HP Performance Optimized Data Center (POD) 40cp manual EPO LED indicators

Page 30

EPO LED indicators

The ECS cabinet contains white (1, 2, 6, 7), red (1,3), yellow (1,5), and green (4) EPO LED indicators.

Tools are not required for installation.

Removing the EPO LED indicator

1.On the back of the ECS cabinet door, push the gray tab on the EPO LED indicator module down to release the module (1), and then pull the module out of the door (2).

Removal and replacement procedures 30

Image 30
Contents Abstract Page Contents Periodic maintenance Contacting HP Illustrated parts catalog Structural component identificationParts and part number identification Life safety component identification Electrical power component identification Component DescriptionExternal panel labels Front view shown Callout Electrical safety label Description Electrical safety label Description Control cabinet component identificationCooling system component identification HP POD 40c NA racksAisle clearances Cold aisle clearanceReplaceable components Hot aisle clearanceRemoval and replacement procedures Safety considerationsOperator safety Fire detection and suppression Air filterRemoving the air filter Replacing the air filter Busway drop box Removing the busway drop boxReplacing the busway drop box Differential pressure sensor Removing the differential pressure sensor Replacing the differential pressure sensorDoor position contact Removing the door position contactReplacing the door position contact Drain pan sensor Removing the drain pan sensorReplacing the drain pan sensor Removal and replacement procedures ECS touchscreen Removing the ECS touchscreen EPO button Replacing the ECS touchscreenRemoving the EPO button Replacing the EPO button EPO LED indicators Removing the EPO LED indicatorReplacing the EPO LED indicator EPO thermister Removing the EPO thermisterReplacing the EPO thermister External chilled water flow actuator Removing the external chilled water flow actuatorRemoval and replacement procedures External chilled water flow valve Replacing the external chilled water flow actuatorExternal pressure gauge isolation valve Removing the external chilled water flow valveReplacing the external chilled water flow valve Fan Removing the external pressure gauge isolation valveReplacing the external pressure gauge isolation valve Removing the fan Replacing the fan Fan bank Removing the fan bankReplacing the fan bank Fire strobe light Removing the fire strobe lightHumidifier Replacing the fire strobe lightRemoving the humidifier Removal and replacement procedures Replacing the humidifier Humidistat Removing the humidistatReplacing the humidistat Removal and replacement procedures Humidity sensor Removing the humidity sensorRemoval and replacement procedures Replacing the humidity sensor LED light Removing the LED lightTemperature sensor cold aisle Replacing the LED lightRemoving the cold aisle temperature sensor Replacing the cold aisle temperature sensor Temperature sensor hot aisle Removing the hot aisle temperature sensorRemoval and replacement procedures Replacing the hot aisle temperature sensor Vesda filter Removing the Vesda filterReplacing the Vesda filter Cooling system maintenance schedule Periodic maintenancePeriodic maintenance overview Qualified personnelLeak detection maintenance Humidifier if installed ECSElectrical POD Shut Down RequiredFire alarm and suppression system VesdaLife safety HP POD 40c NA structureAccess control Third-party componentsPeriodic maintenance Specifications General specificationsElectrical specifications Environmental specifications Water specificationsRack specifications Thermal and air flow performanceOptional features specifications Contacting HP Before you contact HPHP contact information Safety and regulatory compliance Warranty informationRegulatory information Glossary AHJPDU Documentation feedback Index Temperature sensor
Related manuals
Manual 63 pages 13.75 Kb Manual 21 pages 18 Kb