York YCAL0065, YCAL0041 manual Millennium Control Center, Unit ON/OFF switch

Page 5

FORM 150.64-EG1

MILLENNIUM CONTROL CENTER

All controls are contained in a NEMA 3R/12 (and equivalent to IP55*) cabinet with hinged outer door and includes:

Liquid Crystal Display with Light Emitting Diode back- lighting for outdoor viewing:

Two display lines

Twenty characters per line

Color coded 12-button non-tactile keypad with sections for:

DISPLAY/PRINT of typical information: Chilled liquid temperatures Ambient temperature

System pressures (each circuit)

Operating hours and starts (each compressor) Print calls up to the liquid crystal display: Operating data for the systems

History of fault shutdown data for up to the last six fault shutdown conditions An RS-232 port, in conjunction with this press-to-print button, is provided to permit the capability of hard copy print-outs via a separate printer (by others).

ENTRY section to:

ENTER setpoints or modify system values

SETPOINTS updating can be performed to: Chilled liquid temperature setpoint and range Remote reset temperature range

Set daily schedule/holiday for start/stop Manual override for servicing

Low and high ambient cutouts Number of compressors Low liquid temperature cutout Low suction pressure cutout High discharge pressure cutout

Anti-recycle timer (compressor start cycle time)

Anti-coincident timer (delay compressor starts)

UNIT section to: Set time

Set unit options

UNIT ON/OFF switch

The microprocessor control center is capable of dis- playing the following:

Return and leaving liquid temperature

Low leaving liquid temperature cutout setting

Low ambient temperature cutout setting

Outdoor air temperature

English or Metric data

Suction pressure cutout setting

Each system suction pressure

Discharge pressure (optional)

Liquid Temperature Reset via a YORK ISN DDC or Building Automation System (by others) via:

-a pulse width modulated (PWM) input as stan- dard

-a 4-20 milliamp or 0 -10 VDC input, or contact closure with the optional B.A.S. interface option

Anti-recycle timer status for each system

Anti-coincident system start timer condition

Compressor run status

No cooling load condition

Day, date and time

Daily start/stop times

Holiday status

Automatic or manual system lead/lag control

Lead system definition

Compressor starts & operating hours (each compressor)

Status of hot gas valves, evaporator heater and fan operation

Run permissive status

Number of compressors running

Liquid solenoid valve status

Load & unload timer status

Water pump status

*Intensity of Protection European Standard

YORK INTERNATIONAL

5

Image 5
Contents Form 150.64-EG1 AIR-COOLED Scroll ChillersTable of Contents Introduction General SpecificationCompressors CoolerMillennium Control Center Unit ON/OFF switchPower Panel Power Options Options and AccessoriesSINGLE-POINT NON-FUSED Disconnect Switch Control OptionsDX Cooler 300 Psig 21 bar DWP Waterside Condenser and Cabinet OptionsCompressor Acoustic Sound Blanket Each This page intentionally left blank Guide to Selection Selection DataSelection Rules Method of SelectionDetermine E.G. GPM Calculate GPMExample Brine Chilling SI Units Ycal Design ParametersEnglish Ycal 100 Water Pressure Drop1000 Model YCAL0041EC Ratings R-22 60Hz English UnitsModel YCAL0045EC Model YCAL0051EC31.3 42.2 30.5 44.7 29.6 47.4 28.7 50.2 27.8 53.2 105 110.0 115.0 120.0 125.032.4 42.5 31.5 45.0 30.6 47.6 29.7 50.4 28.7 53.4 33.4 42.7 32.5 45.2 31.6 47.9 30.7 50.7 29.7 53.7Model YCAL0065EC Model YCAL0055ECModel YCAL0061EC 43.8 58.5 42.6 61.8 41.3 65.2 30.0 48.3 29.0 50.9 42.3 58.2 41.2 61.4 39.9 64.8 29.0 48.0 28.0 50.645.3 58.8 44.0 62.1 42.7 65.6 31.1 48.5 30.1 51.2 46.0 59.0 44.7 62.3 43.4 65.8 31.6 48.6 30.6 51.325.0 30.0 35.0 40.0 45.0 50.0 Ratings R-22 60Hz SI Units172.2 43.1 166.0 47.5 159.3 52.3 152.2 57.7 Ratings R-22 50Hz English Units 42.0 34.5 26.6 36.7 25.8 39.2 25.0 41.8 24.1 44.6 40.0 34.3 25.7 36.5 25.0 39.0 24.1 41.6 23.2 44.444.0 34.7 27.5 36.9 26.7 39.4 25.9 42.0 24.9 44.8 45.0 34.8 28.0 37.0 27.2 39.5 26.3 42.1 25.4 44.935.7 12.2 33.8 13.140.0 10.6 34.0 13.542.0 47.8 36.2 50.6 35.1 53.6 34.0 56.7 32.8 60.0 40.0 47.5 35.0 50.3 33.9 53.3 32.8 56.4 31.7 59.744.0 48.0 37.4 50.9 36.3 53.8 35.2 57.0 34.0 60.3 45.0 48.2 38.1 51.0 36.9 54.0 35.8 57.1 34.6 60.5Ratings R-22 50Hz SI Units 146.1 34.7 140.9 38.4 135.3 42.5 129.3 47.1 Full Part Load Ratings R-22 English UnitsUnit Load Tons EER DisplLoad COP Displ Part Load Ratings R-22 SIYCAL055 Full Load Scop DisplPhysical Data Side Water Per Power Chiller87.0 47400125 250 500 1000 2000 4000 8000 DBA Sound Data50Hz Line Frequency Low Noise Fan R-22 Dimensions YCAL0041 English 90 9/16 DIA Mounting HOLEStyp45 5/16 13/160045 63.2 43.7 Dimensions YCAL0045 English0045 59.2 43.5 Copper 13/16 25 3/8 B 13 5/8 20 1/160051 64.3 42.9 Dimensions YCAL0051 English0051 59.2 42.6 Copper Front View 62 5/8 TYP 15/16 Dimensions YCAL0055EC English34 11/16 0055 57.9 43.0 Copper15 1/16 144 13/16 18 7/1628 9/16 61 7/8 Dimensions YCAL0061 English43 1/8 0061 56.6 45.2 Copper25 3/8 28 9/16 43 5/1616 11/16 62 5/8 Dimensions YCAL0065 English0065 59.7 44.9 Copper 0065 65.2 44.9Cooler Coil END Dimensions YCAL0041 SI 1150 2301249 5540045 1605.9 1109.7 Dimensions YCAL0045 SI0045 1503.5 1105.5 Copper 509 0051 1633.0 1090.8 Dimensions YCAL0051 SI0051 1504.6 1082.4 Copper Cooler END Dimensions -YCAL0055 SI 249 468 1151131 965 645 726Dimensions YCAL0061 SI 249 424 11000065 1655.5 1141.1 Dimensions YCAL0065 SI0065 1517.6 1140.3 Copper TOP View CIP-X Isolator SelectionsONE Inch Deflection Spring Isolator CROSS-REFERENCE For Units with ALL Point Loads Less Thatn 1404 LBS 637 KGNeoprene Isolator CROSS-REFERENCE ND-XUp to 751 lbs Up to 341 kg 751 to 1651 lbs 341 to 749 kgSlrs Isolator Details contd12 1/4 215.9 34.9 355.6 311.2Intentionally Left Blank Electrical Data Voltage Range Electrical Data 60Hz RLA Electrical Data 50Hz LUG Wire RangeCOMPR. #1 COMPR. #2 Fans Standard Power Supply Wiring Ycal 0014 Power WiringYork International York International Control Wiring Unit Location Application DataFoundation Chilled Liquid PipingInlet Part 1 General Guide SpecificationsQuality Assurance Delivery and HandlingControls Refrigerant Circuit ComponentsHeat Exchangers Accessories and Options Power Connection and DISTRI- ButionYork International Part 3 Execution Installation York International ALL Right