Toshiba HFC R-410A manual Technical specifications, Indoor units Way ceiling cassettes

Page 46

9.Technical specifications

Indoor units

4-way ceiling cassettes

Model MMU-AP

 

0091H

0121H

0151H

0181H

0241H

0271H

0301H

0361H

0481H

0561H

Cooling capacity*

kW

2.8

3.6

4.5

5.6

7.1

8.0

9.0

11.2

14.0

16.0

Heating capacity

kW

3.2

4.0

5.0

6.3

8.0

9.0

10.0

12.5

16.0

18.0

Electrical data

 

 

 

 

 

 

 

 

 

 

 

Power supply

V-ph-Hz

230-1-50 (voltage range 220-240 V) - power supply to indoor unit only

 

 

 

Operating current

A

0.17

0.17

0.19

0.21

0.24

0.24

0.35

0.59

0.81

0.83

Power input

kW

0.020

0.020

0.022

0.026

0.032

0.032

0.048

0.070

0.110

0.112

Starting current

A

0.30

0.30

0.33

0.36

0.42

0.42

0.59

0.87

1.23

1.26

Unit appearance

 

Zinc hot dipping steel plate - heat insulating material attached

 

 

 

 

Unit dimensions

 

 

 

 

 

 

 

 

 

 

 

Height

mm

256

256

256

256

256

256

256

319

319

319

Width

mm

840

840

840

840

840

840

840

840

840

840

Depth

mm

840

840

840

840

840

840

840

840

840

840

Unit weight

kg

20

20

22

22

23

23

23

28

28

28

Heat exchanger

 

Finned tube

 

 

 

 

 

 

 

 

Sound proofing/heat insulating material

 

Non-flammable insulation

 

 

 

 

 

 

 

Fan type

 

Turbo fan

 

 

 

 

 

 

 

 

 

Fan motor power input

W

60

60

60

60

60

60

60

90

90

90

Air flow

 

 

 

 

 

 

 

 

 

 

 

High

l/s

222

222

258

292

333

333

367

467

567

581

Medium

l/s

203

203

231

256

256

256

308

361

397

422

Low

l/s

189

189

219

222

228

228

236

297

314

342

Air flow

 

 

 

 

 

 

 

 

 

 

 

High

m3/h

800

800

930

1050

1200

1200

1320

1680

2040

2090

Medium

m3/h

730

730

830

920

920

920

1110

1300

1430

1520

Low

m3/h

680

680

790

800

820

820

850

1070

1130

1230

Sound power level (high/medium/low)

dB(A)

43/42/40

43/42/40

44/42/40

45/42/41

47/44/41

47/44/41

50/46/43

53/49/46

57/51/47

58/53/47

Sound pressure level (high/medium/low)**

dB(A)

30/29/27

30/29/27

31/29/27

32/29/28

34/31/28

34/31/28

37/33/30

40/36/33

44/38/34

45/40/34

Air filter

 

Standard long-life filter supplied

 

 

 

 

 

 

 

Controller

 

Remote controller

 

 

 

 

 

 

 

 

Connection pipes

 

 

 

 

 

 

 

 

 

 

 

Gas connection diameter

in

3/8

3/8

1/2

1/2

5/8

5/8

5/8

5/8

5/8

5/8

Liquid connection diameter

in

1/4

1/4

1/4

1/4

3/8

3/8

3/8

3/8

3/8

3/8

Drain connection, nom. dia (polyvinyl tube)

in

1

1

1

1

1

1

1

1

1

1

Ceiling panel model number

 

RBC-U21PG (W)-E

 

 

 

 

 

 

 

 

Panel colour

 

Moon white (Munsell/2.5GY 9.0/0.5)

 

 

 

 

 

 

Panel dimensions

 

 

 

 

 

 

 

 

 

 

 

Height

mm

35

35

35

35

35

35

35

35

35

35

Width

mm

950

950

950

950

950

950

950

950

950

950

Depth

mm

950

950

950

950

950

950

950

950

950

950

Panel weight

kg

4.5

4.5

4.5

4.5

4.5

4.5

4.5

4.5

4.5

4.5

Rated conditions: Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db

Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb

*Cooling capacities and electrical data are measured at the conditions specified by JIS B 8615, based on the reference piping which consists of 5 m of main piping and 2.5 m of branch piping connected with 0 metre height.

**The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating environment become larger than the indicated values due to the effects of external sound.

46

Image 46
Contents Super Modular Multi Page Super Modular Multi System Contents Outline of Toshiba Super Modular Multi System S-MMS Outdoor unit Indoor unit  Largest system capacity  Self-diagnostic system Compact  Energy saving designTechnical specifications combination of outdoor units Summary of system equipmentTechnical specifications outdoor units Branching joints and headersCombined capacity range Outdoor unit model line-up cooling only unitsProduct designation Rated conditionsOutdoor unit model line-up heat pump units MMY- M AP 000 0 H TTechnical specifications indoor units Wireless remote controller kit Connected to indoor unit Remote controllerSimplified remote controller Connected to indoor unit TCB-AX21U W-EController, wired remote controller Weekly timer RBC-EXW21E Connected to central remoteMaster System legend example 8 hp system Basic system configuration8HP Hp system 10HP10HP 10HP Hp system 10HP 10HP 10HP Outdoor unit Indoor unit Remote controller Indoor unit and outdoor unit combination Equipment selection procedureSelection flow chart Capacity codeCapacity correction value Indoor air wet bulb temperature C  Correction of outdoor unit diversity Capacity correction value Indoor air dry bulb temperature C  Correction of outdoor unit diversity Capacity calculation for each indoor unit Operating temperature rangeHeating mode Rated conditionsSelection criteria for each floor Example of equipment selectionOutside view Indoor unit Outdoor unit Model Capacity kW Cooling Heating Procedure and result of equipment selectionAir conditioning load Equipment selection Floor Room No Cooling HeatingExample Equipment selection based on system load profile Load in each roomSchematic diagram MMY-AP2801T8 MMY-AP2801HT8Refrigerant piping design Check of concentration limitFree branching system Line branching system Header branching systemSystem restrictions Allowable length/height difference of refrigerant pipingAllowable value Piping section  Pipe size of outdoor unit Table Model name Selection of refrigerant pipingGas side Liquid side Charge Cooling only Charging requirement with additional refrigerantCalculating the amount of additional refrigerant required Liquid side pipe diameterElectrical wiring design Wiring designOutdoor unit power supply GeneralControl wiring design Type Control wiring diagramControl wiring between outdoor units L5 Wiring LengthDesign FLA MCA MocpVoltage Range Ph-Hz Min Max Compressor Fan motor Power supplySingle outdoor unit Heat pump Cooling only Nominal Combination of outdoor units Heat pump Cooling only NominalControls Control via indoor remote controllerControl via the central remote controller Range of controls to meet various system needsTwo remote controllers Applications for indoor remote controllerBasic function System diagram Model Individual control Control by weekly timerIndoor remote controller Application controls for central remote controllerBasic function System diagram Model Function of central remote controllerAvailable TCB-PCNT30TLEBACnet Application control for networkTCB-1FLN BMS-LSVBMS-TP5120ACE Remote controller AccessoriesIndoor unit accessories Indoor unit type Accessory name Model Applicable modelTechnical specifications Indoor units Way ceiling cassettesRBC-UW136PG RBC-UW266PG Room thermostat RBC-UY135PG RBC-US165PG RBC-US265PGIndoor units Standard ducted units Fan motor power inputStatic pressure factory setting Static pressure max Sound pressure level high/medium/low** dBASound power level high Unit weightStatic pressure factory setting Indoor units High-pressure ducted unitsRear air inlet Sound power level high/medium/low Lower air inlet Sound power level high/medium/lowIndoor units Slim duct units Indoor units Ceiling-suspended units Indoor units High-wall units 1 Series Indoor units High-wall units 2 Series Indoor units Floor-mounted console units Indoor units Concealed chassis units Static pressureIndoor units Floor-mounted cabinet units Outdoor units Outdoor units combination DBA 74.5 DBA 75.0 24.26 Power factor, cooling Operating current, cooling 30.51 258 256 DBA 76.5 77.0 Max. number of connectable indoor units High-pressure switch Power supply ± 10% Ph-Hz 400-3-50 130.0 135.0 MMD-AP0071BH, AP0091BH Fan characteristicsCase of square duct flange of discharge section MMD-AP0121BHMMD-AP0301BH MMD-AP0241BH, AP0271BHMMD-AP0361BH MMD-AP0481BH, AP0561BHMMD-AP0241H, AP0271H High-pressure ducted unitMMD-AP0181H MMD-AP0361HMMD-AP0721H MMD-AP0961HMMD-AP0071SPH, AP0091SPH MMD-AP0121SPH Slim duct unitMMD-AP0151SPH MMD-AP0181SPH Slim duct unit with filter attached MMD-AP0151SPHIndoor unit 4-way ceiling cassette Dimensional drawingsAll dimensions are given in mm MMU-AP0091H to P0561HIndoor unit 2-way ceiling cassette All dimensions are given in mm ViewMMU-AP0071WH, AP0091WH, AP0121WH MMU-AP0151WH, AP0181WH, AP0241WH, AP0271WH, AP0301WH View Space required for installation and servicingModel MMU-AP0151WH to AP0181WH MMU-AP0241WH to AP0301WH MMU-AP0481WH Indoor unit 1-way ceiling cassette MMU-AP0071YH, AP0091YH, AP0121YHView Model MMU AP0151SH, AP0181SH MMU-AP0151SH, AP0181SH, AP0241SHAP0241SH Indoor unit standard ducted unit Indoor unit high-pressure ducted unit View Space required for installation and servicing *1MMD-AP0271H, AP0961H Bottom view complete with filter Indoor unit slim duct unitMMD-AP0071SPH, AP0091SPH, AP0121SPH, AP0151SPH, AP0181SPH Bottom view excluding filterModel MMC AP0151H, AP0181H Indoor unit ceiling-suspended unitMMC-AP0151H, AP0181H, AP0241H, AP0271H, AP0361H, AP0481H AP0241H to AP0271HIndoor unit high-wall unit 1 Series MMK-AP0071H, AP0091H, AP0121HMMK-AP0151H, AP0181H MMK-AP0241H Indoor unit high-wall unit 2 Series MMK-AP0072H, AP0092H, AP0122HIndoor unit floor-mounted console unit MML-AP0071H, AP0091H, AP0121H, AP0151H, AP0181H, AP0241HModel MML AP0071BH, AP0091BH, AP0121BH Indoor unit concealed chassis unitNo. Name AP0151BH, AP0181HIndoor unit floor-mounted cabinet unit Space required for service For right-hand pipingMMF-AP0151H, AP0181H, AP0241H, AP0271H MMF-AP0361H, AP0481H, AP0561H Refrigerant pipe positions Details of hole for rear pipingRemote controller All dimensions are given in mm TCB-AX21E Wireless remote controller kitWeekly timer RBC-EXW21ELON Gateway Central remote controllerTCB-SC642TLE TCB-IFLNBMS-IFLSV1E TCS-Net relay interfaceTouch-screen controller BMS-TP5120ACE BMS-LSV2E Intelligent serverEnergy monitoring relay interface BMS-IFWH3E BMS-IFDD01E Digital I/O relay interfaceWindows-based central controller BMS-LSV Outdoor module Outdoor module Two units connected Unit combination Outdoor module Three units connectedOutdoor unit combination Master unit Slave unit Outdoor module Four units connected Unit combination Outdoor unit combination Master unitBranch header RBM-HY1043E, HY1083E, HY2043E,HY2083E Model Accessory socket x quantityBranch header/branch joint Shape branching jointRBM-BY53E, BY103E RBM-BY203E, BY303EAccessory socket Page Toshiba Air Conditioning