Toshiba HFC R-410A Selection of refrigerant piping,  Pipe size of outdoor unit Table Model name

Page 32

4. Selection of refrigerant piping

 

 

 

 

 

Branching pipe

Header branching pipe

 

 

 

 

 

 

Slave

Slave

Slave

Master

 

Indoor unit connection piping

unit 3

unit 2

unit 1

unit

 

 

 

 

 

 

 

 

Outdoor unit

 

 

 

 

 

 

Balance pipe

 

 

 

 

 

 

T-shape

Y-shape

Indoor unit

 

 

 

 

branching joint

 

Outdoor unit

 

 

 

branching

 

 

 

 

 

 

connection

 

 

 

Main piping

joint

 

piping

 

 

 

 

 

 

 

 

 

 

 

 

 

Main connection

 

 

 

 

 

piping between

1st branching

Indoor unit

 

 

 

outdoor units

section

connection piping

 

Indoor unit

Pipe size of outdoor unit (Table 1)

Model name

MMY-

Gas side

Liquid side

MAP0501T8

MAP0501HT8

Ø5/8”

Ø3/8”

MAP0601T8

MAP0601HT8

Ø3/4”

Ø3/8”

MAP0801T8

MAP0801HT8

Ø7/8”

Ø1/2”

MAP1001T8

MAP1001HT8

Ø7/8”

Ø1/2”

MAP1201T8

MAP1201HT8

Ø1-1/8”

Ø1/2”

Connecting pipe size between outdoor units (Table 2)

Total capacity code of

Gas side

Liquid side

Balance pipe

outdoor units downstream

 

 

 

14 to below 22

Ø1-1/8”

Ø5/8”

Ø3/8”

22 to below 26

Ø1-3/8”

Ø5/8”

Ø3/8”

26 to below 36

Ø1-3/8”

Ø3/4”

Ø3/8”

36 or more

Ø1-5/8”

Ø7/8”

Ø3/8”

Size of main pipe (Table 3)

Total capacity code of

Gas side

Liquid side

all outdoor units (*1)

 

 

Below 6

Ø5/8”

Ø3/8”

6 to below 8

Ø3/4”

Ø3/8”

8 to below 12

Ø7/8”

Ø1/2”

12 to below 14

Ø1-1/8”

Ø1/2”

14 to below 22

Ø1-1/8”

Ø5/8”

22 to below 26

Ø1-3/8”

Ø5/8”

26 to below 36

Ø1-3/8”

Ø3/4”

36 to below 46

Ø1-5/8”

Ø7/8”

46 or more

Ø1-5/8” (*5)

Ø7/8”

Determine thickness of the main pipe according to capacity of the outdoor units.

Pipe size between branching sections (Table 4)

Total capacity code of

Gas side

Liquid side

indoor units downstream (*1)

 

 

2.8 or less

Ø1/2”

Ø3/8”

2.8 to below 6.4

Ø5/8”

Ø3/8”

6.4 to below 12.2

Ø7/8”

Ø1/2”

12.2 to below 20.2

Ø1-1/8”

Ø5/8”

20.2 to below 25.2

Ø1-3/8”

Ø5/8”

25.2 to below 35.2

Ø1-3/8”

Ø3/4”

35.2 or more

Ø1-5/8”

Ø7/8”

If the total capacity code value of indoor units exceeds that of the outdoor units, apply the capacity code of the outdoor units.

Piping of indoor unit (Table 5)

Indoor unit size

Gas side

Liquid side

007 to 012

Actual length 15 m or less

Ø3/8”

Ø1/4”

 

Actual length exceeds 15 m

Ø1/2”

Ø1/4”

015 to 018

 

Ø1/2”

Ø1/4”

024 to 056

 

Ø5/8”

Ø3/8”

072 to 096

 

Ø7/8”

Ø1/2”

Selection of branching section (Table 6)

 

 

Total capacity code of indoor unit (*1)

Model

 

Y-shape

 

Below 6.4

RBM-BY53E

branching joint

 

6.4 to below 14.2

RBM-BY103E

(*2)

 

14.2 to below 25.2

RBM-BY203E

 

 

 

25.2 or more

RBM-BY303E

 

Branching

For 4

Below 14.2

RBM-HY1043E

header

branching

14.2 to below 25.2

RBM-HY2043E

(*3)

For 8

Below 14.2

RBM-HY1083E

 

 

branching

14.2 to below 25.2

RBM-HY2083E

 

T-shape

1 set of 3 types of T-shape joint pipes as

RBM-BT13E

branching joint

described below:

 

(For connecting

The required quantity is arranged and

 

outdoor unit)

combined at the site.

 

 

 

• Balance pipe (Corresponding difference

 

 

 

Ø3/8”) × 1

 

 

 

• Piping at liquid side (Corresponding

 

 

 

difference Ø3/8” to Ø7/8”) × 1

 

 

 

• Piping at gas side (Corresponding

 

 

 

difference Ø5/8” to Ø1-5/8”) × 1

 

Minimum wall thickness for R-410A application (Table 7)

Soft

Half hard or hard

OD (Inch)

Minimum wall thickness (mm)

OK

OK

1/4”

0.80

OK

OK

3/8”

0.80

OK

OK

1/2”

0.80

OK

OK

5/8”

1.00

NG

OK (*4)

3/4”

1.00

NG

OK (*4)

7/8”

1.00

NG

OK (*4)

1-1/8”

1.00

NG

OK (*4)

1-3/8”

1.10

NG

OK (*4)

1-5/8”

1.25

*1 Code is determined according to the unit size. For details, refer to pages 7-9.

*2 When using Y-shape branching joint for 1st branching, select according to capacity code of outdoor unit.

*3 For one line after header branching, indoor units with a maximum of 6.0 capacity code in total can be connected. *4 If the pipe size is Ø3/4” or more, use a hard type or half hard type for material of the pipe.

*5 The maximum equivalent length of the main pipe should be 70 m or shorter.

32

Image 32
Contents Super Modular Multi Page Super Modular Multi System Contents Outline of Toshiba Super Modular Multi System S-MMS Outdoor unit Indoor unit  Self-diagnostic system  Compact Largest system capacity  Energy saving designSummary of system equipment Technical specifications outdoor unitsTechnical specifications combination of outdoor units Branching joints and headersOutdoor unit model line-up cooling only units Product designationCombined capacity range Rated conditionsOutdoor unit model line-up heat pump units MMY- M AP 000 0 H TTechnical specifications indoor units Remote controller Simplified remote controller Connected to indoor unitWireless remote controller kit Connected to indoor unit TCB-AX21U W-EMaster Weekly timer RBC-EXW21E Connected to central remoteController, wired remote controller 8HP Basic system configurationSystem legend example 8 hp system Hp system 10HP10HP 10HP Hp system 10HP 10HP 10HP Outdoor unit Indoor unit Remote controller Equipment selection procedure Selection flow chartIndoor unit and outdoor unit combination Capacity codeCapacity correction value Indoor air wet bulb temperature C  Correction of outdoor unit diversity Capacity correction value Indoor air dry bulb temperature C  Correction of outdoor unit diversity Operating temperature range Heating modeCapacity calculation for each indoor unit Rated conditionsOutside view Example of equipment selectionSelection criteria for each floor Procedure and result of equipment selection Air conditioning load Equipment selection Floor Room NoIndoor unit Outdoor unit Model Capacity kW Cooling Heating Cooling HeatingExample Equipment selection based on system load profile Load in each roomSchematic diagram MMY-AP2801T8 MMY-AP2801HT8Refrigerant piping design Check of concentration limitFree branching system Line branching system Header branching systemAllowable value Piping section Allowable length/height difference of refrigerant pipingSystem restrictions Gas side Liquid side Selection of refrigerant piping Pipe size of outdoor unit Table Model name Charging requirement with additional refrigerant Calculating the amount of additional refrigerant requiredCharge Cooling only Liquid side pipe diameterWiring design Outdoor unit power supplyElectrical wiring design GeneralControl wiring design Control wiring diagram Control wiring between outdoor units L5 WiringType LengthDesign FLA MCA MocpCompressor Fan motor Power supply Single outdoor unit Heat pump Cooling only NominalVoltage Range Ph-Hz Min Max Combination of outdoor units Heat pump Cooling only NominalControl via indoor remote controller Control via the central remote controllerControls Range of controls to meet various system needsApplications for indoor remote controller Basic function System diagram Model Individual controlTwo remote controllers Control by weekly timerApplication controls for central remote controller Basic function System diagram ModelIndoor remote controller Function of central remote controllerAvailable TCB-PCNT30TLEApplication control for network TCB-1FLNBACnet BMS-LSVBMS-TP5120ACE Accessories Indoor unit accessoriesRemote controller Indoor unit type Accessory name Model Applicable modelTechnical specifications Indoor units Way ceiling cassettesRBC-UW136PG RBC-UW266PG Room thermostat RBC-UY135PG RBC-US165PG RBC-US265PGFan motor power input Static pressure factory setting Static pressure maxIndoor units Standard ducted units Sound pressure level high/medium/low** dBAUnit weight Static pressure factory settingSound power level high Indoor units High-pressure ducted unitsIndoor units Slim duct units Lower air inlet Sound power level high/medium/lowRear air inlet Sound power level high/medium/low Indoor units Ceiling-suspended units Indoor units High-wall units 1 Series Indoor units High-wall units 2 Series Indoor units Floor-mounted console units Indoor units Concealed chassis units Static pressureIndoor units Floor-mounted cabinet units Outdoor units Outdoor units combination DBA 74.5 DBA 75.0 24.26 Power factor, cooling Operating current, cooling 30.51 258 256 DBA 76.5 77.0 Max. number of connectable indoor units High-pressure switch Power supply ± 10% Ph-Hz 400-3-50 130.0 135.0 Fan characteristics Case of square duct flange of discharge sectionMMD-AP0071BH, AP0091BH MMD-AP0121BHMMD-AP0241BH, AP0271BH MMD-AP0361BHMMD-AP0301BH MMD-AP0481BH, AP0561BHHigh-pressure ducted unit MMD-AP0181HMMD-AP0241H, AP0271H MMD-AP0361HMMD-AP0721H MMD-AP0961HMMD-AP0151SPH MMD-AP0181SPH Slim duct unitMMD-AP0071SPH, AP0091SPH MMD-AP0121SPH Slim duct unit with filter attached MMD-AP0151SPHDimensional drawings All dimensions are given in mmIndoor unit 4-way ceiling cassette MMU-AP0091H to P0561HMMU-AP0071WH, AP0091WH, AP0121WH All dimensions are given in mm ViewIndoor unit 2-way ceiling cassette Model MMU-AP0151WH to AP0181WH MMU-AP0241WH to AP0301WH View Space required for installation and servicingMMU-AP0151WH, AP0181WH, AP0241WH, AP0271WH, AP0301WH MMU-AP0481WH Indoor unit 1-way ceiling cassette MMU-AP0071YH, AP0091YH, AP0121YHAP0241SH MMU-AP0151SH, AP0181SH, AP0241SHView Model MMU AP0151SH, AP0181SH Indoor unit standard ducted unit MMD-AP0271H, AP0961H View Space required for installation and servicing *1Indoor unit high-pressure ducted unit Indoor unit slim duct unit MMD-AP0071SPH, AP0091SPH, AP0121SPH, AP0151SPH, AP0181SPHBottom view complete with filter Bottom view excluding filterIndoor unit ceiling-suspended unit MMC-AP0151H, AP0181H, AP0241H, AP0271H, AP0361H, AP0481HModel MMC AP0151H, AP0181H AP0241H to AP0271HIndoor unit high-wall unit 1 Series MMK-AP0071H, AP0091H, AP0121HMMK-AP0151H, AP0181H MMK-AP0241H Indoor unit high-wall unit 2 Series MMK-AP0072H, AP0092H, AP0122HIndoor unit floor-mounted console unit MML-AP0071H, AP0091H, AP0121H, AP0151H, AP0181H, AP0241HIndoor unit concealed chassis unit No. NameModel MML AP0071BH, AP0091BH, AP0121BH AP0151BH, AP0181HMMF-AP0151H, AP0181H, AP0241H, AP0271H Space required for service For right-hand pipingIndoor unit floor-mounted cabinet unit MMF-AP0361H, AP0481H, AP0561H Refrigerant pipe positions Details of hole for rear pipingRemote controller All dimensions are given in mm Wireless remote controller kit Weekly timerTCB-AX21E RBC-EXW21ECentral remote controller TCB-SC642TLELON Gateway TCB-IFLNTouch-screen controller BMS-TP5120ACE TCS-Net relay interfaceBMS-IFLSV1E Energy monitoring relay interface BMS-IFWH3E Intelligent serverBMS-LSV2E Windows-based central controller BMS-LSV Digital I/O relay interfaceBMS-IFDD01E Outdoor module Outdoor module Two units connected Outdoor unit combination Master unit Slave unit Outdoor module Three units connectedUnit combination Outdoor module Four units connected Unit combination Outdoor unit combination Master unitModel Accessory socket x quantity Branch header/branch jointBranch header RBM-HY1043E, HY1083E, HY2043E,HY2083E Shape branching jointRBM-BY53E, BY103E RBM-BY203E, BY303EAccessory socket Page Toshiba Air Conditioning