Design Parameters
FORM
ENGLISH
YCAL | LEAVING WATER | COOLER FLOW (GPM) | AIR ON CONDENSER (°F) | ||||
TEMPERATURE (°F) | |||||||
|
|
|
|
| |||
| MIN | MAX | MIN | MAX | MIN | MAX | |
0041 | 40 | 55 | 40 | 200 | 0 | 125 | |
0045 | 40 | 55 | 40 | 200 | 0 | 125 | |
0051 | 40 | 55 | 40 | 200 | 0 | 125 | |
0055 | 40 | 55 | 60 | 300 | 0 | 125 | |
0061 | 40 | 55 | 60 | 300 | 0 | 125 | |
0065 | 40 | 55 | 60 | 300 | 0 | 125 | |
|
|
|
|
|
|
| |
|
|
| SI UNITS |
|
|
| |
YCAL | LEAVING WATER | COOLER FLOW (L/S) | AIR ON CONDENSER (°C) | ||||
TEMPERATURE (°DC) | |||||||
|
|
|
|
| |||
| MIN | MAX | MIN | MAX | MIN | MAX | |
0041 | 4.4 | 12.8 | 2.5 | 12.6 | 51.7 | ||
0045 | 4.4 | 12.8 | 2.5 | 12.6 | 51.7 | ||
0051 | 4.4 | 12.8 | 2.5 | 12.6 | 51.7 | ||
0055 | 4.4 | 12.8 | 3.8 | 18.9 | 51.7 | ||
0061 | 4.4 | 12.8 | 3.8 | 18.9 | 51.7 | ||
0065 | 4.4 | 12.8 | 3.8 | 18.9 | 51.7 |
NOTES:
1.For leaving brine temperature below 40°F (4.4°C), contact your nearest YORK Office for application requirements.
2.For leaving water temperature higher than 55°F (12.8°C), contact the nearest YORK Office for application guidelines.
3.The evaporator is protected against freezing to
4.For operation at temperatures below 25°F
5.For operation at temperatures above 115°F (46.1°C), the optional High Ambient Kit will need to be installed on the system.
YORK INTERNATIONAL | 13 |