Page 61
Outdoor units (combination)
Rating | hp | 24 | | | | 24 | |
Cooling only system MMY | | AP2401T8 | | | | AP2411T8 | |
Heat pump system MMY | | AP2401HT8 | | | | AP2411HT8 | |
Outdoor unit type | | Inverter | Inverter | Inverter | Inverter | Inverter |
Outdoor unit combination | | | | | | | |
cooling only MMY-MAP | | 0801T8 | 0801T8 | 0801T8 | 1201T8 | 1201T8 |
Outdoor unit combination | | | | | | | |
heat pump MMY-MAP | | 0801HT8 | 0801HT8 | 0801HT8 | 1201HT8 | 1201HT8 |
Cooling capacity | kW | 68.0 | | | | 68.0 | |
Heating capacity | kW | 76.5 | | | | 76.5 | |
Power supply | V-ph-Hz | 400-3-50 ± 10% | 400-3-50 ± 10% | 400-3-50 ± 10% | | 400-3-50 ± 10% | 400-3-50 ± 10% |
Voltage range | V | 380-415 | 380-415 | 380-415 | | 380-415 | 380-415 |
Power input, cooling | kW | 18.44 | | | | 25.02 | |
Power factor, cooling | % | 96 | | | | 95 | |
Operating current, cooling | A | 27.73 | | | | 38.02 | |
EER, cooling | kW/kW | 3.69 | | | | 2.72 | |
Starting current | A | 1.0 | | | | 1.0 | |
Power input, heating | kW | 18.79 | | | | 21.32 | |
Power factor, heating | % | 97 | | | | 96 | |
Operating current, heating | A | 27.96 | | | | 32.06 | |
COP, heating | kW/kW | 4.07 | | | | 3.59 | |
Starting current | A | 1.0 | | | | 1.0 | |
Unit appearance | | Silky shade (Munsell 1Y8.5/0.5) | | | | |
Dimensions | | | | | | | |
Height | mm | 1800 | 1800 | 1800 | | 1800 | 1800 |
Width | mm | 990 | 990 | 990 | | 990 | 990 |
Depth | mm | 750 | 750 | 750 | | 750 | 750 |
Total weight - cooling only unit | kg | 256 | 256 | 256 | | 256 | 256 |
Total weight - heat pump unit | kg | 258 | 258 | 258 | | 258 | 258 |
Heat exchanger | | Finned type | | | | | |
Sound power level | dB(A) | 75.0 | | | | 75.0 | |
Sound pressure level | dB(A) at 1 m | 62.0 | | | | 62.0 | |
Fan type | | Propeller | Propeller | Propeller | | Propeller | Propeller |
Motor power input | kW | 0.6 | 0.6 | 0.6 | | 0.6 | 0.6 |
Air flow | l/s | 2750 | 2750 | 2750 | | 2917 | 2917 |
| m3/h | 9900 | 9900 | 9900 | | 10500 | 10500 |
Compressor type | | Hermetic | Hermetic | Hermetic | | Hermetic | Hermetic |
Motor power input | kW | 2.3 x 2 | 2.3 x 2 | 2.3 x 2 | | 4.2 x 2 | 4.2 x 2 |
Refrigerant charge R-410A* | | | | | | | |
Cooling | kg | 11.0 | 11.0 | 11.0 | | 11.0 | 11.0 |
Heating | kg | 12.5 | 12.5 | 12.5 | | 12.5 | 12.5 |
Pipework** | | | | | | | |
Suction line type - diameter | in | Brazed - 7/8 | Brazed - 7/8 | Brazed - 7/8 | | Brazed - 1-1/8 | Brazed -1-1/8 |
Liquid line type - diameter | in | Flare - 1/2 | Flare - 1/2 | Flare - 1/2 | | Flare - 1/2 | Flare - 1/2 |
Balance pipe type - diameter | in | Flare - 3/8 | Flare - 3/8 | Flare - 3/8 | | Flare - 3/8 | Flare - 3/8 |
Maximum equivalent length separation | m | 175 | 175 | 175 | | 175 | 175 |
Maximum actual piping length | m | 150 (if equivalent bend length is longer, equivalent length is standard) | |
Maximum total piping length | m | 300 | 300 | 300 | | 300 | 300 |
|
Maximum lift - indoor unit above/below*** | m | 40/50 | 40/50 | 40/50 | | 40/50 | 40/50 |
Control wiring | | Shielded wire 1.25 mm2 x 2 cores up to 2000 m | | |
Central remote controller | | Shielded wire 1.25 mm2 x 2 pieces up to 1000 m, 2.0 mm2 x 2 pieces up to 2000 m | |
Max. number of connectable indoor units | | 40 | | | | 40 | |
High-pressure switch | MPa | Off: 2.90/On: 3.73 | | | | | |
Protection devices | | Discharge temperature sensor, suction temperature sensor, compressor crankcase heater, |
| | high-pressure switch, overcurrent sensor, high-pressure sensor, low-pressure sensor, | |
| | overcurrent relay | | | | | |
Operating range, cooling† | °C | -5 to 43 db | -5 to 43 db | -5 to 43 db | | -5 to 43 db | -5 to 43 db |
Operating range, heating† | °C | -20 to 16 wb | -20 to 16 wb | -20 to 16 wb | | -20 to 16 wb | -20 to 16 wb |
Rated conditions: Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db
Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb
The standard piping equals 5 m main pipe length plus 2.5 m branch pipe length.
*The amount does not cover extra piping lengths. Refrigerant must be added on-site in accordance with the actual piping length.
** The maximum total piping length is the sum of one-way piping lengths on the liquid side or gas side.
*** If the indoor unit is above, maximum lift is reduced to 30 m, if the height difference between indoor units exceeds 3 m.
† Please refer to page 24.
61
Contents
Super Modular Multi
Page
Super Modular Multi System Contents
Outline of Toshiba Super Modular Multi System S-MMS
Outdoor unit Indoor unit
Compact
Self-diagnostic system
Largest system capacity
Energy saving design
Technical specifications outdoor units
Summary of system equipment
Technical specifications combination of outdoor units
Branching joints and headers
Product designation
Outdoor unit model line-up cooling only units
Combined capacity range
Rated conditions
MMY- M AP 000 0 H T
Outdoor unit model line-up heat pump units
Technical specifications indoor units
Simplified remote controller Connected to indoor unit
Remote controller
Wireless remote controller kit Connected to indoor unit
TCB-AX21U W-E
Controller, wired remote controller
Weekly timer RBC-EXW21E Connected to central remote
Master
System legend example 8 hp system
Basic system configuration
8HP
10HP
Hp system
10HP 10HP
Hp system
10HP 10HP 10HP
Outdoor unit Indoor unit Remote controller
Selection flow chart
Equipment selection procedure
Indoor unit and outdoor unit combination
Capacity code
Capacity correction value Indoor air wet bulb temperature C
Correction of outdoor unit diversity
Capacity correction value Indoor air dry bulb temperature C
Correction of outdoor unit diversity
Heating mode
Operating temperature range
Capacity calculation for each indoor unit
Rated conditions
Selection criteria for each floor
Example of equipment selection
Outside view
Air conditioning load Equipment selection Floor Room No
Procedure and result of equipment selection
Indoor unit Outdoor unit Model Capacity kW Cooling Heating
Cooling Heating
Load in each room
Example Equipment selection based on system load profile
MMY-AP2801T8 MMY-AP2801HT8
Schematic diagram
Check of concentration limit
Refrigerant piping design
Line branching system Header branching system
Free branching system
System restrictions
Allowable length/height difference of refrigerant piping
Allowable value Piping section
Pipe size of outdoor unit Table Model name
Selection of refrigerant piping
Gas side Liquid side
Calculating the amount of additional refrigerant required
Charging requirement with additional refrigerant
Charge Cooling only
Liquid side pipe diameter
Outdoor unit power supply
Wiring design
Electrical wiring design
General
Control wiring design
Control wiring between outdoor units L5 Wiring
Control wiring diagram
Type
Length
FLA MCA Mocp
Design
Single outdoor unit Heat pump Cooling only Nominal
Compressor Fan motor Power supply
Voltage Range Ph-Hz Min Max
Combination of outdoor units Heat pump Cooling only Nominal
Control via the central remote controller
Control via indoor remote controller
Controls
Range of controls to meet various system needs
Basic function System diagram Model Individual control
Applications for indoor remote controller
Two remote controllers
Control by weekly timer
Basic function System diagram Model
Application controls for central remote controller
Indoor remote controller
Function of central remote controller
TCB-PCNT30TLE
Available
TCB-1FLN
Application control for network
BACnet
BMS-LSV
BMS-TP5120ACE
Indoor unit accessories
Accessories
Remote controller
Indoor unit type Accessory name Model Applicable model
Indoor units Way ceiling cassettes
Technical specifications
RBC-UW136PG RBC-UW266PG
RBC-UY135PG RBC-US165PG RBC-US265PG
Room thermostat
Static pressure factory setting Static pressure max
Fan motor power input
Indoor units Standard ducted units
Sound pressure level high/medium/low** dBA
Static pressure factory setting
Unit weight
Sound power level high
Indoor units High-pressure ducted units
Rear air inlet Sound power level high/medium/low
Lower air inlet Sound power level high/medium/low
Indoor units Slim duct units
Indoor units Ceiling-suspended units
Indoor units High-wall units 1 Series
Indoor units High-wall units 2 Series
Indoor units Floor-mounted console units
Static pressure
Indoor units Concealed chassis units
Indoor units Floor-mounted cabinet units
Outdoor units
Outdoor units combination
DBA 74.5
DBA 75.0
24.26 Power factor, cooling Operating current, cooling 30.51
258 256
DBA 76.5
77.0
Max. number of connectable indoor units High-pressure switch
Power supply ± 10% Ph-Hz 400-3-50
130.0 135.0
Case of square duct flange of discharge section
Fan characteristics
MMD-AP0071BH, AP0091BH
MMD-AP0121BH
MMD-AP0361BH
MMD-AP0241BH, AP0271BH
MMD-AP0301BH
MMD-AP0481BH, AP0561BH
MMD-AP0181H
High-pressure ducted unit
MMD-AP0241H, AP0271H
MMD-AP0361H
MMD-AP0961H
MMD-AP0721H
MMD-AP0071SPH, AP0091SPH MMD-AP0121SPH
Slim duct unit
MMD-AP0151SPH MMD-AP0181SPH
MMD-AP0151SPH
Slim duct unit with filter attached
All dimensions are given in mm
Dimensional drawings
Indoor unit 4-way ceiling cassette
MMU-AP0091H to P0561H
Indoor unit 2-way ceiling cassette
All dimensions are given in mm View
MMU-AP0071WH, AP0091WH, AP0121WH
MMU-AP0151WH, AP0181WH, AP0241WH, AP0271WH, AP0301WH
View Space required for installation and servicing
Model MMU-AP0151WH to AP0181WH MMU-AP0241WH to AP0301WH
MMU-AP0481WH
MMU-AP0071YH, AP0091YH, AP0121YH
Indoor unit 1-way ceiling cassette
View Model MMU AP0151SH, AP0181SH
MMU-AP0151SH, AP0181SH, AP0241SH
AP0241SH
Indoor unit standard ducted unit
Indoor unit high-pressure ducted unit
View Space required for installation and servicing *1
MMD-AP0271H, AP0961H
MMD-AP0071SPH, AP0091SPH, AP0121SPH, AP0151SPH, AP0181SPH
Indoor unit slim duct unit
Bottom view complete with filter
Bottom view excluding filter
MMC-AP0151H, AP0181H, AP0241H, AP0271H, AP0361H, AP0481H
Indoor unit ceiling-suspended unit
Model MMC AP0151H, AP0181H
AP0241H to AP0271H
MMK-AP0071H, AP0091H, AP0121H
Indoor unit high-wall unit 1 Series
MMK-AP0151H, AP0181H
MMK-AP0241H
MMK-AP0072H, AP0092H, AP0122H
Indoor unit high-wall unit 2 Series
MML-AP0071H, AP0091H, AP0121H, AP0151H, AP0181H, AP0241H
Indoor unit floor-mounted console unit
No. Name
Indoor unit concealed chassis unit
Model MML AP0071BH, AP0091BH, AP0121BH
AP0151BH, AP0181H
Indoor unit floor-mounted cabinet unit
Space required for service For right-hand piping
MMF-AP0151H, AP0181H, AP0241H, AP0271H
Refrigerant pipe positions Details of hole for rear piping
MMF-AP0361H, AP0481H, AP0561H
Remote controller
All dimensions are given in mm
Weekly timer
Wireless remote controller kit
TCB-AX21E
RBC-EXW21E
TCB-SC642TLE
Central remote controller
LON Gateway
TCB-IFLN
BMS-IFLSV1E
TCS-Net relay interface
Touch-screen controller BMS-TP5120ACE
BMS-LSV2E
Intelligent server
Energy monitoring relay interface BMS-IFWH3E
BMS-IFDD01E
Digital I/O relay interface
Windows-based central controller BMS-LSV
Outdoor module
Outdoor module Two units connected
Unit combination
Outdoor module Three units connected
Outdoor unit combination Master unit Slave unit
Unit combination Outdoor unit combination Master unit
Outdoor module Four units connected
Branch header/branch joint
Model Accessory socket x quantity
Branch header RBM-HY1043E, HY1083E, HY2043E,HY2083E
Shape branching joint
RBM-BY203E, BY303E
RBM-BY53E, BY103E
Accessory socket
Page