Procedure 1
Push simultaneously + + buttons for 4 seconds or more. After a while, the display part flashes as shown below. Check the displayed CODE No. is [10].
•When the CODE No. is other than [10], push button to erase the display and repeat procedure from the first step.
(After pushing button, operation of the remote control is not accepted for approx. 1 minute.) (For a group control, No. of the firstly displayed indoor unit becomes the header unit.)
(* Display changes according to the model No. of indoor unit.)
Procedure 2
Every pushing button, the indoor UNIT No. in the group control is displayed in order. Select the indoor unit of which setup is changed.
In this time, the position of the indoor unit of which setup is changed can be confirmed because fan and louver of the selected indoor unit operate.
Procedure 3
1.Using temp. setup / buttons, specify CODE No. [12].
(CODE No. [12]: Line address)
2.Using timer time / buttons, change the line address from [3] to [2].
3.Push button.
In this time, the setup finishes when the display changes from flashing to lighting.
Indoor UNIT No. before setup change is displayed.
Procedure 4
1.Using temp. setup / buttons, specify CODE No. [13].
(CODE No. [13]: Indoor address)
2.Using timer time / buttons, change the indoor address from [3] to [2].
3.Push button.
In this time, the setup finishes when the display changes from flashing to lighting.
Indoor UNIT No. before setup change is displayed.
Procedure 5
1.Using temp. setup / buttons, specify CODE No. [14].
(CODE No. [14]: Group address)
2.Using timer time / buttons, change the setup data from [0001] to [0002].
(Setup data [Header unit: 0001] [Follower unit: 0002])
3.Push button.
In this time, the setup finishes when the display changes from flashing to lighting.
Indoor UNIT No. before setup change is displayed.