Busway drop box
The internal electrical busways provide a location to connect each of the drop boxes, which then power the PDUs. Stagger the drop boxes on the electrical busways by connecting one drop box to busway #1 and connecting the next drop box to busway #2. A staggered configuration enables load balancing with the rack equipment and is necessary to ensure redundancy.
You need a socket wrench for installation.
IMPORTANT: HP recommends that you shut down the associated IT equipment and
Removing the busway drop box
1.Turn the power off by opening both breakers on the busway drop box (1).
2.Disconnect the PDUs that are connected to the busway drop box (2).
3.Use a socket wrench to loosen and remove the bolt securing the busway drop box to the retaining hardware bracket (1).
Removal and replacement procedures 18