Periodic maintenance
Periodic maintenance overview
Perform periodic inspections on the components in this section to ensure that the HP POD 40c NA continues to perform within the designed parameters.
Qualified personnel
Qualified personnel are identified as personnel who are:
•Properly trained in the operation and maintenance of the HP POD 40c NA
•
Qualified personnel can be:
•HP personnel
•Agents for HP
•Site maintenance personnel
Cooling system maintenance schedule
Component to be inspected | Task | Frequency | Capable Party |
| |
|
|
|
|
| |
Air filters | Inspect and replace as necessary | Quarterly, or as | Qualified personnel |
| |
|
|
| needed |
|
|
Air filter differential pressure | Inspect and test, replace as | Annually | Qualified personnel |
| |
sensor | necessary |
|
|
| |
Cooling system leak check | Verify there is no visible chilled | Quarterly | Qualified personnel |
| |
| water leak from: |
|
|
| |
| • | Heat exchanger |
|
|
|
| • Cold water supply piping |
|
|
| |
| • Cold water return piping |
|
|
| |
| If a leak is detected, see "Leak |
|
|
| |
| detection maintenance (on page |
|
|
| |
| 63)" |
|
|
| |
Condensate drain pans | Inspect pans: | Quarterly | Qualified personnel |
| |
| • | Free of debris |
|
|
|
| • | No leaks |
|
|
|
| • Leakage detectors are in |
|
|
| |
|
| proper position |
|
|
|
| Clean pans as necessary |
|
|
| |
Condensate drain pan sensors | Inspect and test, replace as | Quarterly | Qualified personnel |
| |
| necessary |
|
|
| |
| If a leak is detected, see "Leak |
|
|
| |
| detection maintenance (on page |
|
|
| |
| 63)" |
|
|
| |
|
|
|
| Periodic maintenance 62 |