Fire alarm panel connections
The electrical layout of the fire alarm system is as described in the schematic drawing supplied with the HP POD 40c NA.
Water specifications
The following table describes the chilled water system specifications for the HP POD 40c NA.
Feature | Specification |
|
|
Facility input temperature to the HP POD | 12ºC to 24ºC (55ºF to 75ºF) |
40c NA |
|
Working pressure | 1,034 kPa (150 psi) |
HP POD 40c NA pressure drop | 172.4 kPa (25 psi) |
HP POD 40c NA water flow rate | 908.5 lpm (240 gpm) |
Chilled water supply and return | • North |
connections | flanges |
| • |
|
|
Rack specifications
Standard HP POD 40c NA racks (AT978A)
Feature | Specification |
|
|
U height | 50U |
Width | 54.6 cm (21.5 in) |
Depth | 99 cm (39 in)* |
Maximum load weight | 1,360.7 kg (3,000 lb) |
*This specification indicates the maximum clearance for the cold aisle. Equipment cannot exceed this measurement.
Thermal and air flow performance
Maximum thermal and air flow | HP POD 40c NA specification |
performance parameters |
|
|
|
Air | Dependent on IT configuration and chilled water inlet temperature |
components) |
|
Chilled water temperature | 12°C to 24°C (55°F to 75°F) |
Total | Variable as required to maintain the hot aisle setpoint temperature |
| and dependent on IT configuration |
Heat rejection capacity | 600 kW |
Environmental specifications
Feature | Specification |
|
|
Operating temperature |