9 TROUBLESHOOTING

Under Ceiling Type

Installation Manual

9 TROUBLESHOOTING

„Confirmation and check

When a trouble occurred in the air conditioner, the check code and the indoor UNIT No. appear on the display part of the remote control.

The check code is only displayed during the operation. If the display disappears, operate the air conditioner according to the following “Confirmation of error history” for confirmation.

Check code

Indoor UNIT No. in

 

which an error occurred

„Confirmation of error history

When a trouble occurred on the air conditioner, the trouble history can be confirmed with the following procedure. (The trouble history is stored in memory up to 4 troubles.)

The history can be confirmed from both operating status and stop status.

Procedure 2

Every pushing of „Confirmation and check„Confirmation of error history– 29 – button used to set temperature, the trouble history stored in memory is displayed in order.

The numbers in CODE No. indicate CODE No. [01] (latest) [04] (oldest).

REQUIREMENT

Do not push Manual background button because all the trouble history of the indoor unit will be deleted.

Procedure 3

After confirmation, push Manual backgroundManual background button to return to the usual display.

1.Check the troubles according to the above procedure.

2.Ask an authorized dealer or qualified service (maintenance) professional to repair or maintain the air conditioner.

2

 

3

1

Procedure 1

When pushing Manual backgroundManual background and Manual backgroundManual background buttons at the same time for 4 seconds or more, the following display appears.

If [Service check] Manual background is displayed, the mode enters in the trouble history mode.

[01: Order of trouble history] is displayed in CODE No. window.

[Check code] is displayed in CHECK window.

[Indoor unit address in which an error occurred] is displayed in Unit No..

29-EN

– 29 –

Image 30
Contents RAV-SP360CT-UL RAV-SP420CT-UL AIR CONDITIONER SPLIT TYPERAV-SP180CT-UL RAV-SP240CT-UL RAV-SP300CT-UL EnglishContents ADOPTION OF NEW REFRIGERANT1 ACCESSORY PARTS „Accessory partsUnder Ceiling Type 2 PRECAUTIONS FOR SAFETY Under Ceiling TypeUnder Ceiling Type „Height of ceiling 3 SELECTION OF INSTALLATION PLACE„Installation space Avoid installing in the following places2 Removing wire guard „Wireless remote control„Before installation Under Ceiling TypeInstallation Manual4 Removal of protective vinyl „External view3 Removal of side panel 5 Removal of protectorInstallation Manual Unit in mm Under Ceiling Type„Pipe knockout hole „Installation of hanging bolts„Draw-outdirection of pipe/ wire Using attached installation patternInstallation Manual „Installation of indoor unit„Installation of remote control Sold separately There is ceiling material„Pipe size 4 REFRIGERANT PIPING AND EVACUATING„Refrigerant Piping „Permissible Piping Length and Height DifferenceRefrigerant amount to be added „EvacuationTightening connection Piping with outdoor unitThermal insulation process Under Ceiling TypeREQUIREMENT „Drain up 5 DRAIN PIPING WORK„Piping/Heat insulating material Under Ceiling Type„Connection of drain pipe „Connection of drain hose„Thermal insulating process Under Ceiling TypeWiring 6 ELECTRICAL CONNECTIONRemote control wiring Under Ceiling TypeUnder Ceiling Type „Wire connection Under Ceiling TypeREQUIREMENT Under Ceiling Type Connected at backsideConnected at upside 19-EN„Wiring Diagram „System interconnection Wires and Ground Wire„Remote Control Wiring Single systemProcedure „Changing applicable control setting7 APPLICABLE CONTROLS Procedure1 → 2 → 3 → 4 → 5 → „Installation to high ceiling„Using wireless remote control Procedure„Group control „Filter sign setting„To secure better effect of heating Procedure exampleProcedure ProcedureProcedure ProcedureProcedure ProcedureProcedure Procedure„Remote control switch monitoring function Installation ManualUnder Ceiling Type „Before test run 8 TEST RUN2, 4 1,5 „Execute a test runProcedure Wireless remote controlProcedure Procedure„Confirmation and check 9 TROUBLESHOOTING„Confirmation of error history Procedure„Check codes and parts to be checked Under Ceiling Type30-EN Under Ceiling Type 31-ENUnder Ceiling Type 32-ENEH99864801