Toshiba RAV-SP300CT-UL „Connection of drain hose, „Thermal insulating process, Under Ceiling Type

Page 16
„Connection of drain hose

Under Ceiling Type

Installation Manual

„Connection of drain hose

Insert the attached drain hose into the drain pipe connecting port on the drain pan up to the end.

Fit the attached hose band to the end of the pipe connecting port, and then tighten it securely.

REQUIREMENT

Be sure to fix the drain hose with the attached hose band, and set the tightening position upward.

As the draining is the natural water draining, arrange the pipe outside of the unit on the down slope.

If piping is performed as shown in the figure, drain cannot be discharged.

NO GOOD Refrigerant pipe

Drain pipe

Drain pipe

Fit the attached hose band to the end of the hose, lay down the knob, and then tighten hose band.

Drain pan

Attached drain hose

Confirm that soft hose is pushed in up to the end of the drain pan.

„Thermal insulating process

Using the attached drain hose thermal insulator, lap the connecting section and the drain hose without clearance, and then tighten with two handing band so that thermal insulator does not open.

Covering the attached drain hose thermal insulator, lap the thermal insulator (procured locally) to the drain pipe without clearance.

Lap covering connecting section

Thermal insulator

between drain pan and drain hose.

 

(procured locally)

Drain hose

 

 

Drain

 

 

pan

 

 

Hose band Banding band Hose band

Lap the attached

 

 

thermal insulation

Attached thermal insulator

 

so that the one

 

end is put on the

 

 

* Tighten the banding band so that

 

other end at the

 

upper side.

attached thermal insulator is not

 

 

 

pushed excessively.

 

 

„Connection of drain pipe

Connect the hard vinyl chloride pipe (procured locally) to the mounted drain hose which was attached.

Piping from left side

In case of taking pipe from the left side, exchange the plug from left to right. Push in the plug of which end is not sharp up to the end.

Drain pan

Plug

15-EN

– 15 –

Image 16
Contents AIR CONDITIONER SPLIT TYPE RAV-SP180CT-UL RAV-SP240CT-UL RAV-SP300CT-ULRAV-SP360CT-UL RAV-SP420CT-UL EnglishContents ADOPTION OF NEW REFRIGERANT„Accessory parts 1 ACCESSORY PARTSUnder Ceiling Type 2 PRECAUTIONS FOR SAFETY Under Ceiling TypeUnder Ceiling Type 3 SELECTION OF INSTALLATION PLACE „Installation space„Height of ceiling Avoid installing in the following places„Wireless remote control „Before installation2 Removing wire guard Under Ceiling TypeInstallation Manual„External view 3 Removal of side panel4 Removal of protective vinyl 5 Removal of protectorInstallation Manual Unit in mm Under Ceiling Type„Installation of hanging bolts „Draw-outdirection of pipe/ wire„Pipe knockout hole Using attached installation pattern„Installation of indoor unit „Installation of remote control Sold separatelyInstallation Manual There is ceiling material4 REFRIGERANT PIPING AND EVACUATING „Refrigerant Piping„Pipe size „Permissible Piping Length and Height Difference„Evacuation Tightening connectionRefrigerant amount to be added Piping with outdoor unitUnder Ceiling Type Thermal insulation processREQUIREMENT 5 DRAIN PIPING WORK „Piping/Heat insulating material„Drain up Under Ceiling Type„Connection of drain hose „Thermal insulating process„Connection of drain pipe Under Ceiling Type6 ELECTRICAL CONNECTION Remote control wiringWiring Under Ceiling TypeUnder Ceiling Type Under Ceiling Type „Wire connectionREQUIREMENT Connected at backside Connected at upsideUnder Ceiling Type 19-EN„System interconnection Wires and Ground Wire „Remote Control Wiring„Wiring Diagram Single system„Changing applicable control setting 7 APPLICABLE CONTROLSProcedure Procedure„Installation to high ceiling „Using wireless remote control1 → 2 → 3 → 4 → 5 → Procedure„Filter sign setting „To secure better effect of heating„Group control Procedure exampleProcedure ProcedureProcedure ProcedureProcedure ProcedureProcedure ProcedureInstallation Manual „Remote control switch monitoring functionUnder Ceiling Type 8 TEST RUN 2, 4 1,5„Before test run „Execute a test runWireless remote control ProcedureProcedure Procedure9 TROUBLESHOOTING „Confirmation of error history„Confirmation and check ProcedureUnder Ceiling Type „Check codes and parts to be checked30-EN Under Ceiling Type 31-ENUnder Ceiling Type 32-ENEH99864801