FORM
Typical Piping for
Coolers
Notes:
1.Placement on a level surface free of obstructions (including snow, for winter operation) or air recircula- tion ensures rated performance, reliable operation and ease of maintenance.
2.Piping and wiring shown is for reference use only and is not in accordance with any national or local standards.
3.All wiring and piping must comply with applicable local and national codes.
4.All wiring and piping must follow standard piping techniques as discussed in the ASHRAE hand- book.
5.A strainer with a mesh size between .5 and 1.5 mm is recommended upstream of the heat exchanger to prevent clogging.
Vibration
Eliminators
Strainer Vent
INLET
Isolation
Valves
Flow
Switch
Pressure | Shut Off |
Gauge | Valves |
|
OUTLET
Drain
Vibration
Eliminators
YORK INTERNATIONAL | 73 |