Toshiba HFC R-410A manual Summary of system equipment, Technical specifications outdoor units

Page 7

2.Summary of system equipment

Technical specifications - outdoor units

Rating

hp

5

6

8

10

12

 

Cooling only model MMY-MAP

 

0501T8

0601T8

0801T8

1001T8

1201T8

 

Heat pump model MMY-MAP

 

0501HT8

0601HT8

0801HT8

1001HT8

1201HT8

Cooling capacity

kW

14.0

16.0

22.4

28.0

33.5

 

Heating capacity

kW

16.0

18.0

25.0

31.5

37.5

 

Technical specifications - combination of outdoor units

Rating

hp

5

6

8

10

12

14

16

Cooling only model MMY-MAP

 

0501T8

0601T8

0801T8

1001T8

1201T8

1401T8

1601T8

Heat pump model MMY-MAP

 

0501HT8

0601HT8

0801HT8

1001HT8

1201HT8

1401HT8

1601HT8

Cooling capacity

kW

14.0

16.0

22.4

28.0

33.5

38.4

45.0

Heating capacity

kW

16.0

18.0

25.0

31.5

37.5

43.0

50.0

Combined outdoor units

hp

5

6

8

10

12

8

8

 

 

-

-

-

-

-

6

8

No. of connectable indoor units

 

8

10

13

16

20

23

27

Rating

hp

18

20

22

22

24

24

26

Cooling only model MMY-MAP

 

1801T8

2001T8

2201T8

2211T8

2401T8

2411T8

2601T8

Heat pump model MMY-MAP

 

1801HT8

2001HT8

2201HT8

2211HT8

2401HT8

2411HT8

2601HT8

Cooling capacity

kW

50.4

56.0

61.5

61.5

68.0

68.0

73.0

Heating capacity

kW

56.5

63.0

69.0

69.0

76.5

76.5

81.5

Combined outdoor units

hp

10

10

8

12

8

12

10

 

 

8

10

8

10

8

12

8

 

 

-

-

6

-

8

-

8

No. of connectable indoor units

 

30

33

37

37

40

40

43

Rating

hp

28

30

32

32

34

34

36

Cooling only model MMY-MAP

 

2801T8

3001T8

3201T8

3211T8

3401T8

3411T8

3601T8

Heat pump model MMY-MAP

 

2801HT8

3001HT8

3201HT8

3211HT8

3401HT8

3411HT8

3601HT8

Cooling capacity

kW

78.5

84.0

90.0

90.0

96.0

96.0

101.0

Heating capacity

kW

88.0

95.0

100.0

100.0

108.0

108.0

113.0

Combined outdoor units

hp

10

10

8

12

10

12

10

 

 

10

10

8

10

8

12

10

 

 

8

10

8

10

8

10

8

 

 

-

-

8

-

8

-

8

No. of connectable indoor units

 

47

48

48

48

48

48

48

Rating

hp

36

38

40

42

44

46

48

Cooling only model MMY-MAP

 

3611T8

3801T8

4001T8

4201T8

4401T8

4601T8

4801T8

Heat pump model MMY-MAP

 

3611HT8

3801HT8

4001HT8

4201HT8

4401HT8

4601HT8

4801HT8

Cooling capacity

kW

101.0

106.5

112.0

118.0

123.5

130.0

135.0

Heating capacity

kW

113.0

119.5

126.5

132.0

138.0

145.0

150.0

Combined outdoor units

hp

12

10

10

12

12

12

12

 

 

12

10

10

10

12

12

12

 

 

12

10

10

10

10

12

12

 

 

-

8

10

10

10

10

12

No. of connectable indoor units

 

48

48

48

48

48

48

48

Branching joints and headers

 

Model

 

Usage

 

 

 

 

Appearance

Y-shape branching joint (*3)

RBM-BY53E

 

Indoor unit capacity code (*1) : Total below 6.4

 

 

 

 

 

 

 

RBM-BY103E

 

Indoor unit capacity code (*1) : Total 6.4 or more and below 14.2

(*2)

 

 

 

 

 

 

 

 

 

 

RBM-BY203E

 

Indoor unit capacity code (*1) : Total 14.2 or more and below 25.2

(*2)

 

 

 

 

 

RBM-BY303E

 

Indoor unit capacity code (*1) : Total 25.2 or more

(*2)

 

 

 

 

4-branching header (*4)

RBM-HY1043E

 

Indoor unit capacity code (*1) : Total below 14.2

 

Max.4

 

 

RBM-HY2043E

 

Indoor unit capacity code (*1) : Total 14.2 or more and below 25.2

 

branches

 

8-branching header (*4) (*5)

RBM-HY1083E

 

Indoor unit capacity code (*1) : Total below 14.2

 

Max.8

 

 

 

 

RBM-HY2083E

 

Indoor unit capacity code (*1) : Total 14.2 or more and below 25.2

 

branches

 

T-shape branching joint

RBM-BT13E

 

1 set of 3 types of T-shape joint pipes as described below:

 

 

 

 

 

 

(For connection of

 

 

The required quantity is arranged and they are combined at the site.

outdoor units)

 

 

 

 

 

 

 

 

 

 

 

 

 

Connection piping

Corresponding dia. (mm)

Q’ty

 

 

 

 

 

 

 

Balance pipe

Ø3/8”

1

 

 

 

 

 

 

 

Liquid side piping

Ø3/8” to Ø7/8”

1

 

 

 

 

 

 

 

Gas side piping

Ø5/8” to Ø1-5/8”

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*1 The capacity code can be obtained from page 10 (capacity code is not actual capacity).

*2 If total capacity code value of indoor unit exceeds that of outdoor unit, apply capacity code of outdoor unit.

*3 When using Y-shape branching joint for 1st branching, select according to capacity code of outdoor unit.

*4 Max. 6.0 capacity code in total can be connected.

*5 If capacity code of outdoor unit is 26 and more, it is not used for 1st branching.

*6 Model names for outdoor and indoor units described in this guide are shortened because of the space constraints.

7

Image 7
Contents Super Modular Multi Page Super Modular Multi System Contents Outline of Toshiba Super Modular Multi System S-MMS Outdoor unit Indoor unit  Energy saving design  Self-diagnostic system Compact  Largest system capacityBranching joints and headers Summary of system equipmentTechnical specifications outdoor units Technical specifications combination of outdoor unitsRated conditions Outdoor unit model line-up cooling only unitsProduct designation Combined capacity rangeMMY- M AP 000 0 H T Outdoor unit model line-up heat pump unitsTechnical specifications indoor units TCB-AX21U W-E Remote controllerSimplified remote controller Connected to indoor unit Wireless remote controller kit Connected to indoor unitController, wired remote controller Weekly timer RBC-EXW21E Connected to central remoteMaster System legend example 8 hp system Basic system configuration8HP 10HP Hp system10HP 10HP Hp system 10HP 10HP 10HP Outdoor unit Indoor unit Remote controller Capacity code Equipment selection procedureSelection flow chart Indoor unit and outdoor unit combinationCapacity correction value Indoor air wet bulb temperature C  Correction of outdoor unit diversity Capacity correction value Indoor air dry bulb temperature C  Correction of outdoor unit diversity Rated conditions Operating temperature rangeHeating mode Capacity calculation for each indoor unitSelection criteria for each floor Example of equipment selectionOutside view Cooling Heating Procedure and result of equipment selectionAir conditioning load Equipment selection Floor Room No Indoor unit Outdoor unit Model Capacity kW Cooling HeatingLoad in each room Example Equipment selection based on system load profileMMY-AP2801T8 MMY-AP2801HT8 Schematic diagramCheck of concentration limit Refrigerant piping designLine branching system Header branching system Free branching systemSystem restrictions Allowable length/height difference of refrigerant pipingAllowable value Piping section  Pipe size of outdoor unit Table Model name Selection of refrigerant pipingGas side Liquid side Liquid side pipe diameter Charging requirement with additional refrigerantCalculating the amount of additional refrigerant required Charge Cooling onlyGeneral Wiring designOutdoor unit power supply Electrical wiring designControl wiring design Length Control wiring diagramControl wiring between outdoor units L5 Wiring TypeFLA MCA Mocp DesignCombination of outdoor units Heat pump Cooling only Nominal Compressor Fan motor Power supplySingle outdoor unit Heat pump Cooling only Nominal Voltage Range Ph-Hz Min MaxRange of controls to meet various system needs Control via indoor remote controllerControl via the central remote controller ControlsControl by weekly timer Applications for indoor remote controllerBasic function System diagram Model Individual control Two remote controllersFunction of central remote controller Application controls for central remote controllerBasic function System diagram Model Indoor remote controllerTCB-PCNT30TLE AvailableBMS-LSV Application control for networkTCB-1FLN BACnetBMS-TP5120ACE Indoor unit type Accessory name Model Applicable model AccessoriesIndoor unit accessories Remote controllerIndoor units Way ceiling cassettes Technical specificationsRBC-UW136PG RBC-UW266PG RBC-UY135PG RBC-US165PG RBC-US265PG Room thermostatSound pressure level high/medium/low** dBA Fan motor power inputStatic pressure factory setting Static pressure max Indoor units Standard ducted unitsIndoor units High-pressure ducted units Unit weightStatic pressure factory setting Sound power level highRear air inlet Sound power level high/medium/low Lower air inlet Sound power level high/medium/lowIndoor units Slim duct units Indoor units Ceiling-suspended units Indoor units High-wall units 1 Series Indoor units High-wall units 2 Series Indoor units Floor-mounted console units Static pressure Indoor units Concealed chassis unitsIndoor units Floor-mounted cabinet units Outdoor units Outdoor units combination DBA 74.5 DBA 75.0 24.26 Power factor, cooling Operating current, cooling 30.51 258 256 DBA 76.5 77.0 Max. number of connectable indoor units High-pressure switch Power supply ± 10% Ph-Hz 400-3-50 130.0 135.0 MMD-AP0121BH Fan characteristicsCase of square duct flange of discharge section MMD-AP0071BH, AP0091BHMMD-AP0481BH, AP0561BH MMD-AP0241BH, AP0271BHMMD-AP0361BH MMD-AP0301BHMMD-AP0361H High-pressure ducted unitMMD-AP0181H MMD-AP0241H, AP0271HMMD-AP0961H MMD-AP0721HMMD-AP0071SPH, AP0091SPH MMD-AP0121SPH Slim duct unitMMD-AP0151SPH MMD-AP0181SPH MMD-AP0151SPH Slim duct unit with filter attachedMMU-AP0091H to P0561H Dimensional drawingsAll dimensions are given in mm Indoor unit 4-way ceiling cassetteIndoor unit 2-way ceiling cassette All dimensions are given in mm ViewMMU-AP0071WH, AP0091WH, AP0121WH MMU-AP0151WH, AP0181WH, AP0241WH, AP0271WH, AP0301WH View Space required for installation and servicingModel MMU-AP0151WH to AP0181WH MMU-AP0241WH to AP0301WH MMU-AP0481WH MMU-AP0071YH, AP0091YH, AP0121YH Indoor unit 1-way ceiling cassetteView Model MMU AP0151SH, AP0181SH MMU-AP0151SH, AP0181SH, AP0241SHAP0241SH Indoor unit standard ducted unit Indoor unit high-pressure ducted unit View Space required for installation and servicing *1MMD-AP0271H, AP0961H Bottom view excluding filter Indoor unit slim duct unitMMD-AP0071SPH, AP0091SPH, AP0121SPH, AP0151SPH, AP0181SPH Bottom view complete with filterAP0241H to AP0271H Indoor unit ceiling-suspended unitMMC-AP0151H, AP0181H, AP0241H, AP0271H, AP0361H, AP0481H Model MMC AP0151H, AP0181HMMK-AP0071H, AP0091H, AP0121H Indoor unit high-wall unit 1 SeriesMMK-AP0151H, AP0181H MMK-AP0241H MMK-AP0072H, AP0092H, AP0122H Indoor unit high-wall unit 2 SeriesMML-AP0071H, AP0091H, AP0121H, AP0151H, AP0181H, AP0241H Indoor unit floor-mounted console unitAP0151BH, AP0181H Indoor unit concealed chassis unitNo. Name Model MML AP0071BH, AP0091BH, AP0121BHIndoor unit floor-mounted cabinet unit Space required for service For right-hand pipingMMF-AP0151H, AP0181H, AP0241H, AP0271H Refrigerant pipe positions Details of hole for rear piping MMF-AP0361H, AP0481H, AP0561HRemote controller All dimensions are given in mm RBC-EXW21E Wireless remote controller kitWeekly timer TCB-AX21ETCB-IFLN Central remote controllerTCB-SC642TLE LON GatewayBMS-IFLSV1E TCS-Net relay interfaceTouch-screen controller BMS-TP5120ACE BMS-LSV2E Intelligent serverEnergy monitoring relay interface BMS-IFWH3E BMS-IFDD01E Digital I/O relay interfaceWindows-based central controller BMS-LSV Outdoor module Outdoor module Two units connected Unit combination Outdoor module Three units connectedOutdoor unit combination Master unit Slave unit Unit combination Outdoor unit combination Master unit Outdoor module Four units connectedShape branching joint Model Accessory socket x quantityBranch header/branch joint Branch header RBM-HY1043E, HY1083E, HY2043E,HY2083ERBM-BY203E, BY303E RBM-BY53E, BY103EAccessory socket Page Toshiba Air Conditioning