Under Ceiling Type | Installation Manual |
System interconnection Wires and Ground Wire
1. Strip wire ends. |
System interconnection wire : 0.4” (10 mm). |
Ground wire : 0.8” (20 mm) |
Remote Control Wiring
•Strip off approx. 0.4” (9 mm) the wire to be connected.
•Non polarity, 2 x AWG20 wire is used for wiring of the remote control.
2. | Match wire colours with terminal numbers on indoor |
| and outdoor units’ terminal blocks and firmly screw |
| wires to the corresponding terminals. |
3. | Secure the ground wire with the ground screw. |
4. | Fix the wire with cord clamp. |
Unit: in (mm)
Terminal block for remote control wiring of indoor unit
A
B
Remote control wire (Procured locally)
Terminal block
A | Remote | |
control | ||
B | ||
unit | ||
|
L1 L2 S
0.8” (20)
Wiring Diagram
0.4” (10)
Connecting wire
Ground wire
▼Single system
Low voltage
Indoor unit
A B
L1 L2 S
High voltage
L1 L2 S
CAUTION
• Firmly tighten the screws of the terminal block.
Keep the wire length as shown in figure below when it is connected to the terminal block.
0.08” (2 mm) or less
System interconnection wire
Remote Outdoor
control unit
EN |
– 20 – |