Toshiba HFC R-410A manual Weekly timer RBC-EXW21E Connected to central remote, Master

Page 12

Appearance

Application

Function

Infrared remote controller

Connected to indoor unit

Start/stop

 

 

Mode change

WH-H2UE

 

Temperature adjustment

 

 

• Air flow adjustment (5 steps)

 

 

Clock

 

 

Timer function

 

 

 

- ON/OFF timer (10 min. steps)

 

 

 

- Daily timer

 

 

High power mode

• ECO mode (sleep timer with ECO-logic)

One-touch pre-set memory

Weekly timer RBC-EXW21E

Connected to central remote

• Weekly schedule operation

controller, wired remote controller

 

Setting start/stop times for each day

 

 

 

of the week

 

 

ON/OFF can be set 3 times a day.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Press ‘CHECK’ ‘PROGRAM’ ‘DAY’

Wired remote

Weekly

button for easy program copying.

Two schedules a week can be

controller

timer

specified (summer/winter schedule).

 

 

Press ‘CANCEL’ ‘DAY’ button for easy

 

 

holiday override setting.

 

 

If power supply fails, the settings are

 

Outdoor unit

stored in the memory for 100 hours.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Central remote

Weekly

controller

timer

Central remote controller

Connected to outdoor unit,

 

indoor unit

 

TCB-SC642TLE

Master

Slave

 

Outdoor unit

Central remote controller

Individual control of up to 64 indoor units

Individual control of max. 64 indoor units divided into 1 to 4 zones.

(Upzone.to 16 indoor units for each )

Up to 16 outdoor master units are connectable.

4 central control setting types to inhibit individual operation by remote controller can be selected.

Setting for one of 1 to 4 zones is available.

Usable with other central control devices (up to 10 central control devices in one control circuit).

Two control mode choices

Centrol controller mode

)

( Remote controller mode

• Settings of simultaneous ON/OFF 3 times for each day of the week combined with weekly timer.

Central remote controller

Indoor remote controller

12

Image 12
Contents Super Modular Multi Page Super Modular Multi System Contents Outline of Toshiba Super Modular Multi System S-MMS Outdoor unit Indoor unit  Self-diagnostic system  Compact Largest system capacity  Energy saving designSummary of system equipment Technical specifications outdoor unitsTechnical specifications combination of outdoor units Branching joints and headersOutdoor unit model line-up cooling only units Product designationCombined capacity range Rated conditionsOutdoor unit model line-up heat pump units MMY- M AP 000 0 H TTechnical specifications indoor units Remote controller Simplified remote controller Connected to indoor unitWireless remote controller kit Connected to indoor unit TCB-AX21U W-EWeekly timer RBC-EXW21E Connected to central remote Controller, wired remote controllerMaster Basic system configuration System legend example 8 hp system8HP Hp system 10HP10HP 10HP Hp system 10HP 10HP 10HP Outdoor unit Indoor unit Remote controller Equipment selection procedure Selection flow chartIndoor unit and outdoor unit combination Capacity codeCapacity correction value Indoor air wet bulb temperature C  Correction of outdoor unit diversity Capacity correction value Indoor air dry bulb temperature C  Correction of outdoor unit diversity Operating temperature range Heating modeCapacity calculation for each indoor unit Rated conditionsExample of equipment selection Selection criteria for each floorOutside view Procedure and result of equipment selection Air conditioning load Equipment selection Floor Room NoIndoor unit Outdoor unit Model Capacity kW Cooling Heating Cooling HeatingExample Equipment selection based on system load profile Load in each roomSchematic diagram MMY-AP2801T8 MMY-AP2801HT8Refrigerant piping design Check of concentration limitFree branching system Line branching system Header branching systemAllowable length/height difference of refrigerant piping System restrictionsAllowable value Piping section Selection of refrigerant piping  Pipe size of outdoor unit Table Model nameGas side Liquid side Charging requirement with additional refrigerant Calculating the amount of additional refrigerant requiredCharge Cooling only Liquid side pipe diameterWiring design Outdoor unit power supplyElectrical wiring design GeneralControl wiring design Control wiring diagram Control wiring between outdoor units L5 WiringType LengthDesign FLA MCA MocpCompressor Fan motor Power supply Single outdoor unit Heat pump Cooling only NominalVoltage Range Ph-Hz Min Max Combination of outdoor units Heat pump Cooling only NominalControl via indoor remote controller Control via the central remote controllerControls Range of controls to meet various system needsApplications for indoor remote controller Basic function System diagram Model Individual controlTwo remote controllers Control by weekly timerApplication controls for central remote controller Basic function System diagram ModelIndoor remote controller Function of central remote controllerAvailable TCB-PCNT30TLEApplication control for network TCB-1FLNBACnet BMS-LSVBMS-TP5120ACE Accessories Indoor unit accessoriesRemote controller Indoor unit type Accessory name Model Applicable modelTechnical specifications Indoor units Way ceiling cassettesRBC-UW136PG RBC-UW266PG Room thermostat RBC-UY135PG RBC-US165PG RBC-US265PGFan motor power input Static pressure factory setting Static pressure maxIndoor units Standard ducted units Sound pressure level high/medium/low** dBAUnit weight Static pressure factory settingSound power level high Indoor units High-pressure ducted unitsLower air inlet Sound power level high/medium/low Rear air inlet Sound power level high/medium/lowIndoor units Slim duct units Indoor units Ceiling-suspended units Indoor units High-wall units 1 Series Indoor units High-wall units 2 Series Indoor units Floor-mounted console units Indoor units Concealed chassis units Static pressureIndoor units Floor-mounted cabinet units Outdoor units Outdoor units combination DBA 74.5 DBA 75.0 24.26 Power factor, cooling Operating current, cooling 30.51 258 256 DBA 76.5 77.0 Max. number of connectable indoor units High-pressure switch Power supply ± 10% Ph-Hz 400-3-50 130.0 135.0 Fan characteristics Case of square duct flange of discharge sectionMMD-AP0071BH, AP0091BH MMD-AP0121BHMMD-AP0241BH, AP0271BH MMD-AP0361BHMMD-AP0301BH MMD-AP0481BH, AP0561BHHigh-pressure ducted unit MMD-AP0181HMMD-AP0241H, AP0271H MMD-AP0361HMMD-AP0721H MMD-AP0961HSlim duct unit MMD-AP0071SPH, AP0091SPH MMD-AP0121SPHMMD-AP0151SPH MMD-AP0181SPH Slim duct unit with filter attached MMD-AP0151SPHDimensional drawings All dimensions are given in mmIndoor unit 4-way ceiling cassette MMU-AP0091H to P0561HAll dimensions are given in mm View Indoor unit 2-way ceiling cassetteMMU-AP0071WH, AP0091WH, AP0121WH View Space required for installation and servicing MMU-AP0151WH, AP0181WH, AP0241WH, AP0271WH, AP0301WHModel MMU-AP0151WH to AP0181WH MMU-AP0241WH to AP0301WH MMU-AP0481WH Indoor unit 1-way ceiling cassette MMU-AP0071YH, AP0091YH, AP0121YHMMU-AP0151SH, AP0181SH, AP0241SH View Model MMU AP0151SH, AP0181SHAP0241SH Indoor unit standard ducted unit View Space required for installation and servicing *1 Indoor unit high-pressure ducted unitMMD-AP0271H, AP0961H Indoor unit slim duct unit MMD-AP0071SPH, AP0091SPH, AP0121SPH, AP0151SPH, AP0181SPHBottom view complete with filter Bottom view excluding filterIndoor unit ceiling-suspended unit MMC-AP0151H, AP0181H, AP0241H, AP0271H, AP0361H, AP0481HModel MMC AP0151H, AP0181H AP0241H to AP0271HIndoor unit high-wall unit 1 Series MMK-AP0071H, AP0091H, AP0121HMMK-AP0151H, AP0181H MMK-AP0241H Indoor unit high-wall unit 2 Series MMK-AP0072H, AP0092H, AP0122HIndoor unit floor-mounted console unit MML-AP0071H, AP0091H, AP0121H, AP0151H, AP0181H, AP0241HIndoor unit concealed chassis unit No. NameModel MML AP0071BH, AP0091BH, AP0121BH AP0151BH, AP0181HSpace required for service For right-hand piping Indoor unit floor-mounted cabinet unitMMF-AP0151H, AP0181H, AP0241H, AP0271H MMF-AP0361H, AP0481H, AP0561H Refrigerant pipe positions Details of hole for rear pipingRemote controller All dimensions are given in mm Wireless remote controller kit Weekly timerTCB-AX21E RBC-EXW21ECentral remote controller TCB-SC642TLELON Gateway TCB-IFLNTCS-Net relay interface BMS-IFLSV1ETouch-screen controller BMS-TP5120ACE Intelligent server BMS-LSV2EEnergy monitoring relay interface BMS-IFWH3E Digital I/O relay interface BMS-IFDD01EWindows-based central controller BMS-LSV Outdoor module Outdoor module Two units connected Outdoor module Three units connected Unit combinationOutdoor unit combination Master unit Slave unit Outdoor module Four units connected Unit combination Outdoor unit combination Master unitModel Accessory socket x quantity Branch header/branch jointBranch header RBM-HY1043E, HY1083E, HY2043E,HY2083E Shape branching jointRBM-BY53E, BY103E RBM-BY203E, BY303EAccessory socket Page Toshiba Air Conditioning