HP Performance Optimized Data Center (POD) 40cp manual Specifications, General specifications

Page 70

Specifications

General specifications

Features

Specifications

 

 

Overall dimensions

Height—3.66 m (12 ft)

 

Length—12.19 m (40 ft)

 

Width—2.43 m (7.97 ft)

 

 

Weight1

Empty—16,783 kg (37,000 lb)

 

Maximum fully loaded—46,266 kg (102,000 lb)

Maximum power2

600 kW HP POD 40c NA

Power input voltage

380 VAC to 415 VAC

 

 

Power distribution3

8 x 200 A electrical busways

Maximum rack quantity

20 racks

RU per rack

50 RU

RU total

1,197 RU

Average capacity per rack (kW)

30 kW

Peak rack capacity

69 kW

 

 

Voltage to rack

200 VAC to 240 VAC

Minimum quantity of PDUs per HP POD 40c NA

20 (one per rack)

Maximum quantity of PDUs per HP POD 40c NA

40 (two per rack)

Maximum power per PDU

30A = 17 kW; 60A = 34 kW

Network supported

Bulk cable pass through fiber

 

Bulk cable pass through copper

 

(Optional) External rated demarcation box

 

 

1The Empty weight includes the HP POD 40c NA structure, empty racks, PDUs, and drop boxes. It does not include IT equipment. All weights are estimates and can vary for your POD.

2Maximum power depends on the exact installation and power configuration in your POD. The HP POD 40c NA is electrically limited to 600 kW.

3Can be configured for redundancy or non-redundancy.

Electrical specifications

Electrical busway system information

Feature

Specification

 

 

Number of busways

8

Frequency

60 Hz

Amps (per busway)

200 A

Voltage (per busway)

380 to 415 V

Grounding

Copper

Busway configuration

3-phase + neutral + equipment ground

Specifications 70

Image 70
Contents Abstract Page Contents Periodic maintenance Contacting HP Structural component identification Illustrated parts catalogParts and part number identification Life safety component identification Electrical power component identification Component DescriptionExternal panel labels Front view shown Callout Electrical safety label Description Electrical safety label Description Control cabinet component identificationCooling system component identification HP POD 40c NA racksAisle clearances Cold aisle clearanceReplaceable components Hot aisle clearanceSafety considerations Removal and replacement proceduresOperator safety Air filter Fire detection and suppressionRemoving the air filter Replacing the air filter Busway drop box Removing the busway drop boxReplacing the busway drop box Differential pressure sensor Removing the differential pressure sensor Replacing the differential pressure sensorRemoving the door position contact Door position contactReplacing the door position contact Drain pan sensor Removing the drain pan sensorReplacing the drain pan sensor Removal and replacement procedures ECS touchscreen Removing the ECS touchscreenEPO button Replacing the ECS touchscreenRemoving the EPO button Replacing the EPO button EPO LED indicators Removing the EPO LED indicatorReplacing the EPO LED indicator Removing the EPO thermister EPO thermisterReplacing the EPO thermister External chilled water flow actuator Removing the external chilled water flow actuatorRemoval and replacement procedures External chilled water flow valve Replacing the external chilled water flow actuatorRemoving the external chilled water flow valve External pressure gauge isolation valveReplacing the external chilled water flow valve Removing the external pressure gauge isolation valve FanReplacing the external pressure gauge isolation valve Removing the fan Replacing the fan Fan bank Removing the fan bankReplacing the fan bank Fire strobe light Removing the fire strobe lightHumidifier Replacing the fire strobe lightRemoving the humidifier Removal and replacement procedures Replacing the humidifier Humidistat Removing the humidistatReplacing the humidistat Removal and replacement procedures Humidity sensor Removing the humidity sensorRemoval and replacement procedures Replacing the humidity sensor LED light Removing the LED lightTemperature sensor cold aisle Replacing the LED lightRemoving the cold aisle temperature sensor Replacing the cold aisle temperature sensor Temperature sensor hot aisle Removing the hot aisle temperature sensorRemoval and replacement procedures Replacing the hot aisle temperature sensor Vesda filter Removing the Vesda filterReplacing the Vesda filter Cooling system maintenance schedule Periodic maintenancePeriodic maintenance overview Qualified personnelLeak detection maintenance Humidifier if installed ECSElectrical POD Shut Down RequiredFire alarm and suppression system VesdaLife safety HP POD 40c NA structureAccess control Third-party componentsPeriodic maintenance General specifications SpecificationsElectrical specifications Environmental specifications Water specificationsRack specifications Thermal and air flow performanceOptional features specifications Before you contact HP Contacting HPHP contact information Warranty information Safety and regulatory complianceRegulatory information Glossary AHJPDU Documentation feedback Index Temperature sensor