chilling below 30°F
CHICAGO CODE RELIEF VALVES – Unit will be pro- vided with relief valves to meet Chicago code require- ments.
SERVICE ISOLATION VALVE – Service suction and discharge (ball type) isolation valves are added to unit per system. This option also includes a system high pressure relief valve in compliance with ASHRAE 15.
HOT GAS
DX COOLER 300 PSIG (21 bar) DWP WATERSIDE
–The waterside will be of 300 PSIG (21 bar) instead of the standard 150 PSIG DWP. 300 PSIG R.F. flanges are included on the DX cooler nozzles.
FLANGES (VICTAULIC TYPE) – Consists of two (2) Flange adapters for grooved end pipe (standard 150 psi [10.5 bar] cooler).
FLOW SWITCH – The flow switch or its equivalent must be furnished with each unit.
150 PSIG (10.5 bar) DWP – For standard units. Johnson Controls model
300 psig (21 bar) DWP – For units with optional 300 PSIG (21 bar) DX cooler. McDonnell & Miller model FS74W
DIFFERENTIAL PRESSURE SWITCH – Alternative to an above mentioned flow switch. Pretempco model
REMOTE DX COOLER – A split system arrangement with the cooler, leaving & return water sensors, liquid line solenoid valves, filter driers, sightglasses & TXVs shipped loose for field connection to the
CONDENSER AND CABINET OPTIONS:
Condenser coil protection against corrosive environ- ments is available by choosing any of the following op- tions. For additional application recommendations, refer to FORM
COPPER FIN CONDENSER COILS – The unit's coils are constructed with copper fins. (This is not recom- mended for units in areas where they may be exposed to acid rain.)
ENCLOSURE PANELS (UNIT) – Tamperproof En- closure Panels prevent unauthorized access to units. Enclosure Panels can provide an aesthetically pleas- ing alternative to expensive fencing. Additionally, for proper head pressure control, YORK recommends the use of :
LOUVERED PANELS (Full Unit) – Louvered panels surround the front, back, and sides of the unit. They prevent unauthorized access and visually screen unit components. Unrestricted air flow is permitted through generously sized louvered openings. This option is ap- plicable for any outdoor design ambient temperature up to 115°F (46°C).
SOUND ATTENUATION – One or both of the follow- ing sound attenuation options are recommended for