Toshiba HFC R-410A manual Max. number of connectable indoor units High-pressure switch

Page 66

Outdoor units (combination)

Rating

hp

38

 

 

 

 

40

 

 

 

Cooling only system MMY

 

AP3801T8

 

 

 

 

AP4001T8

 

 

 

Heat pump system MMY

 

AP3801HT8

 

 

 

 

AP4001HT8

 

 

 

Outdoor unit type

 

Inverter

Inverter

Inverter

Inverter

Inverter

Inverter

Inverter

Inverter

Outdoor unit combination

 

 

 

 

 

 

 

 

 

 

cooling only MMY-MAP

 

1001T8

1001T8

1001T8

0801T8

1001T8

1001T8

1001T8

1001T8

Outdoor unit combination

 

 

 

 

 

 

 

 

 

 

heat pump MMY-MAP

 

1001HT8

1001HT8

1001HT8

0801HT8

1001HT8

1001HT8

1001HT8

1001HT8

Cooling capacity

kW

106.5

 

 

 

 

112.0

 

 

 

Heating capacity

kW

119.5

 

 

 

 

126.5

 

 

 

Power supply ± 10%

V-ph-Hz

400-3-50

400-3-50

400-3-50

400-3-50

 

400-3-50

400-3-50

400-3-50

400-3-50

Voltage range

V

380-415

380-415

380-415

380-415

 

380-415

380-415

380-415

380-415

Power input, cooling

kW

30.36

 

 

 

 

32.34

 

 

 

Power factor, cooling

%

96

 

 

 

 

96

 

 

 

Operating current, cooling

A

45.65

 

 

 

 

48.63

 

 

 

EER, cooling

kW/kW

3.51

 

 

 

 

3.46

 

 

 

Starting current

A

1.0

 

 

 

 

1.0

 

 

 

Power input, heating

kW

30.83

 

 

 

 

33.05

 

 

 

Power factor, heating

%

96

 

 

 

 

96

 

 

 

Operating current, heating

A

46.36

 

 

 

 

49.69

 

 

 

COP, heating

kW/kW

3.88

 

 

 

 

3.83

 

 

 

Starting current

A

1.0

 

 

 

 

1.0

 

 

 

Unit appearance

 

Silky shade (Munsell 1Y8.5/0.5)

 

 

 

 

 

 

Dimensions

 

 

 

 

 

 

 

 

 

 

Height

mm

1800

1800

1800

1800

 

1800

1800

1800

1800

Width

mm

990

990

990

990

 

990

990

990

990

Depth

mm

750

750

750

750

 

750

750

750

750

Total weight - cooling only unit

kg

256

256

256

256

 

256

256

256

256

Total weight - heat pump unit

kg

258

258

258

258

 

258

258

258

258

Heat exchanger

 

Finned type

 

 

 

 

 

 

 

 

Sound power level

dB(A)

77.0

 

 

 

 

77.0

 

 

 

Sound pressure level

dB(A) at 1 m

64.0

 

 

 

 

64.0

 

 

 

Fan type

 

Propeller

Propeller

Propeller

Propeller

 

Propeller

Propeller

Propeller

Propeller

Motor power input

kW

0.6

0.6

0.6

0.6

 

0.6

0.6

0.6

0.6

Air flow

l/s

2917

2917

2917

2750

 

2917

2917

2917

2917

 

m3/h

10500

10500

10500

9900

 

10500

10500

10500

10500

Compressor type

 

Hermetic

Hermetic

Hermetic

Hermetic

 

Hermetic

Hermetic

Hermetic

Hermetic

Motor power input

kW

3.1 x 2

3.1 x 2

3.1 x 2

2.3 x 2

 

3.1 x 2

3.1 x 2

3.1 x 2

3.1 x 2

Refrigerant charge R-410A*

 

 

 

 

 

 

 

 

 

 

Cooling

kg

11.0

11.0

11.0

11.0

 

11.0

11.0

11.0

11.0

Heating

kg

12.5

12.5

12.5

12.5

 

12.5

12.5

12.5

12.5

Pipework**

 

 

 

 

 

 

 

 

 

 

Suction line type - diameter

in

Brazed - 7/8

Brazed - 7/8

Brazed - 7/8

Brazed - 7/8

 

Brazed - 7/8 Brazed - 7/8 Brazed - 7/8

Brazed - 7/8

Liquid line type - diameter

in

Flare - 1/2

Flare - 1/2

Flare - 1/2

Flare - 1/2

 

Flare - 1/2

Flare - 1/2

Flare - 1/2

Flare - 1/2

Balance pipe type - diameter

in

Flare - 3/8

Flare - 3/8

Flare - 3/8

Flare - 3/8

 

Flare - 3/8

Flare - 3/8

Flare - 3/8

Flare - 3/8

Maximum equivalent length separation

m

175

175

175

175

 

175

175

175

175

Maximum actual piping length

m

150 (if equivalent bend length is longer, equivalent length is standard)

 

 

Maximum total piping length

m

300

300

300

300

 

300

300

300

300

 

Maximum lift - indoor unit above/below***

m

40/50

40/50

40/50

40/50

 

40/50

40/50

40/50

40/50

Control wiring

 

Shielded wire 1.25 mm2 x 2 cores up to 2000 m

 

 

 

 

Central remote controller

 

Shielded wire 1.25 mm2 x 2 pieces up to 1000 m, 2.0 mm2 x 2 pieces up to 2000 m

 

Max. number of connectable indoor units

48

 

 

 

 

48

 

 

 

High-pressure switch

MPa

Off: 2.90/On: 3.73

 

 

 

 

 

 

 

Protection devices

 

Discharge temperature sensor, suction temperature sensor, compressor crankcase heater,

 

 

 

high-pressure switch, overcurrent sensor, high-pressure sensor, low-pressure sensor,

 

 

 

overcurrent relay

 

 

 

 

 

 

 

Operating range, cooling†

°C

-5 to 43 db

-5 to 43 db

-5 to 43 db

5 to 43 db

 

-5 to 43 db

-5 to 43 db

5 to 43 db

-5 to 43 db

Operating range, heating†

°C

-20 to 16 wb

-20 to 16 wb

-20 to 16 wb

-20 to 16 wb

 

-20 to 16 wb -20 to 16 wb -20 to 16 wb

-20 to 16 wb

Rated conditions: Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db

Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb

The standard piping equals 5 m main pipe length plus 2.5 m branch pipe length.

*The amount does not cover extra piping lengths. Refrigerant must be added on-site in accordance with the actual piping length.

** The maximum total piping length is the sum of one-way piping lengths on the liquid side or gas side.

*** If the indoor unit is above, maximum lift is reduced to 30 m, if the height difference between indoor units exceeds 3 m.

† Please refer to page 24.

66

Image 66
Contents Super Modular Multi Page Super Modular Multi System Contents Outline of Toshiba Super Modular Multi System S-MMS Outdoor unit Indoor unit  Largest system capacity  Self-diagnostic system Compact  Energy saving designTechnical specifications combination of outdoor units Summary of system equipmentTechnical specifications outdoor units Branching joints and headersCombined capacity range Outdoor unit model line-up cooling only unitsProduct designation Rated conditionsOutdoor unit model line-up heat pump units MMY- M AP 000 0 H TTechnical specifications indoor units Wireless remote controller kit Connected to indoor unit Remote controllerSimplified remote controller Connected to indoor unit TCB-AX21U W-EWeekly timer RBC-EXW21E Connected to central remote Controller, wired remote controllerMaster Basic system configuration System legend example 8 hp system8HP Hp system 10HP10HP 10HP Hp system 10HP 10HP 10HP Outdoor unit Indoor unit Remote controller Indoor unit and outdoor unit combination Equipment selection procedureSelection flow chart Capacity codeCapacity correction value Indoor air wet bulb temperature C  Correction of outdoor unit diversity Capacity correction value Indoor air dry bulb temperature C  Correction of outdoor unit diversity Capacity calculation for each indoor unit Operating temperature rangeHeating mode Rated conditionsExample of equipment selection Selection criteria for each floorOutside view Indoor unit Outdoor unit Model Capacity kW Cooling Heating Procedure and result of equipment selectionAir conditioning load Equipment selection Floor Room No Cooling HeatingExample Equipment selection based on system load profile Load in each roomSchematic diagram MMY-AP2801T8 MMY-AP2801HT8Refrigerant piping design Check of concentration limitFree branching system Line branching system Header branching systemAllowable length/height difference of refrigerant piping System restrictionsAllowable value Piping section Selection of refrigerant piping  Pipe size of outdoor unit Table Model nameGas side Liquid side Charge Cooling only Charging requirement with additional refrigerantCalculating the amount of additional refrigerant required Liquid side pipe diameterElectrical wiring design Wiring designOutdoor unit power supply GeneralControl wiring design Type Control wiring diagramControl wiring between outdoor units L5 Wiring LengthDesign FLA MCA MocpVoltage Range Ph-Hz Min Max Compressor Fan motor Power supplySingle outdoor unit Heat pump Cooling only Nominal Combination of outdoor units Heat pump Cooling only NominalControls Control via indoor remote controllerControl via the central remote controller Range of controls to meet various system needsTwo remote controllers Applications for indoor remote controllerBasic function System diagram Model Individual control Control by weekly timerIndoor remote controller Application controls for central remote controllerBasic function System diagram Model Function of central remote controllerAvailable TCB-PCNT30TLEBACnet Application control for networkTCB-1FLN BMS-LSVBMS-TP5120ACE Remote controller AccessoriesIndoor unit accessories Indoor unit type Accessory name Model Applicable modelTechnical specifications Indoor units Way ceiling cassettesRBC-UW136PG RBC-UW266PG Room thermostat RBC-UY135PG RBC-US165PG RBC-US265PGIndoor units Standard ducted units Fan motor power inputStatic pressure factory setting Static pressure max Sound pressure level high/medium/low** dBASound power level high Unit weightStatic pressure factory setting Indoor units High-pressure ducted unitsLower air inlet Sound power level high/medium/low Rear air inlet Sound power level high/medium/lowIndoor units Slim duct units Indoor units Ceiling-suspended units Indoor units High-wall units 1 Series Indoor units High-wall units 2 Series Indoor units Floor-mounted console units Indoor units Concealed chassis units Static pressureIndoor units Floor-mounted cabinet units Outdoor units Outdoor units combination DBA 74.5 DBA 75.0 24.26 Power factor, cooling Operating current, cooling 30.51 258 256 DBA 76.5 77.0 Max. number of connectable indoor units High-pressure switch Power supply ± 10% Ph-Hz 400-3-50 130.0 135.0 MMD-AP0071BH, AP0091BH Fan characteristicsCase of square duct flange of discharge section MMD-AP0121BHMMD-AP0301BH MMD-AP0241BH, AP0271BHMMD-AP0361BH MMD-AP0481BH, AP0561BHMMD-AP0241H, AP0271H High-pressure ducted unitMMD-AP0181H MMD-AP0361HMMD-AP0721H MMD-AP0961HSlim duct unit MMD-AP0071SPH, AP0091SPH MMD-AP0121SPHMMD-AP0151SPH MMD-AP0181SPH Slim duct unit with filter attached MMD-AP0151SPHIndoor unit 4-way ceiling cassette Dimensional drawingsAll dimensions are given in mm MMU-AP0091H to P0561HAll dimensions are given in mm View Indoor unit 2-way ceiling cassetteMMU-AP0071WH, AP0091WH, AP0121WH View Space required for installation and servicing MMU-AP0151WH, AP0181WH, AP0241WH, AP0271WH, AP0301WHModel MMU-AP0151WH to AP0181WH MMU-AP0241WH to AP0301WH MMU-AP0481WH Indoor unit 1-way ceiling cassette MMU-AP0071YH, AP0091YH, AP0121YHMMU-AP0151SH, AP0181SH, AP0241SH View Model MMU AP0151SH, AP0181SHAP0241SH Indoor unit standard ducted unit View Space required for installation and servicing *1 Indoor unit high-pressure ducted unitMMD-AP0271H, AP0961H Bottom view complete with filter Indoor unit slim duct unitMMD-AP0071SPH, AP0091SPH, AP0121SPH, AP0151SPH, AP0181SPH Bottom view excluding filterModel MMC AP0151H, AP0181H Indoor unit ceiling-suspended unitMMC-AP0151H, AP0181H, AP0241H, AP0271H, AP0361H, AP0481H AP0241H to AP0271HIndoor unit high-wall unit 1 Series MMK-AP0071H, AP0091H, AP0121HMMK-AP0151H, AP0181H MMK-AP0241H Indoor unit high-wall unit 2 Series MMK-AP0072H, AP0092H, AP0122HIndoor unit floor-mounted console unit MML-AP0071H, AP0091H, AP0121H, AP0151H, AP0181H, AP0241HModel MML AP0071BH, AP0091BH, AP0121BH Indoor unit concealed chassis unitNo. Name AP0151BH, AP0181HSpace required for service For right-hand piping Indoor unit floor-mounted cabinet unitMMF-AP0151H, AP0181H, AP0241H, AP0271H MMF-AP0361H, AP0481H, AP0561H Refrigerant pipe positions Details of hole for rear pipingRemote controller All dimensions are given in mm TCB-AX21E Wireless remote controller kitWeekly timer RBC-EXW21ELON Gateway Central remote controllerTCB-SC642TLE TCB-IFLNTCS-Net relay interface BMS-IFLSV1ETouch-screen controller BMS-TP5120ACE Intelligent server BMS-LSV2EEnergy monitoring relay interface BMS-IFWH3E Digital I/O relay interface BMS-IFDD01EWindows-based central controller BMS-LSV Outdoor module Outdoor module Two units connected Outdoor module Three units connected Unit combinationOutdoor unit combination Master unit Slave unit Outdoor module Four units connected Unit combination Outdoor unit combination Master unitBranch header RBM-HY1043E, HY1083E, HY2043E,HY2083E Model Accessory socket x quantityBranch header/branch joint Shape branching jointRBM-BY53E, BY103E RBM-BY203E, BY303EAccessory socket Page Toshiba Air Conditioning