5 DRAIN PIPING WORK

Under Ceiling Type

Installation Manual

5 DRAIN PIPING WORK

„Piping/Heat insulating material CAUTION

Following the Installation Manual, perform the drain piping work so that water is properly drained, and apply a heat insulation so as not to cause a dew dropping.

Inappropriate piping work may result in water leakage in the room and wet of furniture.

„Piping/Heat insulating material

Require the following materials for piping and heat insulating at site.

Piping

Hard vinyl chloride pipe VP20

(Outer dia.: Ø1.0” (26 mm))

 

 

 

Heat insulator

Foam polyethylene:

Thickness 0.4” (10 mm) or more

 

REQUIREMENT

Be sure to perform heat insulation of the drain pipes of the indoor unit.

Never forget to perform heat insulation of the connecting part with the indoor unit.

An incomplete heat insulation causes dew dropping.

Set the drain pipe with downward slope (1/100 or more), and do not make swelling or trap on the piping. It may cause an abnormal sound.

For length of the traversing drain pipe, restrict 65’7” (20 m) or less.

In case of a long pipe, provide support brackets with interval of 4’11” - 6’7” (1.5 - 2 m) in order to prevent waving.

4’11” - 6’7” (1.5 - 2 m)

Support

 

bracket

1/100 or more

 

downward

 

Thermal insulator

 

Arched shape

NO

 

GOOD

Trap

 

Set the collective piping as shown in the below figure.

As long as possible (3.9” (100 mm))

VP20 VP20 VP20

 

 

Extended

 

 

ventilating

VP30 or more

Downward slope

pipe

 

1/100 or more

 

<Collective piping>

Be sure not to apply force to the connecting part of the drain pipe.

The hard vinyl-chloride pipe cannot be directly connected to the drain pipe connecting port of the indoor unit.

For connection with the drain pipe connecting port, be sure to use/fix the attached flexible hose with the hose band, otherwise a damage or water leak is caused on the drain pipe connecting port.

Drain pipe connecting

 

 

Attached flexible hose

 

port (Hard socket)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Attached hose band

 

 

Attached hose band

 

 

 

 

 

 

 

 

Drain pan

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Soft socket

 

 

Soft socket

 

 

 

 

 

 

 

 

 

 

 

Adhesive agent

 

 

 

 

 

 

 

 

VP20 vinyl chloride pipe

prohibited

 

 

 

(procured locally)

 

 

 

 

 

 

 

 

 

Adhesive inhibited:

Use the attached flexible hose and hose band for connecting the drain hose to the clear drain socket. If applying the adhesive, socket will be damaged and cause water leakage.

„Drain up

When not securing down slope on the drain pipe, use a Drain pump kit sold separately.

Also refer to the “Drain pump kit installation manual”. The drain pipe can be raised 23.6” (600 mm) from the top face of the main unit.

*When using Drain pump kit, both drain pipe and refrigerant pipe can be taken only from upper side.

*VP25 PVC pipe is needed when a drain pump is used.

EN

– 14 –

14-EN

Image 15
Contents English AIR CONDITIONER SPLIT TYPERAV-SP180CT-UL RAV-SP240CT-UL RAV-SP300CT-UL RAV-SP360CT-UL RAV-SP420CT-ULADOPTION OF NEW REFRIGERANT Contents1 ACCESSORY PARTS „Accessory partsUnder Ceiling Type Under Ceiling Type 2 PRECAUTIONS FOR SAFETYUnder Ceiling Type Avoid installing in the following places 3 SELECTION OF INSTALLATION PLACE„Installation space „Height of ceilingUnder Ceiling TypeInstallation Manual „Wireless remote control„Before installation 2 Removing wire guard5 Removal of protector „External view3 Removal of side panel 4 Removal of protective vinylUnder Ceiling Type Installation Manual Unit in mmUsing attached installation pattern „Installation of hanging bolts„Draw-outdirection of pipe/ wire „Pipe knockout holeThere is ceiling material „Installation of indoor unit„Installation of remote control Sold separately Installation Manual„Permissible Piping Length and Height Difference 4 REFRIGERANT PIPING AND EVACUATING„Refrigerant Piping „Pipe sizePiping with outdoor unit „EvacuationTightening connection Refrigerant amount to be addedThermal insulation process Under Ceiling TypeREQUIREMENT Under Ceiling Type 5 DRAIN PIPING WORK„Piping/Heat insulating material „Drain upUnder Ceiling Type „Connection of drain hose„Thermal insulating process „Connection of drain pipeUnder Ceiling Type 6 ELECTRICAL CONNECTIONRemote control wiring WiringUnder Ceiling Type „Wire connection Under Ceiling TypeREQUIREMENT 19-EN Connected at backsideConnected at upside Under Ceiling TypeSingle system „System interconnection Wires and Ground Wire„Remote Control Wiring „Wiring DiagramProcedure „Changing applicable control setting7 APPLICABLE CONTROLS ProcedureProcedure „Installation to high ceiling„Using wireless remote control 1 → 2 → 3 → 4 → 5 →Procedure example „Filter sign setting„To secure better effect of heating „Group controlProcedure ProcedureProcedure ProcedureProcedure ProcedureProcedure Procedure„Remote control switch monitoring function Installation ManualUnder Ceiling Type „Execute a test run 8 TEST RUN2, 4 1,5 „Before test runProcedure Wireless remote controlProcedure ProcedureProcedure 9 TROUBLESHOOTING„Confirmation of error history „Confirmation and check„Check codes and parts to be checked Under Ceiling Type30-EN 31-EN Under Ceiling Type32-EN Under Ceiling TypeEH99864801