Toshiba HFC R-410A manual MMK-AP0241H

Page 87

Indoor unit - high-wall unit (1 Series)

MMK-AP0241H

Position of installation board hole

Space required for service

Legend

1.(Installation board)

2.Top of installation board

3.Wood screw slot 21-6 x 30

4.Anchor bolt slot 16-10 x 20

5.Air outlet

Air flow direction adjustable (up/down/left/right)

6.Air inlet

7.Gas pipe

8.Liquid pipe

9.Drain pipe

10.Supplied with pipe outlet left

11.Including installation board

12.Including installation board (accessory)

13.Earth screw (M4) (inside control box)

14.Refrigerant pipe connection (gas Ø5/8”)

15.Refrigerant pipe connection (liquid Ø3/8”)

16.Drain pipe connection

17.Pipe outlet left/right side (knockout hole)

All dimensions are given in mm.

87

Image 87
Contents Super Modular Multi Page Super Modular Multi System Contents Outline of Toshiba Super Modular Multi System S-MMS Outdoor unit Indoor unit  Energy saving design  Self-diagnostic system Compact  Largest system capacityBranching joints and headers Summary of system equipmentTechnical specifications outdoor units Technical specifications combination of outdoor unitsRated conditions Outdoor unit model line-up cooling only unitsProduct designation Combined capacity rangeMMY- M AP 000 0 H T Outdoor unit model line-up heat pump unitsTechnical specifications indoor units TCB-AX21U W-E Remote controllerSimplified remote controller Connected to indoor unit Wireless remote controller kit Connected to indoor unitWeekly timer RBC-EXW21E Connected to central remote Controller, wired remote controllerMaster Basic system configuration System legend example 8 hp system8HP 10HP Hp system10HP 10HP Hp system 10HP 10HP 10HP Outdoor unit Indoor unit Remote controller Capacity code Equipment selection procedureSelection flow chart Indoor unit and outdoor unit combinationCapacity correction value Indoor air wet bulb temperature C  Correction of outdoor unit diversity Capacity correction value Indoor air dry bulb temperature C  Correction of outdoor unit diversity Rated conditions Operating temperature rangeHeating mode Capacity calculation for each indoor unitExample of equipment selection Selection criteria for each floorOutside view Cooling Heating Procedure and result of equipment selectionAir conditioning load Equipment selection Floor Room No Indoor unit Outdoor unit Model Capacity kW Cooling HeatingLoad in each room Example Equipment selection based on system load profileMMY-AP2801T8 MMY-AP2801HT8 Schematic diagramCheck of concentration limit Refrigerant piping designLine branching system Header branching system Free branching systemAllowable length/height difference of refrigerant piping System restrictionsAllowable value Piping section Selection of refrigerant piping  Pipe size of outdoor unit Table Model nameGas side Liquid side Liquid side pipe diameter Charging requirement with additional refrigerantCalculating the amount of additional refrigerant required Charge Cooling onlyGeneral Wiring designOutdoor unit power supply Electrical wiring designControl wiring design Length Control wiring diagramControl wiring between outdoor units L5 Wiring TypeFLA MCA Mocp DesignCombination of outdoor units Heat pump Cooling only Nominal Compressor Fan motor Power supplySingle outdoor unit Heat pump Cooling only Nominal Voltage Range Ph-Hz Min MaxRange of controls to meet various system needs Control via indoor remote controllerControl via the central remote controller ControlsControl by weekly timer Applications for indoor remote controllerBasic function System diagram Model Individual control Two remote controllersFunction of central remote controller Application controls for central remote controllerBasic function System diagram Model Indoor remote controllerTCB-PCNT30TLE AvailableBMS-LSV Application control for networkTCB-1FLN BACnetBMS-TP5120ACE Indoor unit type Accessory name Model Applicable model AccessoriesIndoor unit accessories Remote controllerIndoor units Way ceiling cassettes Technical specificationsRBC-UW136PG RBC-UW266PG RBC-UY135PG RBC-US165PG RBC-US265PG Room thermostatSound pressure level high/medium/low** dBA Fan motor power inputStatic pressure factory setting Static pressure max Indoor units Standard ducted unitsIndoor units High-pressure ducted units Unit weightStatic pressure factory setting Sound power level highLower air inlet Sound power level high/medium/low Rear air inlet Sound power level high/medium/lowIndoor units Slim duct units Indoor units Ceiling-suspended units Indoor units High-wall units 1 Series Indoor units High-wall units 2 Series Indoor units Floor-mounted console units Static pressure Indoor units Concealed chassis unitsIndoor units Floor-mounted cabinet units Outdoor units Outdoor units combination DBA 74.5 DBA 75.0 24.26 Power factor, cooling Operating current, cooling 30.51 258 256 DBA 76.5 77.0 Max. number of connectable indoor units High-pressure switch Power supply ± 10% Ph-Hz 400-3-50 130.0 135.0 MMD-AP0121BH Fan characteristicsCase of square duct flange of discharge section MMD-AP0071BH, AP0091BHMMD-AP0481BH, AP0561BH MMD-AP0241BH, AP0271BHMMD-AP0361BH MMD-AP0301BHMMD-AP0361H High-pressure ducted unitMMD-AP0181H MMD-AP0241H, AP0271HMMD-AP0961H MMD-AP0721HSlim duct unit MMD-AP0071SPH, AP0091SPH MMD-AP0121SPHMMD-AP0151SPH MMD-AP0181SPH MMD-AP0151SPH Slim duct unit with filter attachedMMU-AP0091H to P0561H Dimensional drawingsAll dimensions are given in mm Indoor unit 4-way ceiling cassetteAll dimensions are given in mm View Indoor unit 2-way ceiling cassetteMMU-AP0071WH, AP0091WH, AP0121WH View Space required for installation and servicing MMU-AP0151WH, AP0181WH, AP0241WH, AP0271WH, AP0301WHModel MMU-AP0151WH to AP0181WH MMU-AP0241WH to AP0301WH MMU-AP0481WH MMU-AP0071YH, AP0091YH, AP0121YH Indoor unit 1-way ceiling cassetteMMU-AP0151SH, AP0181SH, AP0241SH View Model MMU AP0151SH, AP0181SHAP0241SH Indoor unit standard ducted unit View Space required for installation and servicing *1 Indoor unit high-pressure ducted unitMMD-AP0271H, AP0961H Bottom view excluding filter Indoor unit slim duct unitMMD-AP0071SPH, AP0091SPH, AP0121SPH, AP0151SPH, AP0181SPH Bottom view complete with filterAP0241H to AP0271H Indoor unit ceiling-suspended unitMMC-AP0151H, AP0181H, AP0241H, AP0271H, AP0361H, AP0481H Model MMC AP0151H, AP0181HMMK-AP0071H, AP0091H, AP0121H Indoor unit high-wall unit 1 SeriesMMK-AP0151H, AP0181H MMK-AP0241H MMK-AP0072H, AP0092H, AP0122H Indoor unit high-wall unit 2 SeriesMML-AP0071H, AP0091H, AP0121H, AP0151H, AP0181H, AP0241H Indoor unit floor-mounted console unitAP0151BH, AP0181H Indoor unit concealed chassis unitNo. Name Model MML AP0071BH, AP0091BH, AP0121BHSpace required for service For right-hand piping Indoor unit floor-mounted cabinet unitMMF-AP0151H, AP0181H, AP0241H, AP0271H Refrigerant pipe positions Details of hole for rear piping MMF-AP0361H, AP0481H, AP0561HRemote controller All dimensions are given in mm RBC-EXW21E Wireless remote controller kitWeekly timer TCB-AX21ETCB-IFLN Central remote controllerTCB-SC642TLE LON GatewayTCS-Net relay interface BMS-IFLSV1ETouch-screen controller BMS-TP5120ACE Intelligent server BMS-LSV2EEnergy monitoring relay interface BMS-IFWH3E Digital I/O relay interface BMS-IFDD01EWindows-based central controller BMS-LSV Outdoor module Outdoor module Two units connected Outdoor module Three units connected Unit combinationOutdoor unit combination Master unit Slave unit Unit combination Outdoor unit combination Master unit Outdoor module Four units connectedShape branching joint Model Accessory socket x quantityBranch header/branch joint Branch header RBM-HY1043E, HY1083E, HY2043E,HY2083ERBM-BY203E, BY303E RBM-BY53E, BY103EAccessory socket Page Toshiba Air Conditioning