Toshiba RAV-SP360CT-UL Wireless remote control, Procedure, Cooling test run, Heating test run

Page 29
Wireless remote control

Under Ceiling Type

Installation Manual

Wireless remote control

Procedure 1

Turn on the circuit breaker of the air conditioner. The operation is not accepted for 5 minutes when circuit breaker is turned on at first time after installation, and 1 minute when circuit breaker is turned on at the next time and after. After the specified time has passed, perform a test operation.

Procedure 2

Push “ON/OFF” button on the remote control, select [COOL] or [HEAT] with “MODE” button, and then select [HIGH] with “FAN” button.

Procedure 3

Cooling test run

Heating test run

 

 

Set the temperature to 64°F

Set the temperature to 86 °F

(18°C) with the temp. setup

(30°C) with the temp. setup

buttons.

buttons.

Procedure 4

Cooling test run

Heating test run

 

 

After confirming a signal

After confirming a signal

receiving sound “beep”

receiving sound “beep”

immediately set the

immediately set the

temperature to 66 °F (19°C)

temperature to 84 °F (29°C)

with the temp. setup buttons.

with the temp. setup buttons.

Procedure 5

Cooling test run

Heating test run

 

 

After confirming a signal

After confirming a signal

receiving sound “beep”

receiving sound “beep”

immediately set the

immediately set the

temperature to 64 °F (18°C)

temperature to 86 °F (30°C)

with the temp. setup buttons.

with the temp. setup buttons.

Procedure 6

Repeat procedures 4 5 4 5.

Indicators “Operation” (green), “Timer” (green), and “Ready” (orange) in the wireless receiver section flash in approx. 10 seconds, and the air conditioner starts operation. If any of these indicators does not flash, repeat procedures

2 to 5.

Procedure 7

Upon completion of the test run, push “ON/OFF” button to stop operation.

<Overview of test run operations using the wireless remote control>

Cooling test run:

ON/OFF 64 °F (18 °C) 66 °F (19°C) 64 °F (18°C) 66 °F (19°C) 64 °F (18°C) 66 °F (19°C)

64 °F (18°C) (test run) ON/OFF

Heating test run:

ON/OFF 86 °F (30°C) 84 °F (29°C) 86 °F (30°C) 84 °F (29°C) 86 °F (30°C) 84 °F (29°C)

86 °F (30°C) (test run) ON/OFF

Always select

 

[HIGH] fan

 

speed.

3, 4,

2

2

5, 6

2,7

 

EN

– 28 –

28-EN

Image 29
Contents RAV-SP180CT-UL RAV-SP240CT-UL RAV-SP300CT-UL AIR CONDITIONER SPLIT TYPERAV-SP360CT-UL RAV-SP420CT-UL EnglishADOPTION OF NEW REFRIGERANT ContentsUnder Ceiling Type 1 ACCESSORY PARTS„Accessory parts Under Ceiling Type 2 PRECAUTIONS FOR SAFETYUnder Ceiling Type „Installation space 3 SELECTION OF INSTALLATION PLACE„Height of ceiling Avoid installing in the following places„Before installation „Wireless remote control2 Removing wire guard Under Ceiling TypeInstallation Manual3 Removal of side panel „External view4 Removal of protective vinyl 5 Removal of protectorUnder Ceiling Type Installation Manual Unit in mm„Draw-outdirection of pipe/ wire „Installation of hanging bolts„Pipe knockout hole Using attached installation pattern„Installation of remote control Sold separately „Installation of indoor unitInstallation Manual There is ceiling material„Refrigerant Piping 4 REFRIGERANT PIPING AND EVACUATING„Pipe size „Permissible Piping Length and Height DifferenceTightening connection „EvacuationRefrigerant amount to be added Piping with outdoor unitREQUIREMENT Thermal insulation processUnder Ceiling Type „Piping/Heat insulating material 5 DRAIN PIPING WORK„Drain up Under Ceiling Type„Thermal insulating process „Connection of drain hose„Connection of drain pipe Under Ceiling TypeRemote control wiring 6 ELECTRICAL CONNECTIONWiring Under Ceiling TypeUnder Ceiling Type REQUIREMENT „Wire connectionUnder Ceiling Type Connected at upside Connected at backsideUnder Ceiling Type 19-EN„Remote Control Wiring „System interconnection Wires and Ground Wire„Wiring Diagram Single system7 APPLICABLE CONTROLS „Changing applicable control settingProcedure Procedure„Using wireless remote control „Installation to high ceiling1 → 2 → 3 → 4 → 5 → Procedure„To secure better effect of heating „Filter sign setting„Group control Procedure exampleProcedure ProcedureProcedure ProcedureProcedure ProcedureProcedure ProcedureUnder Ceiling Type „Remote control switch monitoring functionInstallation Manual 2, 4 1,5 8 TEST RUN„Before test run „Execute a test runProcedure Wireless remote controlProcedure Procedure„Confirmation of error history 9 TROUBLESHOOTING„Confirmation and check Procedure30-EN „Check codes and parts to be checkedUnder Ceiling Type 31-EN Under Ceiling Type32-EN Under Ceiling TypeEH99864801