Toshiba HFC R-410A manual Equipment selection procedure, Selection flow chart, Capacity code

Page 19

4.Equipment selection procedure

1. Selection flow chart

1. Determination of indoor air conditioning load

2. Preliminary selection of indoor units

3. Preliminary selection of outdoor unit with indoor units

4. Capacity correction for piping length/height between indoor and outdoor units

5. Capacity correction based on indoor and outdoor temperature

6. Validate preliminary selection of indoor units

No

7. Confirmation of selection for indoor unit and outdoor units

End

2. Indoor unit and outdoor unit combination

For indoor unit, the capacity code is decided for each model size.

Model size

007

009

012

015

018

024

027

030

036

048

056

072

096

Cooling capacity, kW

2.2

2.8

3.6

4.5

5.6

7.1

8.0

9.0

11.2

14.0

16.0

22.4

28.0

Capacity code

0.8

1

1.25

1.7

2

2.5

3

3.2

4

5

6

8

10

Note: Model size: corresponding to Btu/h. Capacity code: corresponding to horsepower.

For outdoor unit, maximum number of connectable indoor units and total capacity code of indoor units are decided.

Outdoor unit

Outdoor unit

Capacity code

Max. No. of

Total indoor unit

(cooling only)

(heat pump)

of outdoor unit

indoor units

capacity code

MMY-MAP0501T8

MMY-MAP0501HT8

5

8

2.5 to 6.75

MMY-MAP0601T8

MMY-MAP0601HT8

6

10

3 to 8.1

MMY-MAP0801T8

MMY-MAP0801HT8

8

13

4 to 10.8

MMY-MAP1001T8

MMY-MAP1001HT8

10

16

5 to 13.5

MMY-MAP1201T8

MMY-MAP1201HT8

12

20

6 to 16.2

MMY-AP1401T8

MMY-AP1401HT8

14

23

7 to 18.9

MMY-AP1601T8

MMY-AP1601HT8

16

27

8 to 21.6

MMY-AP1801T8

MMY-AP1801HT8

18

30

9 to 24.3

MMY-AP2001T8

MMY-AP2001HT8

20

33

10 to 27.0

MMY-AP2201T8

MMY-AP2201HT8

22

37

11 to 29.7

MMY-AP2211T8

MMY-AP2211HT8

22

37

11 to 29.7

MMY-AP2401T8

MMY-AP2401HT8

24

40

12 to 32.4

MMY-AP2411T8

MMY-AP2411HT8

24

40

12 to 32.4

MMY-AP2601T8

MMY-AP2601HT8

26

43

13 to 35.1

MMY-AP2801T8

MMY-AP2801HT8

28

47

14 to 37.8

MMY-AP3001T8

MMY-AP3001HT8

30

48

15 to 40.5

MMY-AP3201T8

MMY-AP3201HT8

32

48

16 to 43.2

MMY-AP3211T8

MMY-AP3211HT8

32

48

16 to 43.2

MMY-AP3401T8

MMY-AP3401HT8

34

48

17 to 45.9

MMY-AP3411T8

MMY-AP3411HT8

34

48

17 to 45.9

MMY-AP3601T8

MMY-AP3601HT8

36

48

18 to 48.6

MMY-AP3611T8

MMY-AP3611HT8

36

48

18 to 48.6

MMY-AP3801T8

MMY-AP3801HT8

38

48

19 to 51.3

MMY-AP4001T8

MMY-AP4001HT8

40

48

20 to 54.0

MMY-AP4201T8

MMY-AP4201HT8

42

48

21 to 56.7

MMY-AP4401T8

MMY-AP4401HT8

44

48

22 to 59.4

MMY-AP4601T8

MMY-AP4601HT8

46

48

23 to 62.1

MMY-AP4801T8

MMY-AP4801HT8

48

48

24 to 64.8

50 to 135% of outdoor unit capacity

19

Image 19
Contents Super Modular Multi Page Super Modular Multi System Contents Outline of Toshiba Super Modular Multi System S-MMS Outdoor unit Indoor unit  Energy saving design  Self-diagnostic system Compact  Largest system capacityBranching joints and headers Summary of system equipmentTechnical specifications outdoor units Technical specifications combination of outdoor unitsRated conditions Outdoor unit model line-up cooling only unitsProduct designation Combined capacity rangeMMY- M AP 000 0 H T Outdoor unit model line-up heat pump unitsTechnical specifications indoor units TCB-AX21U W-E Remote controllerSimplified remote controller Connected to indoor unit Wireless remote controller kit Connected to indoor unitController, wired remote controller Weekly timer RBC-EXW21E Connected to central remoteMaster System legend example 8 hp system Basic system configuration8HP 10HP Hp system10HP 10HP Hp system 10HP 10HP 10HP Outdoor unit Indoor unit Remote controller Capacity code Equipment selection procedureSelection flow chart Indoor unit and outdoor unit combinationCapacity correction value Indoor air wet bulb temperature C  Correction of outdoor unit diversity Capacity correction value Indoor air dry bulb temperature C  Correction of outdoor unit diversity Rated conditions Operating temperature rangeHeating mode Capacity calculation for each indoor unitSelection criteria for each floor Example of equipment selectionOutside view Cooling Heating Procedure and result of equipment selectionAir conditioning load Equipment selection Floor Room No Indoor unit Outdoor unit Model Capacity kW Cooling HeatingLoad in each room Example Equipment selection based on system load profileMMY-AP2801T8 MMY-AP2801HT8 Schematic diagramCheck of concentration limit Refrigerant piping designLine branching system Header branching system Free branching systemSystem restrictions Allowable length/height difference of refrigerant pipingAllowable value Piping section  Pipe size of outdoor unit Table Model name Selection of refrigerant pipingGas side Liquid side Liquid side pipe diameter Charging requirement with additional refrigerantCalculating the amount of additional refrigerant required Charge Cooling onlyGeneral Wiring designOutdoor unit power supply Electrical wiring designControl wiring design Length Control wiring diagramControl wiring between outdoor units L5 Wiring TypeFLA MCA Mocp DesignCombination of outdoor units Heat pump Cooling only Nominal Compressor Fan motor Power supplySingle outdoor unit Heat pump Cooling only Nominal Voltage Range Ph-Hz Min MaxRange of controls to meet various system needs Control via indoor remote controllerControl via the central remote controller ControlsControl by weekly timer Applications for indoor remote controllerBasic function System diagram Model Individual control Two remote controllersFunction of central remote controller Application controls for central remote controllerBasic function System diagram Model Indoor remote controllerTCB-PCNT30TLE AvailableBMS-LSV Application control for networkTCB-1FLN BACnetBMS-TP5120ACE Indoor unit type Accessory name Model Applicable model AccessoriesIndoor unit accessories Remote controllerIndoor units Way ceiling cassettes Technical specificationsRBC-UW136PG RBC-UW266PG RBC-UY135PG RBC-US165PG RBC-US265PG Room thermostatSound pressure level high/medium/low** dBA Fan motor power inputStatic pressure factory setting Static pressure max Indoor units Standard ducted unitsIndoor units High-pressure ducted units Unit weightStatic pressure factory setting Sound power level highRear air inlet Sound power level high/medium/low Lower air inlet Sound power level high/medium/lowIndoor units Slim duct units Indoor units Ceiling-suspended units Indoor units High-wall units 1 Series Indoor units High-wall units 2 Series Indoor units Floor-mounted console units Static pressure Indoor units Concealed chassis unitsIndoor units Floor-mounted cabinet units Outdoor units Outdoor units combination DBA 74.5 DBA 75.0 24.26 Power factor, cooling Operating current, cooling 30.51 258 256 DBA 76.5 77.0 Max. number of connectable indoor units High-pressure switch Power supply ± 10% Ph-Hz 400-3-50 130.0 135.0 MMD-AP0121BH Fan characteristicsCase of square duct flange of discharge section MMD-AP0071BH, AP0091BHMMD-AP0481BH, AP0561BH MMD-AP0241BH, AP0271BHMMD-AP0361BH MMD-AP0301BHMMD-AP0361H High-pressure ducted unitMMD-AP0181H MMD-AP0241H, AP0271HMMD-AP0961H MMD-AP0721HMMD-AP0071SPH, AP0091SPH MMD-AP0121SPH Slim duct unitMMD-AP0151SPH MMD-AP0181SPH MMD-AP0151SPH Slim duct unit with filter attachedMMU-AP0091H to P0561H Dimensional drawingsAll dimensions are given in mm Indoor unit 4-way ceiling cassetteIndoor unit 2-way ceiling cassette All dimensions are given in mm ViewMMU-AP0071WH, AP0091WH, AP0121WH MMU-AP0151WH, AP0181WH, AP0241WH, AP0271WH, AP0301WH View Space required for installation and servicingModel MMU-AP0151WH to AP0181WH MMU-AP0241WH to AP0301WH MMU-AP0481WH MMU-AP0071YH, AP0091YH, AP0121YH Indoor unit 1-way ceiling cassetteView Model MMU AP0151SH, AP0181SH MMU-AP0151SH, AP0181SH, AP0241SHAP0241SH Indoor unit standard ducted unit Indoor unit high-pressure ducted unit View Space required for installation and servicing *1MMD-AP0271H, AP0961H Bottom view excluding filter Indoor unit slim duct unitMMD-AP0071SPH, AP0091SPH, AP0121SPH, AP0151SPH, AP0181SPH Bottom view complete with filterAP0241H to AP0271H Indoor unit ceiling-suspended unitMMC-AP0151H, AP0181H, AP0241H, AP0271H, AP0361H, AP0481H Model MMC AP0151H, AP0181HMMK-AP0071H, AP0091H, AP0121H Indoor unit high-wall unit 1 SeriesMMK-AP0151H, AP0181H MMK-AP0241H MMK-AP0072H, AP0092H, AP0122H Indoor unit high-wall unit 2 SeriesMML-AP0071H, AP0091H, AP0121H, AP0151H, AP0181H, AP0241H Indoor unit floor-mounted console unitAP0151BH, AP0181H Indoor unit concealed chassis unitNo. Name Model MML AP0071BH, AP0091BH, AP0121BHIndoor unit floor-mounted cabinet unit Space required for service For right-hand pipingMMF-AP0151H, AP0181H, AP0241H, AP0271H Refrigerant pipe positions Details of hole for rear piping MMF-AP0361H, AP0481H, AP0561HRemote controller All dimensions are given in mm RBC-EXW21E Wireless remote controller kitWeekly timer TCB-AX21ETCB-IFLN Central remote controllerTCB-SC642TLE LON GatewayBMS-IFLSV1E TCS-Net relay interfaceTouch-screen controller BMS-TP5120ACE BMS-LSV2E Intelligent serverEnergy monitoring relay interface BMS-IFWH3E BMS-IFDD01E Digital I/O relay interfaceWindows-based central controller BMS-LSV Outdoor module Outdoor module Two units connected Unit combination Outdoor module Three units connectedOutdoor unit combination Master unit Slave unit Unit combination Outdoor unit combination Master unit Outdoor module Four units connectedShape branching joint Model Accessory socket x quantityBranch header/branch joint Branch header RBM-HY1043E, HY1083E, HY2043E,HY2083ERBM-BY203E, BY303E RBM-BY53E, BY103EAccessory socket Page Toshiba Air Conditioning