HP Performance Optimized Data Center (POD) 40cp manual Access control, Third-party components

Page 68

Component to be inspected

Task

Frequency

Capable Party

 

 

 

 

EPO System Test

EPO NON-FUNCTIONAL TEST

Annually

Qualified personnel

 

Mode Key Switch Test - rotate

 

 

 

keyed switch through all modes.

 

 

 

ARMED MODE - Verify:

 

 

 

Power Indicator - White

 

 

 

Armed Light - White

 

 

 

BYPASS MODE - Verify

 

 

 

Bypass Light - Green

 

 

 

TEST MODE - Verify:

 

 

 

Test Light - Amber

 

 

 

Press EPO button (each in

 

 

 

succession) and thermal trip to

 

 

 

verify:

 

 

 

Reset Light - White

 

 

 

Audible alarm

 

 

 

Visual lamp indicator

 

 

 

Replace light upon failure

 

 

Emergency Lighting

Verify emergency lighting is

Every 2 years

Qualified personnel

 

visible when all lighting is off and

 

 

 

the POD doors are shut.

 

 

Exit signs

Visually inspect exit signs for

Every 2 years

Qualified personnel

 

damage. Replace as necessary.

 

 

Emergency egress

Personnel door emergency egress

Every 2 years

Qualified personnel

 

panic bars. (Visual and

 

 

 

operational inspection.)

 

 

Access control

Component to be inspected

Task

Frequency

Capable Party

 

 

 

 

System functional test

Visual inspection and operational

Annually

Qualified personnel

 

test of door access contact

 

 

 

switches

 

 

Visual inspection and operational

Annually

Qualified personnel

 

test of the following:

 

 

 

Door access card readers

 

 

 

Electric strikes

 

 

 

Door release switches at each

 

 

 

personnel door and/or in

 

 

 

each personnel door panic

 

 

 

bar

 

 

 

 

 

 

Third-party components

All maintenance for third-party equipment will be defined by the manufacturer of the equipment. HP will, with a defined and signed SOW, conduct all maintenance as identified by the original manufacturer.

Examples of external third party components that HP will conduct all manufacturer specified maintenance with a signed SOW includes:

External UPS equipment

Periodic maintenance 68

Image 68
Contents Abstract Page Contents Periodic maintenance Contacting HP Parts and part number identification Illustrated parts catalogStructural component identification Life safety component identification Electrical power component identification Component DescriptionExternal panel labels Front view shown Callout Electrical safety label Description Electrical safety label Description Control cabinet component identificationCooling system component identification HP POD 40c NA racksAisle clearances Cold aisle clearanceReplaceable components Hot aisle clearanceOperator safety Removal and replacement proceduresSafety considerations Removing the air filter Fire detection and suppressionAir filter Replacing the air filter Busway drop box Removing the busway drop boxReplacing the busway drop box Differential pressure sensor Removing the differential pressure sensor Replacing the differential pressure sensorReplacing the door position contact Door position contactRemoving the door position contact Drain pan sensor Removing the drain pan sensorReplacing the drain pan sensor Removal and replacement procedures ECS touchscreen Removing the ECS touchscreenEPO button Replacing the ECS touchscreenRemoving the EPO button Replacing the EPO button EPO LED indicators Removing the EPO LED indicatorReplacing the EPO LED indicator Replacing the EPO thermister EPO thermisterRemoving the EPO thermister External chilled water flow actuator Removing the external chilled water flow actuatorRemoval and replacement procedures External chilled water flow valve Replacing the external chilled water flow actuatorReplacing the external chilled water flow valve External pressure gauge isolation valveRemoving the external chilled water flow valve Replacing the external pressure gauge isolation valve FanRemoving the external pressure gauge isolation valve Removing the fan Replacing the fan Fan bank Removing the fan bankReplacing the fan bank Fire strobe light Removing the fire strobe lightHumidifier Replacing the fire strobe lightRemoving the humidifier Removal and replacement procedures Replacing the humidifier Humidistat Removing the humidistatReplacing the humidistat Removal and replacement procedures Humidity sensor Removing the humidity sensorRemoval and replacement procedures Replacing the humidity sensor LED light Removing the LED lightTemperature sensor cold aisle Replacing the LED lightRemoving the cold aisle temperature sensor Replacing the cold aisle temperature sensor Temperature sensor hot aisle Removing the hot aisle temperature sensorRemoval and replacement procedures Replacing the hot aisle temperature sensor Vesda filter Removing the Vesda filterReplacing the Vesda filter Periodic maintenance Periodic maintenance overviewCooling system maintenance schedule Qualified personnelLeak detection maintenance Humidifier if installed ECS Electrical POD Shut Down RequiredFire alarm and suppression system VesdaLife safety HP POD 40c NA structureAccess control Third-party componentsPeriodic maintenance Electrical specifications SpecificationsGeneral specifications Water specifications Rack specificationsEnvironmental specifications Thermal and air flow performanceOptional features specifications HP contact information Contacting HPBefore you contact HP Regulatory information Safety and regulatory complianceWarranty information Glossary AHJPDU Documentation feedback Index Temperature sensor
Related manuals
Manual 63 pages 13.75 Kb Manual 21 pages 18 Kb