Toshiba HFC R-410A Indoor units High-pressure ducted units, Unit weight, Sound power level high

Page 50

Indoor units

High-pressure ducted units

Model MMD-AP

 

0181H

0241H

0271H

0361H

0481H

0721H

0961H

Cooling capacity*

kW

5.6

7.1

8.0

11.2

14.0

22.4

28.0

Heating capacity

kW

6.3

8.0

9.0

12.5

16.0

25.0

31.5

Electrical data

 

 

 

 

 

 

 

 

Power supply

V-ph-Hz

230-1-50 (voltage range 220-240 V) - power supply to indoor unit only

 

 

Operating current

A

0.81

1.35

1.35

1.63

1.84

5.25

5.52

Power input

kW

0.184

0.299

0.299

0.368

0.414

1.200

1.260

Power factor

%

99

96

96

98

98

99

99

Starting current

A

1.3

3.5

3.5

4.1

4.8

13.6

14.8

Unit appearance

 

Zinc hot dipping steel plate

 

 

 

 

 

Unit dimensions

 

 

 

 

 

 

 

 

Height

mm

380

380

380

380

380

470

470

Width

mm

850

850

850

850

1200

1380

1380

Depth

mm

660

660

660

660

660

1250

1250

Unit weight

kg

50

52

52

56

67

150

150

Heat exchanger

 

Finned tube

 

 

 

 

 

 

Sound proofing/heat insulating material

 

Non-flammable insulation

 

 

 

 

 

Fan type

 

Centrifugal fan

 

 

 

 

 

 

Fan motor power input

W

160

160

160

260

260

370 x 3

370 x 3

Air flow

 

 

 

 

 

 

 

 

High

l/s

300

439

439

533

700

1200

1400

Medium

l/s

250

367

367

445

583

1000

1167

Low

l/s

200

295

295

356

467

800

933

Air flow

 

 

 

 

 

 

 

 

High

m3/h

1080

1580

1580

1920

2520

4320

5040

Medium

m3/h

900

1320

1320

1600

2100

3600

4200

Low

m3/h

720

1060

1060

1280

1680

2880

3360

Static pressure (factory setting)

Pa

137

137

137

137

137

137

137

Static pressure (low/medium/high)

Pa

68.6/137/196

68.6/137/196

68.6/137/196

68.6/137/196

68.6/137/196

68.6/137/196

68.6/137/196

Sound power level (high)

dB(A)

50

53

53

53

53

62

63

Sound pressure level (high/medium/low)**

dB(A)

37/35/33

40/38/36

40/38/36

40/38/36

40/38/36

49/47/45

50/48/46

Air filter

 

Optional or field-supplied

 

 

 

 

 

Controller

 

Remote controller

 

 

 

 

 

Connection pipes

 

 

 

 

 

 

 

 

Gas connection diameter

in

1/2

5/8

5/8

5/8

5/8

7/8

7/8

Liquid connection diameter

in

1/4

3/8

3/8

3/8

3/8

1/2

1/2

Drain connection, nom. dia***

in

1

1

1

1

1

1

1

Rated conditions: Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db

Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb

*Cooling capacities and electrical data are measured at the conditions specified by JIS B 8615, based on the reference piping which consists of 5 m of main

piping and 2.5 m of branch piping connected with 0 metre height.

**The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound.

***Male screw connection one side

50

Image 50
Contents Super Modular Multi Page Super Modular Multi System Contents Outline of Toshiba Super Modular Multi System S-MMS Outdoor unit Indoor unit  Largest system capacity  Self-diagnostic system Compact  Energy saving designTechnical specifications combination of outdoor units Summary of system equipmentTechnical specifications outdoor units Branching joints and headersCombined capacity range Outdoor unit model line-up cooling only unitsProduct designation Rated conditionsOutdoor unit model line-up heat pump units MMY- M AP 000 0 H TTechnical specifications indoor units Wireless remote controller kit Connected to indoor unit Remote controllerSimplified remote controller Connected to indoor unit TCB-AX21U W-EMaster Weekly timer RBC-EXW21E Connected to central remoteController, wired remote controller 8HP Basic system configurationSystem legend example 8 hp system Hp system 10HP10HP 10HP Hp system 10HP 10HP 10HP Outdoor unit Indoor unit Remote controller Indoor unit and outdoor unit combination Equipment selection procedureSelection flow chart Capacity codeCapacity correction value Indoor air wet bulb temperature C  Correction of outdoor unit diversity Capacity correction value Indoor air dry bulb temperature C  Correction of outdoor unit diversity Capacity calculation for each indoor unit Operating temperature rangeHeating mode Rated conditionsOutside view Example of equipment selectionSelection criteria for each floor Indoor unit Outdoor unit Model Capacity kW Cooling Heating Procedure and result of equipment selectionAir conditioning load Equipment selection Floor Room No Cooling HeatingExample Equipment selection based on system load profile Load in each roomSchematic diagram MMY-AP2801T8 MMY-AP2801HT8Refrigerant piping design Check of concentration limitFree branching system Line branching system Header branching systemAllowable value Piping section Allowable length/height difference of refrigerant pipingSystem restrictions Gas side Liquid side Selection of refrigerant piping Pipe size of outdoor unit Table Model name Charge Cooling only Charging requirement with additional refrigerantCalculating the amount of additional refrigerant required Liquid side pipe diameterElectrical wiring design Wiring designOutdoor unit power supply GeneralControl wiring design Type Control wiring diagramControl wiring between outdoor units L5 Wiring LengthDesign FLA MCA MocpVoltage Range Ph-Hz Min Max Compressor Fan motor Power supplySingle outdoor unit Heat pump Cooling only Nominal Combination of outdoor units Heat pump Cooling only NominalControls Control via indoor remote controllerControl via the central remote controller Range of controls to meet various system needsTwo remote controllers Applications for indoor remote controllerBasic function System diagram Model Individual control Control by weekly timerIndoor remote controller Application controls for central remote controllerBasic function System diagram Model Function of central remote controllerAvailable TCB-PCNT30TLEBACnet Application control for networkTCB-1FLN BMS-LSVBMS-TP5120ACE Remote controller AccessoriesIndoor unit accessories Indoor unit type Accessory name Model Applicable modelTechnical specifications Indoor units Way ceiling cassettesRBC-UW136PG RBC-UW266PG Room thermostat RBC-UY135PG RBC-US165PG RBC-US265PGIndoor units Standard ducted units Fan motor power inputStatic pressure factory setting Static pressure max Sound pressure level high/medium/low** dBASound power level high Unit weightStatic pressure factory setting Indoor units High-pressure ducted unitsIndoor units Slim duct units Lower air inlet Sound power level high/medium/lowRear air inlet Sound power level high/medium/low Indoor units Ceiling-suspended units Indoor units High-wall units 1 Series Indoor units High-wall units 2 Series Indoor units Floor-mounted console units Indoor units Concealed chassis units Static pressureIndoor units Floor-mounted cabinet units Outdoor units Outdoor units combination DBA 74.5 DBA 75.0 24.26 Power factor, cooling Operating current, cooling 30.51 258 256 DBA 76.5 77.0 Max. number of connectable indoor units High-pressure switch Power supply ± 10% Ph-Hz 400-3-50 130.0 135.0 MMD-AP0071BH, AP0091BH Fan characteristicsCase of square duct flange of discharge section MMD-AP0121BHMMD-AP0301BH MMD-AP0241BH, AP0271BHMMD-AP0361BH MMD-AP0481BH, AP0561BHMMD-AP0241H, AP0271H High-pressure ducted unitMMD-AP0181H MMD-AP0361HMMD-AP0721H MMD-AP0961HMMD-AP0151SPH MMD-AP0181SPH Slim duct unitMMD-AP0071SPH, AP0091SPH MMD-AP0121SPH Slim duct unit with filter attached MMD-AP0151SPHIndoor unit 4-way ceiling cassette Dimensional drawingsAll dimensions are given in mm MMU-AP0091H to P0561HMMU-AP0071WH, AP0091WH, AP0121WH All dimensions are given in mm ViewIndoor unit 2-way ceiling cassette Model MMU-AP0151WH to AP0181WH MMU-AP0241WH to AP0301WH View Space required for installation and servicingMMU-AP0151WH, AP0181WH, AP0241WH, AP0271WH, AP0301WH MMU-AP0481WH Indoor unit 1-way ceiling cassette MMU-AP0071YH, AP0091YH, AP0121YHAP0241SH MMU-AP0151SH, AP0181SH, AP0241SHView Model MMU AP0151SH, AP0181SH Indoor unit standard ducted unit MMD-AP0271H, AP0961H View Space required for installation and servicing *1Indoor unit high-pressure ducted unit Bottom view complete with filter Indoor unit slim duct unitMMD-AP0071SPH, AP0091SPH, AP0121SPH, AP0151SPH, AP0181SPH Bottom view excluding filterModel MMC AP0151H, AP0181H Indoor unit ceiling-suspended unitMMC-AP0151H, AP0181H, AP0241H, AP0271H, AP0361H, AP0481H AP0241H to AP0271HIndoor unit high-wall unit 1 Series MMK-AP0071H, AP0091H, AP0121HMMK-AP0151H, AP0181H MMK-AP0241H Indoor unit high-wall unit 2 Series MMK-AP0072H, AP0092H, AP0122HIndoor unit floor-mounted console unit MML-AP0071H, AP0091H, AP0121H, AP0151H, AP0181H, AP0241HModel MML AP0071BH, AP0091BH, AP0121BH Indoor unit concealed chassis unitNo. Name AP0151BH, AP0181HMMF-AP0151H, AP0181H, AP0241H, AP0271H Space required for service For right-hand pipingIndoor unit floor-mounted cabinet unit MMF-AP0361H, AP0481H, AP0561H Refrigerant pipe positions Details of hole for rear pipingRemote controller All dimensions are given in mm TCB-AX21E Wireless remote controller kitWeekly timer RBC-EXW21ELON Gateway Central remote controllerTCB-SC642TLE TCB-IFLNTouch-screen controller BMS-TP5120ACE TCS-Net relay interfaceBMS-IFLSV1E Energy monitoring relay interface BMS-IFWH3E Intelligent serverBMS-LSV2E Windows-based central controller BMS-LSV Digital I/O relay interfaceBMS-IFDD01E Outdoor module Outdoor module Two units connected Outdoor unit combination Master unit Slave unit Outdoor module Three units connectedUnit combination Outdoor module Four units connected Unit combination Outdoor unit combination Master unitBranch header RBM-HY1043E, HY1083E, HY2043E,HY2083E Model Accessory socket x quantityBranch header/branch joint Shape branching jointRBM-BY53E, BY103E RBM-BY203E, BY303EAccessory socket Page Toshiba Air Conditioning