensorRemoving the door position contact Door position contactReplacing the door position contact Removing the drain pan sensor Drain pan sensorReplacing the drain pan sensor Removal and replacement procedures Removing the ECS touchscreen ECS touchscreenReplacing the ECS touchscreen EPO buttonRemoving the EPO button Replacing the EPO button Removing the EPO LED indicator EPO LED indicatorsReplacing the EPO LED indicator Removing the EPO thermister EPO thermisterReplacing the EPO thermister Removing the external chilled water flow actuator External chilled water flow actuatorRemoval and replacement procedures Replacing the external chilled water flow actuator External chilled water flow valveRemoving the external chilled water flow valve External pressure gauge isolation valveReplacing the external chilled water flow valve Removing the external pressure gauge isolation valve FanReplacing the external pressure gauge isolation valve Removing the fan Replacing the fan Removing the fan bank Fan bankReplacing the fan bank Removing the fire strobe light Fire strobe lightReplacing the fire strobe light HumidifierRemoving the humidifier Removal and replacement procedures Replacing the humidifier Removing the humidistat HumidistatReplacing the humidistat Removal and replacement procedures Removing the humidity sensor Humidity sensorRemoval and replacement procedures Replacing the humidity sensor Removing the LED light LED lightReplacing the LED light Temperature sensor cold aisleRemoving the cold aisle temperature sensor Replacing the cold aisle temperature sensor Removing the hot aisle temperature sensor Temperature sensor hot aisleRemoval and replacement procedures Replacing the hot aisle temperature sensor Removing the Vesda filter Vesda filterReplacing the Vesda filter Periodic maintenance overview Periodic maintenanceCooling system maintenance schedule Qualified personnelLeak detection maintenance ECS Humidifier if installedPOD Shut Down Required ElectricalVesda Fire alarm and suppression systemHP POD 40c NA structure Life safetyThird-party components Access controlPeriodic maintenance General specifications SpecificationsElectrical specifications Rack specifications Water specificationsEnvironmental specifications Thermal and air flow performanceOptional features specifications Before you contact HP Contacting HPHP contact information Warranty information Safety and regulatory complianceRegulatory information AHJ GlossaryPDU Documentation feedback Index Temperature sensor
Related manuals
Manual 63 pages 13.75 Kb Manual 21 pages 18 Kb