Toshiba HFC R-410A manual DBA 74.5

Page 60

Outdoor units (combination)

Rating

hp

22

 

 

22

 

Cooling only system MMY

 

AP2201T8

 

 

AP2211T8

 

Heat pump system MMY

 

AP2201HT8

 

 

AP2211HT8

 

Outdoor unit type

 

Inverter

Inverter

Inverter

Inverter

Inverter

Outdoor unit combination

 

 

 

 

 

 

cooling only MMY-MAP

 

0801T8

0801T8

0601T8

1201T8

1001T8

Outdoor unit combination

 

 

 

 

 

 

heat pump MMY-MAP

 

0801HT8

0801HT8

0601HT8

1201HT8

1001HT8

Cooling capacity

kW

61.5

 

 

61.5

 

Heating capacity

kW

69.0

 

 

69.0

 

Power supply

V-ph-Hz

400-3-50 ± 10%

400-3-50 ± 10%

400-3-50 ± 10%

400-3-50 ± 10%

400-3-50 ± 10%

Voltage range

V

380-415

380-415

380-415

380-415

380-415

Power input, cooling

kW

17.39

 

 

20.41

 

Power factor, cooling

%

95

 

 

95

 

Operating current, cooling

A

26.42

 

 

31.01

 

EER, cooling

kW/kW

3.54

 

 

3.01

 

Starting current

A

1.0

 

 

1.0

 

Power input, heating

kW

17.35

 

 

18.68

 

Power factor, heating

%

95

 

 

95

 

Operating current, heating

A

26.36

 

 

28.38

 

COP, heating

kW/kW

3.98

 

 

3.69

 

Starting current

A

1.0

 

 

1.0

 

Unit appearance

 

Silky shade (Munsell 1Y8.5/0.5)

 

 

 

Dimensions

 

 

 

 

 

 

Height

mm

1800

1800

1800

1800

1800

Width

mm

990

990

990

990

990

Depth

mm

750

750

750

750

750

Total weight - cooling only unit

kg

256

256

227

256

256

Total weight - heat pump unit

kg

258

258

228

258

258

Heat exchanger

 

Finned type

 

 

 

 

Sound power level

dB(A)

74.5

 

 

74.5

 

Sound pressure level

dB(A) at 1 m

61.5

 

 

61.5

 

Fan type

 

Propeller

Propeller

Propeller

Propeller

Propeller

Motor power input

kW

0.6

0.6

0.6

0.6

0.6

Air flow

l/s

2750

2750

2500

2917

2917

 

m3/h

9900

9900

9000

10500

10500

Compressor type

 

Hermetic

Hermetic

Hermetic

Hermetic

Hermetic

Motor power input

kW

2.3 x 2

2.3 x 2

1.4 x 2

4.2 x 2

3.1 x 2

Refrigerant charge R-410A*

 

 

 

 

 

 

Cooling

kg

11.0

11.0

8.0

11.0

11.0

Heating

kg

12.5

12.5

8.5

12.5

12.5

Pipework**

 

 

 

 

 

 

Suction line type - diameter

in

Brazed - 7/8

Brazed - 7/8

Brazed - 3/4

Brazed - 1-1/8

Brazed - 7/8

Liquid line type - diameter

in

Flare - 1/2

Flare - 1/2

Flare - 3/8

Flare - 1/2

Flare - 1/2

Balance pipe type - diameter

in

Flare - 3/8

Flare - 3/8

Flare - 3/8

Flare - 3/8

Flare - 3/8

Maximum equivalent length separation

m

175

175

175

175

175

Maximum actual piping length

m

150 (if equivalent bend length is longer, equivalent length is standard)

 

Maximum total piping length

m

300

300

300

300

300

Maximum lift - indoor unit above/below***

m

40/50

40/50

40/50

40/50

40/50

Control wiring

 

Shielded wire 1.25 mm2 x 2 cores up to 2000 m

 

 

Central remote controller

 

Shielded wire 1.25 mm2 x 2 pieces up to 1000 m, 2.0 mm2 x 2 pieces up to 2000 m

 

Max. number of connectable indoor units

 

37

 

 

37

 

High-pressure switch

MPa

Off: 2.90/On: 3.73

 

 

 

 

Protection devices

 

Discharge temperature sensor, suction temperature sensor, compressor crankcase heater,

 

 

high-pressure switch, overcurrent sensor, high-pressure sensor, low-pressure sensor,

 

 

 

overcurrent relay

 

 

 

 

Operating range, cooling†

°C

-5 to 43 db

-5 to 43 db

-5 to 43 db

-5 to 43 db

-5 to 43 db

Operating range, heating†

°C

-20 to 16 wb

-20 to 16 wb

-20 to 16 wb

-20 to 16 wb

-20 to 16 wb

Rated conditions: Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db

Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb

The standard piping equals 5 m main pipe length plus 2.5 m branch pipe length.

*The amount does not cover extra piping lengths. Refrigerant must be added on-site in accordance with the actual piping length.

** The maximum total piping length is the sum of one-way piping lengths on the liquid side or gas side.

*** If the indoor unit is above, maximum lift is reduced to 30 m, if the height difference between indoor units exceeds 3 m.

† Please refer to page 24.

60

Image 60
Contents Super Modular Multi Page Super Modular Multi System Contents Outline of Toshiba Super Modular Multi System S-MMS Outdoor unit Indoor unit  Self-diagnostic system  Compact Largest system capacity  Energy saving designSummary of system equipment Technical specifications outdoor unitsTechnical specifications combination of outdoor units Branching joints and headersOutdoor unit model line-up cooling only units Product designationCombined capacity range Rated conditionsOutdoor unit model line-up heat pump units MMY- M AP 000 0 H TTechnical specifications indoor units Remote controller Simplified remote controller Connected to indoor unitWireless remote controller kit Connected to indoor unit TCB-AX21U W-EWeekly timer RBC-EXW21E Connected to central remote Controller, wired remote controllerMaster Basic system configuration System legend example 8 hp system8HP Hp system 10HP10HP 10HP Hp system 10HP 10HP 10HP Outdoor unit Indoor unit Remote controller Equipment selection procedure Selection flow chartIndoor unit and outdoor unit combination Capacity codeCapacity correction value Indoor air wet bulb temperature C  Correction of outdoor unit diversity Capacity correction value Indoor air dry bulb temperature C  Correction of outdoor unit diversity Operating temperature range Heating modeCapacity calculation for each indoor unit Rated conditionsExample of equipment selection Selection criteria for each floorOutside view Procedure and result of equipment selection Air conditioning load Equipment selection Floor Room NoIndoor unit Outdoor unit Model Capacity kW Cooling Heating Cooling HeatingExample Equipment selection based on system load profile Load in each roomSchematic diagram MMY-AP2801T8 MMY-AP2801HT8Refrigerant piping design Check of concentration limitFree branching system Line branching system Header branching systemAllowable length/height difference of refrigerant piping System restrictionsAllowable value Piping section Selection of refrigerant piping  Pipe size of outdoor unit Table Model nameGas side Liquid side Charging requirement with additional refrigerant Calculating the amount of additional refrigerant requiredCharge Cooling only Liquid side pipe diameterWiring design Outdoor unit power supplyElectrical wiring design GeneralControl wiring design Control wiring diagram Control wiring between outdoor units L5 WiringType LengthDesign FLA MCA MocpCompressor Fan motor Power supply Single outdoor unit Heat pump Cooling only NominalVoltage Range Ph-Hz Min Max Combination of outdoor units Heat pump Cooling only NominalControl via indoor remote controller Control via the central remote controllerControls Range of controls to meet various system needsApplications for indoor remote controller Basic function System diagram Model Individual controlTwo remote controllers Control by weekly timerApplication controls for central remote controller Basic function System diagram ModelIndoor remote controller Function of central remote controllerAvailable TCB-PCNT30TLEApplication control for network TCB-1FLNBACnet BMS-LSVBMS-TP5120ACE Accessories Indoor unit accessoriesRemote controller Indoor unit type Accessory name Model Applicable modelTechnical specifications Indoor units Way ceiling cassettesRBC-UW136PG RBC-UW266PG Room thermostat RBC-UY135PG RBC-US165PG RBC-US265PGFan motor power input Static pressure factory setting Static pressure maxIndoor units Standard ducted units Sound pressure level high/medium/low** dBAUnit weight Static pressure factory settingSound power level high Indoor units High-pressure ducted unitsLower air inlet Sound power level high/medium/low Rear air inlet Sound power level high/medium/lowIndoor units Slim duct units Indoor units Ceiling-suspended units Indoor units High-wall units 1 Series Indoor units High-wall units 2 Series Indoor units Floor-mounted console units Indoor units Concealed chassis units Static pressureIndoor units Floor-mounted cabinet units Outdoor units Outdoor units combination DBA 74.5 DBA 75.0 24.26 Power factor, cooling Operating current, cooling 30.51 258 256 DBA 76.5 77.0 Max. number of connectable indoor units High-pressure switch Power supply ± 10% Ph-Hz 400-3-50 130.0 135.0 Fan characteristics Case of square duct flange of discharge sectionMMD-AP0071BH, AP0091BH MMD-AP0121BHMMD-AP0241BH, AP0271BH MMD-AP0361BHMMD-AP0301BH MMD-AP0481BH, AP0561BHHigh-pressure ducted unit MMD-AP0181HMMD-AP0241H, AP0271H MMD-AP0361HMMD-AP0721H MMD-AP0961HSlim duct unit MMD-AP0071SPH, AP0091SPH MMD-AP0121SPHMMD-AP0151SPH MMD-AP0181SPH Slim duct unit with filter attached MMD-AP0151SPHDimensional drawings All dimensions are given in mmIndoor unit 4-way ceiling cassette MMU-AP0091H to P0561HAll dimensions are given in mm View Indoor unit 2-way ceiling cassetteMMU-AP0071WH, AP0091WH, AP0121WH View Space required for installation and servicing MMU-AP0151WH, AP0181WH, AP0241WH, AP0271WH, AP0301WHModel MMU-AP0151WH to AP0181WH MMU-AP0241WH to AP0301WH MMU-AP0481WH Indoor unit 1-way ceiling cassette MMU-AP0071YH, AP0091YH, AP0121YHMMU-AP0151SH, AP0181SH, AP0241SH View Model MMU AP0151SH, AP0181SHAP0241SH Indoor unit standard ducted unit View Space required for installation and servicing *1 Indoor unit high-pressure ducted unitMMD-AP0271H, AP0961H Indoor unit slim duct unit MMD-AP0071SPH, AP0091SPH, AP0121SPH, AP0151SPH, AP0181SPHBottom view complete with filter Bottom view excluding filterIndoor unit ceiling-suspended unit MMC-AP0151H, AP0181H, AP0241H, AP0271H, AP0361H, AP0481HModel MMC AP0151H, AP0181H AP0241H to AP0271HIndoor unit high-wall unit 1 Series MMK-AP0071H, AP0091H, AP0121HMMK-AP0151H, AP0181H MMK-AP0241H Indoor unit high-wall unit 2 Series MMK-AP0072H, AP0092H, AP0122HIndoor unit floor-mounted console unit MML-AP0071H, AP0091H, AP0121H, AP0151H, AP0181H, AP0241HIndoor unit concealed chassis unit No. NameModel MML AP0071BH, AP0091BH, AP0121BH AP0151BH, AP0181HSpace required for service For right-hand piping Indoor unit floor-mounted cabinet unitMMF-AP0151H, AP0181H, AP0241H, AP0271H MMF-AP0361H, AP0481H, AP0561H Refrigerant pipe positions Details of hole for rear pipingRemote controller All dimensions are given in mm Wireless remote controller kit Weekly timerTCB-AX21E RBC-EXW21ECentral remote controller TCB-SC642TLELON Gateway TCB-IFLNTCS-Net relay interface BMS-IFLSV1ETouch-screen controller BMS-TP5120ACE Intelligent server BMS-LSV2EEnergy monitoring relay interface BMS-IFWH3E Digital I/O relay interface BMS-IFDD01EWindows-based central controller BMS-LSV Outdoor module Outdoor module Two units connected Outdoor module Three units connected Unit combinationOutdoor unit combination Master unit Slave unit Outdoor module Four units connected Unit combination Outdoor unit combination Master unitModel Accessory socket x quantity Branch header/branch jointBranch header RBM-HY1043E, HY1083E, HY2043E,HY2083E Shape branching jointRBM-BY53E, BY103E RBM-BY203E, BY303EAccessory socket Page Toshiba Air Conditioning