Component to be inspected

Task

Frequency

Capable Party

 

 

 

 

Circuit breakers

Panel breaker operational test

Annually

Licensed electrician

 

(open and shut).

 

 

LLS inspection of breakers,

Quarterly

Licensed

 

disconnects, motor starters, and

 

electrician/Qualified

 

fuse holders (physical).

 

personnel

 

 

 

 

Breaker fault testing for all

Every 3 years

Third party testing

 

breakers ≥ 250AF

 

facility

 

 

 

 

Sensors

Verify proper operation of:

Annually

Qualified personnel

 

Internal POD temperature

 

 

 

 

sensors (thermometer)

 

 

 

Relative humidity sensors (RH

 

 

 

 

meter)

 

 

 

(Investigate discrepancies, trouble

 

 

 

shoot, and replace as necessary.)

 

 

Compare the following with site

Annually

Qualified personnel

 

indications (if available):

 

 

 

CWS/CWR temperature

 

 

 

CWS/CWR pressure

 

 

 

Flow rate (if possible)

 

 

 

(Investigate discrepancies, trouble

 

 

 

shoot, and replace as necessary.)

 

 

POD SHUT DOWN REQUIRED

Annually

Qualified personnel

 

Calibrate (zero out) POD

 

 

 

differential pressure sensors.

 

 

 

(Investigate discrepancies, trouble

 

 

 

shoot, and replace as necessary.)

 

 

Lighting

Visual inspection of lighting

As needed or

Licensed electrician/

 

fixtures and lamps. Replace

Quarterly

Qualified personnel

 

components upon failure.

 

 

Fire alarm and suppression system

Component to be inspected

Task

Frequency

Capable Party

 

 

 

 

 

 

Full system functional check

Inspect and perform a functional

As required by

Authorized technician

 

 

check of the system

local code

 

 

Fire panel

Inspect and test fire panel

Every 2 years

Authorized technician

 

 

battery backup system

 

 

 

VESDA

Inspect and test VESDA power

Quarterly

Authorized technician

 

 

supply

 

 

 

Inspect the VESDA pipe network

Every 2 years

Authorized technician

 

Inspect the VESDA filter.

Annually

Qualified personnel

 

 

Replace as necessary

 

 

 

Conduct a VESDA pipe integrity

Annually

Authorized technician

 

 

smoke test

 

 

 

Check the VESDA pipe flow

Annually

Authorized technician

 

Clean the VESDA sampling

Every 2 years

Authorized technician

 

 

points

 

 

 

Flush the VESDA pipe network

Every 2 years

Authorized technician

 

VESDA system air

As required by

Authorized technician

 

 

sampling/smoke test

local code

 

 

 

 

 

Periodic maintenance 66

Image 66
Contents Abstract Page Contents Periodic maintenance Contacting HP Illustrated parts catalog Structural component identificationParts and part number identification Life safety component identification Electrical power component identification Component DescriptionExternal panel labels Front view shown Callout Electrical safety label Description Electrical safety label Description Control cabinet component identificationCooling system component identification HP POD 40c NA racksAisle clearances Cold aisle clearanceReplaceable components Hot aisle clearanceRemoval and replacement procedures Safety considerationsOperator safety Fire detection and suppression Air filterRemoving the air filter Replacing the air filter Busway drop box Removing the busway drop boxReplacing the busway drop box Differential pressure sensor Removing the differential pressure sensor Replacing the differential pressure sensorDoor position contact Removing the door position contactReplacing the door position contact Drain pan sensor Removing the drain pan sensorReplacing the drain pan sensor Removal and replacement procedures ECS touchscreen Removing the ECS touchscreenEPO button Replacing the ECS touchscreenRemoving the EPO button Replacing the EPO button EPO LED indicators Removing the EPO LED indicatorReplacing the EPO LED indicator EPO thermister Removing the EPO thermisterReplacing the EPO thermister External chilled water flow actuator Removing the external chilled water flow actuatorRemoval and replacement procedures External chilled water flow valve Replacing the external chilled water flow actuatorExternal pressure gauge isolation valve Removing the external chilled water flow valveReplacing the external chilled water flow valve Fan Removing the external pressure gauge isolation valveReplacing the external pressure gauge isolation valve Removing the fan Replacing the fan Fan bank Removing the fan bankReplacing the fan bank Fire strobe light Removing the fire strobe lightHumidifier Replacing the fire strobe lightRemoving the humidifier Removal and replacement procedures Replacing the humidifier Humidistat Removing the humidistatReplacing the humidistat Removal and replacement procedures Humidity sensor Removing the humidity sensorRemoval and replacement procedures Replacing the humidity sensor LED light Removing the LED lightTemperature sensor cold aisle Replacing the LED lightRemoving the cold aisle temperature sensor Replacing the cold aisle temperature sensor Temperature sensor hot aisle Removing the hot aisle temperature sensorRemoval and replacement procedures Replacing the hot aisle temperature sensor Vesda filter Removing the Vesda filterReplacing the Vesda filter Cooling system maintenance schedule Periodic maintenancePeriodic maintenance overview Qualified personnelLeak detection maintenance Humidifier if installed ECSElectrical POD Shut Down RequiredFire alarm and suppression system VesdaLife safety HP POD 40c NA structureAccess control Third-party componentsPeriodic maintenance Specifications General specificationsElectrical specifications Environmental specifications Water specificationsRack specifications Thermal and air flow performanceOptional features specifications Contacting HP Before you contact HPHP contact information Safety and regulatory compliance Warranty informationRegulatory information Glossary AHJPDU Documentation feedback Index Temperature sensor