Toshiba HFC R-410A manual Indoor unit high-wall unit 1 Series, MMK-AP0071H, AP0091H, AP0121H

Page 85

Indoor unit - high-wall unit (1 Series)

MMK-AP0071H, AP0091H, AP0121H

Position of installation board hole

Space required for service

30 min.

Wired remote controller (RBC-AMT31E)

Legend

9.

Drain pipe

1.

(Installation board)

10.

Supplied with pipe outlet left

2.

Top of installation board

11.

Including installation board

3.

Wood screw slot 15-6 x 30

12.

Including installation board (accessory)

4.

Anchor bolt slot 10-10 x 20

13.

Earth screw (M4) (inside control box)

5.

Air outlet

14.

Refrigerant pipe connection (gas Ø3/8”)

 

Air flow direction adjustable (up/down/left/right)

15.

Refrigerant pipe connection (liquid Ø1/4”)

6.

Air inlet

16.

Drain pipe connection

7.

Gas pipe

17.

Pipe outlet left/right side (knockout hole)

8.Liquid pipe

All dimensions are given in mm.

85

Image 85
Contents Super Modular Multi Page Super Modular Multi System Contents Outline of Toshiba Super Modular Multi System S-MMS Outdoor unit Indoor unit  Compact  Self-diagnostic system Largest system capacity  Energy saving designTechnical specifications outdoor units Summary of system equipmentTechnical specifications combination of outdoor units Branching joints and headersProduct designation Outdoor unit model line-up cooling only unitsCombined capacity range Rated conditionsMMY- M AP 000 0 H T Outdoor unit model line-up heat pump unitsTechnical specifications indoor units Simplified remote controller Connected to indoor unit Remote controllerWireless remote controller kit Connected to indoor unit TCB-AX21U W-EController, wired remote controller Weekly timer RBC-EXW21E Connected to central remoteMaster System legend example 8 hp system Basic system configuration8HP 10HP Hp system10HP 10HP Hp system 10HP 10HP 10HP Outdoor unit Indoor unit Remote controller Selection flow chart Equipment selection procedureIndoor unit and outdoor unit combination Capacity codeCapacity correction value Indoor air wet bulb temperature C  Correction of outdoor unit diversity Capacity correction value Indoor air dry bulb temperature C  Correction of outdoor unit diversity Heating mode Operating temperature rangeCapacity calculation for each indoor unit Rated conditionsSelection criteria for each floor Example of equipment selectionOutside view Air conditioning load Equipment selection Floor Room No Procedure and result of equipment selectionIndoor unit Outdoor unit Model Capacity kW Cooling Heating Cooling HeatingLoad in each room Example Equipment selection based on system load profileMMY-AP2801T8 MMY-AP2801HT8 Schematic diagramCheck of concentration limit Refrigerant piping designLine branching system Header branching system Free branching systemSystem restrictions Allowable length/height difference of refrigerant pipingAllowable value Piping section  Pipe size of outdoor unit Table Model name Selection of refrigerant pipingGas side Liquid side Calculating the amount of additional refrigerant required Charging requirement with additional refrigerantCharge Cooling only Liquid side pipe diameterOutdoor unit power supply Wiring designElectrical wiring design GeneralControl wiring design Control wiring between outdoor units L5 Wiring Control wiring diagramType LengthFLA MCA Mocp DesignSingle outdoor unit Heat pump Cooling only Nominal Compressor Fan motor Power supplyVoltage Range Ph-Hz Min Max Combination of outdoor units Heat pump Cooling only NominalControl via the central remote controller Control via indoor remote controllerControls Range of controls to meet various system needsBasic function System diagram Model Individual control Applications for indoor remote controllerTwo remote controllers Control by weekly timerBasic function System diagram Model Application controls for central remote controllerIndoor remote controller Function of central remote controllerTCB-PCNT30TLE AvailableTCB-1FLN Application control for networkBACnet BMS-LSVBMS-TP5120ACE Indoor unit accessories AccessoriesRemote controller Indoor unit type Accessory name Model Applicable modelIndoor units Way ceiling cassettes Technical specificationsRBC-UW136PG RBC-UW266PG RBC-UY135PG RBC-US165PG RBC-US265PG Room thermostatStatic pressure factory setting Static pressure max Fan motor power inputIndoor units Standard ducted units Sound pressure level high/medium/low** dBAStatic pressure factory setting Unit weightSound power level high Indoor units High-pressure ducted unitsRear air inlet Sound power level high/medium/low Lower air inlet Sound power level high/medium/lowIndoor units Slim duct units Indoor units Ceiling-suspended units Indoor units High-wall units 1 Series Indoor units High-wall units 2 Series Indoor units Floor-mounted console units Static pressure Indoor units Concealed chassis unitsIndoor units Floor-mounted cabinet units Outdoor units Outdoor units combination DBA 74.5 DBA 75.0 24.26 Power factor, cooling Operating current, cooling 30.51 258 256 DBA 76.5 77.0 Max. number of connectable indoor units High-pressure switch Power supply ± 10% Ph-Hz 400-3-50 130.0 135.0 Case of square duct flange of discharge section Fan characteristicsMMD-AP0071BH, AP0091BH MMD-AP0121BHMMD-AP0361BH MMD-AP0241BH, AP0271BHMMD-AP0301BH MMD-AP0481BH, AP0561BHMMD-AP0181H High-pressure ducted unitMMD-AP0241H, AP0271H MMD-AP0361HMMD-AP0961H MMD-AP0721HMMD-AP0071SPH, AP0091SPH MMD-AP0121SPH Slim duct unitMMD-AP0151SPH MMD-AP0181SPH MMD-AP0151SPH Slim duct unit with filter attachedAll dimensions are given in mm Dimensional drawingsIndoor unit 4-way ceiling cassette MMU-AP0091H to P0561HIndoor unit 2-way ceiling cassette All dimensions are given in mm ViewMMU-AP0071WH, AP0091WH, AP0121WH MMU-AP0151WH, AP0181WH, AP0241WH, AP0271WH, AP0301WH View Space required for installation and servicingModel MMU-AP0151WH to AP0181WH MMU-AP0241WH to AP0301WH MMU-AP0481WH MMU-AP0071YH, AP0091YH, AP0121YH Indoor unit 1-way ceiling cassetteView Model MMU AP0151SH, AP0181SH MMU-AP0151SH, AP0181SH, AP0241SHAP0241SH Indoor unit standard ducted unit Indoor unit high-pressure ducted unit View Space required for installation and servicing *1MMD-AP0271H, AP0961H MMD-AP0071SPH, AP0091SPH, AP0121SPH, AP0151SPH, AP0181SPH Indoor unit slim duct unitBottom view complete with filter Bottom view excluding filterMMC-AP0151H, AP0181H, AP0241H, AP0271H, AP0361H, AP0481H Indoor unit ceiling-suspended unitModel MMC AP0151H, AP0181H AP0241H to AP0271HMMK-AP0071H, AP0091H, AP0121H Indoor unit high-wall unit 1 SeriesMMK-AP0151H, AP0181H MMK-AP0241H MMK-AP0072H, AP0092H, AP0122H Indoor unit high-wall unit 2 SeriesMML-AP0071H, AP0091H, AP0121H, AP0151H, AP0181H, AP0241H Indoor unit floor-mounted console unitNo. Name Indoor unit concealed chassis unitModel MML AP0071BH, AP0091BH, AP0121BH AP0151BH, AP0181HIndoor unit floor-mounted cabinet unit Space required for service For right-hand pipingMMF-AP0151H, AP0181H, AP0241H, AP0271H Refrigerant pipe positions Details of hole for rear piping MMF-AP0361H, AP0481H, AP0561HRemote controller All dimensions are given in mm Weekly timer Wireless remote controller kitTCB-AX21E RBC-EXW21ETCB-SC642TLE Central remote controllerLON Gateway TCB-IFLNBMS-IFLSV1E TCS-Net relay interfaceTouch-screen controller BMS-TP5120ACE BMS-LSV2E Intelligent serverEnergy monitoring relay interface BMS-IFWH3E BMS-IFDD01E Digital I/O relay interfaceWindows-based central controller BMS-LSV Outdoor module Outdoor module Two units connected Unit combination Outdoor module Three units connectedOutdoor unit combination Master unit Slave unit Unit combination Outdoor unit combination Master unit Outdoor module Four units connectedBranch header/branch joint Model Accessory socket x quantityBranch header RBM-HY1043E, HY1083E, HY2043E,HY2083E Shape branching jointRBM-BY203E, BY303E RBM-BY53E, BY103EAccessory socket Page Toshiba Air Conditioning