Toshiba RAV-SP240CT-UL „Evacuation, Tightening connection, Refrigerant amount to be added

Page 13
Tightening connection

Under Ceiling Type

Installation Manual

Tightening connection

▼Tightening torque of flare pipe connections CAUTION

Do not apply excessive torque. Otherwise, the nut may crack depending on the conditions.

 

(Unit: ft•lbs (N•m))

Outer dia. of copper

Tightening torque

pipe

 

1/4” (6.4 mm)

10 -13 (14 - 18)

 

 

3/8” (9.5 mm)

24 - 31 (33 - 42)

 

 

1/2” (12.7 mm)

37 - 46 (50 - 62)

 

 

5/8” (15.9 mm)

46 - 57 (63 - 77)

 

 

Tightening torque of flare pipe connections

Pressure of R410A is higher than that of R22.

„Evacuation

Using a vacuum pump, perform vacuuming from the charge port of valve of the outdoor unit.

For details, follow to the Installation Manual attached to the outdoor unit.

Never use the refrigerant sealed in the outdoor unit for air purge.

REQUIREMENT

For the tools such as charge hose, etc., use those manufactured exclusively for R410A.

Refrigerant amount to be added

For addition of the refrigerant, add refrigerant “R410A” referring to the attached Installation Manual of outdoor

(Approx. 1.6 times) Therefore, using a torque wrench, tighten the flare pipe connecting sections which connect the indoor and outdoor units of the specified tightening torque.

Incorrect connections may cause not only a gas leak, but also a trouble of the refrigeration cycle.

Flare at indoor „Evacuation unit side

Refrigerant amount to be added Flare at Piping with outdoor unitOpen the valve fully outdoor unit side

unit.

Be sure to use a scale to charge the refrigerant of specified amount.

REQUIREMENT

Charging an excessive or too little amount of

 

refrigerant causes a trouble of the compressor.

 

Be sure to charge the refrigerant of specified

 

amount.

A personnel who charged the refrigerant should

 

write down the pipe length and the added

Align the centres of the connecting pipes and tighten the flare nut as far as possible with your fingers. Then tighten the nut with a spanner and torque wrench as shown in the figure.

Half union Gas leak check– 12 –Manual backgroundManual backgroundFlare nut

Externally

Internally

threaded side

threaded side

Use a wrench to secure.

Use a torque wrench to tighten.

REQUIREMENT

Tightening with an excessive torque may crack the nut depending on installation conditions.

Tighten the nut within the specified tightening torque.

Piping with outdoor unit

Shape of valve differs according to the outdoor unit. For details of installation, refer to the Installation Manual of the outdoor unit.

refrigerant amount in the nameplate attached to the

service panel of the outdoor unit. It is necessary to

troubleshooter the compressor and refrigeration

cycle malfunction.

Open the valve fully

Open the valve of the outdoor unit fully.

For details, refer to the Installation Manual attached to the outdoor unit.

Gas leak check

Check with a leak detector or soap water whether gas leaks or not, from the pipe connecting section or cap of the valve.

REQUIREMENT

Use a leak detector manufactured exclusively for HFC refrigerant (R410A, R134a, etc.).

EN

– 12 –

12-EN

Image 13
Contents RAV-SP180CT-UL RAV-SP240CT-UL RAV-SP300CT-UL AIR CONDITIONER SPLIT TYPERAV-SP360CT-UL RAV-SP420CT-UL EnglishADOPTION OF NEW REFRIGERANT Contents„Accessory parts 1 ACCESSORY PARTSUnder Ceiling Type Under Ceiling Type 2 PRECAUTIONS FOR SAFETYUnder Ceiling Type „Installation space 3 SELECTION OF INSTALLATION PLACE„Height of ceiling Avoid installing in the following places„Before installation „Wireless remote control2 Removing wire guard Under Ceiling TypeInstallation Manual3 Removal of side panel „External view4 Removal of protective vinyl 5 Removal of protectorUnder Ceiling Type Installation Manual Unit in mm„Draw-outdirection of pipe/ wire „Installation of hanging bolts„Pipe knockout hole Using attached installation pattern„Installation of remote control Sold separately „Installation of indoor unitInstallation Manual There is ceiling material„Refrigerant Piping 4 REFRIGERANT PIPING AND EVACUATING„Pipe size „Permissible Piping Length and Height DifferenceTightening connection „EvacuationRefrigerant amount to be added Piping with outdoor unitUnder Ceiling Type Thermal insulation processREQUIREMENT „Piping/Heat insulating material 5 DRAIN PIPING WORK„Drain up Under Ceiling Type„Thermal insulating process „Connection of drain hose„Connection of drain pipe Under Ceiling TypeRemote control wiring 6 ELECTRICAL CONNECTIONWiring Under Ceiling TypeUnder Ceiling Type Under Ceiling Type „Wire connectionREQUIREMENT Connected at upside Connected at backsideUnder Ceiling Type 19-EN„Remote Control Wiring „System interconnection Wires and Ground Wire„Wiring Diagram Single system7 APPLICABLE CONTROLS „Changing applicable control settingProcedure Procedure„Using wireless remote control „Installation to high ceiling1 → 2 → 3 → 4 → 5 → Procedure„To secure better effect of heating „Filter sign setting„Group control Procedure exampleProcedure ProcedureProcedure ProcedureProcedure ProcedureProcedure ProcedureInstallation Manual „Remote control switch monitoring functionUnder Ceiling Type 2, 4 1,5 8 TEST RUN„Before test run „Execute a test runProcedure Wireless remote controlProcedure Procedure„Confirmation of error history 9 TROUBLESHOOTING„Confirmation and check ProcedureUnder Ceiling Type „Check codes and parts to be checked30-EN 31-EN Under Ceiling Type32-EN Under Ceiling TypeEH99864801