4.Secure the busway drop box to the retaining hardware bracket by using a socket wrench to insert and tighten a bolt (4).
5.Connect the PDUs to the busway drop box (1).
6.Turn the power on by closing both breakers on the busway drop box (2).
Differential pressure sensor
The differential pressure sensors are located in the cold aisle.
You need a screwdriver for installation.
Removal and replacement procedures 20