HP Performance Optimized Data Center (POD) 40cp manual Humidifier if installed, Ecs

Page 64

2.Power down the IT equipment in the zone where the leak is located.

3.Determine the affected heat exchanger.

4.Close and danger tag the supply and return valves to the affected heat exchanger.

If the heat affected exchanger cannot be identified, close all the heat exchanger supply and return valves in the affected zone and open one supply valve at a time to determine the location of the leak.

5.Repair the leak or contact HP if you are still within your service contract.

Humidifier (if installed)

Component to be inspected

Task

Frequency

Capable Party

 

 

 

 

 

Humidifier

Inspect for water leaks, verify

Every 2

Qualified personnel

 

that no sparks form between

 

weeks, if

 

 

the electrodes during

staffed

 

 

operation

Quarterly, if

 

 

Inspect the general operation

 

not staffed

 

 

of the cylinder.

 

 

 

Humidifier drains

Verify the following:

Quarterly

Qualified personnel

 

Drains are in working order

 

 

 

 

There is an air gap at the

 

 

 

 

funnel/drain entry into the site

 

 

 

 

system

 

 

 

 

Drain discharge is not getting

 

 

 

 

water on external equipment

 

 

 

 

or grounding system

 

 

 

 

 

 

 

Put the humidifier in system flush

Quarterly

Qualified personnel

 

mode and inspect drain flow and

 

 

 

 

water supply flow. Inspect, clean,

 

 

 

 

and/or replace as necessary.

 

 

 

Inspect for any internal or external

Quarterly

Qualified personnel

 

water leaks, repair or replace

 

 

 

 

leaking components.

 

 

 

Using LLS, verify proper cylinder

Quarterly

Qualified personnel

 

operation. Inspect the cylinder for

 

 

 

 

blackened areas and, if present,

 

 

 

 

check the condition of the

 

 

 

 

electrodes. If necessary, replace

 

 

 

 

the cylinder.

 

 

 

Replace the cylinder.

Annually

Qualified personnel

ECS

Component to be inspected

Task

Frequency

Capable party

 

 

 

 

Full system functional check

Check the operation of all system

Quarterly

Qualified personnel

 

components.

 

 

Check and clear the alarm log.

Quarterly

Qualified personnel

Inspect and test the ECS battery

Every 2 years

Qualified personnel

 

backup system.

 

 

Periodic maintenance 64

Image 64
Contents Abstract Page Contents Periodic maintenance Contacting HP Structural component identification Illustrated parts catalogParts and part number identification Life safety component identification Electrical power component identification Component DescriptionExternal panel labels Front view shown Callout Electrical safety label Description Electrical safety label Description Control cabinet component identificationCooling system component identification HP POD 40c NA racksAisle clearances Cold aisle clearanceReplaceable components Hot aisle clearanceSafety considerations Removal and replacement proceduresOperator safety Air filter Fire detection and suppressionRemoving the air filter Replacing the air filter Busway drop box Removing the busway drop boxReplacing the busway drop box Differential pressure sensor Removing the differential pressure sensor Replacing the differential pressure sensorRemoving the door position contact Door position contactReplacing the door position contact Drain pan sensor Removing the drain pan sensorReplacing the drain pan sensor Removal and replacement procedures ECS touchscreen Removing the ECS touchscreenEPO button Replacing the ECS touchscreenRemoving the EPO button Replacing the EPO button EPO LED indicators Removing the EPO LED indicatorReplacing the EPO LED indicator Removing the EPO thermister EPO thermisterReplacing the EPO thermister External chilled water flow actuator Removing the external chilled water flow actuatorRemoval and replacement procedures External chilled water flow valve Replacing the external chilled water flow actuatorRemoving the external chilled water flow valve External pressure gauge isolation valveReplacing the external chilled water flow valve Removing the external pressure gauge isolation valve FanReplacing the external pressure gauge isolation valve Removing the fan Replacing the fan Fan bank Removing the fan bankReplacing the fan bank Fire strobe light Removing the fire strobe lightHumidifier Replacing the fire strobe lightRemoving the humidifier Removal and replacement procedures Replacing the humidifier Humidistat Removing the humidistatReplacing the humidistat Removal and replacement procedures Humidity sensor Removing the humidity sensorRemoval and replacement procedures Replacing the humidity sensor LED light Removing the LED lightTemperature sensor cold aisle Replacing the LED lightRemoving the cold aisle temperature sensor Replacing the cold aisle temperature sensor Temperature sensor hot aisle Removing the hot aisle temperature sensorRemoval and replacement procedures Replacing the hot aisle temperature sensor Vesda filter Removing the Vesda filterReplacing the Vesda filter Periodic maintenance Periodic maintenance overviewCooling system maintenance schedule Qualified personnelLeak detection maintenance Humidifier if installed ECSElectrical POD Shut Down RequiredFire alarm and suppression system VesdaLife safety HP POD 40c NA structureAccess control Third-party componentsPeriodic maintenance General specifications SpecificationsElectrical specifications Water specifications Rack specificationsEnvironmental specifications Thermal and air flow performanceOptional features specifications Before you contact HP Contacting HPHP contact information Warranty information Safety and regulatory complianceRegulatory information Glossary AHJPDU Documentation feedback Index Temperature sensor