York YCAL0065, YCAL0041 manual Options and Accessories, Power Options, Control Options

Page 7

Options and Accessories

FORM 150.64-EG1

POWER OPTIONS:

COMPRESSOR POWER CONNECTIONS – Single- point (YCAL0041-0065) terminal block connection(s) are provided as standard. The following power connections are available as options. (See electrical data for specific voltage and options availability.) (Factory-Mounted.)

SINGLE-POINT SUPPLY TERMINAL BLOCK – (stan- dard on YCAL0041 - 0065 models). Includes enclosure, terminal-block and interconnecting wiring to the com- pressors. Separate external protection must be supplied, by others, in the incoming compressor-power wiring. (Do not include this option if either the SinglePoint NonFused Disconnect Switch or Single-Point Circuit Breaker op- tions have been included.)

SINGLE-POINT NON-FUSED DISCONNECT SWITCH

Unit-mounted disconnect switch with external, lockable handle (in compliance with Article 440-14 of N.E.C.), can be supplied to isolate the unit power voltage for servicing. Separate external fusing must be supplied, by others in the power wiring, which must comply with the National Electrical Code and/or local codes.

SINGLE-POINT CIRCUIT BREAKER – A unit mounted circuit breaker with external, lockable handle (in com- pliance with N.E.C. Article 440-14), can be supplied to isolate the power voltage for servicing. (This option includes the Single-Point Power connection.)

CONTROL TRANSFORMER – Converts unit power voltage to 115-1-60 (0.5 or 1.0 KVA capacity). Fac- tory mounting includes primary and secondary wiring between the transformer and the control panel. (Fac- tory-Mounted.)

POWER FACTOR CORRECTION CAPACITORS – Will correct unit compressor power factors to a 0.90-0.95.(Factory-Mounted.)

CONTROL OPTIONS:

AMBIENT KIT (LOW) – Units will operate to 25°F (-4°C). This accessory includes all necessary components to permit chiller operation to 0°F (-18°C). (This option in- cludes the Discharge Pressure Transducer / Readout Capability option.) For proper head pressure control in applications below 25°F (-4°C), where wind gusts may exceed five mph, it is recommended that Optional Con- denser Louvered Enclosure Panels also be included. (Factory-Mounted.)

AMBIENT KIT (HIGH) – Required if units are to operate when the ambient temperature is above 115°F (46°C). Includes discharge pressure transducers. (This option

includes the Discharge Pressure Transducer / Readout- Capability option.) (Field-Mounted.)

BUILDING AUTOMATION SYSTEM INTERFACE – The factory addition of a Printed Circuit Board to accept a 4-20 milliamp, 0-10VDC or contact closure input to reset the leaving chiller liquid temperature from a Building Au- tomation System. (Only one of following options can be offered on a unit at a time: BAS, Remote Control Panel or Multi-unit Sequence Control.) (Factory-Mounted.) (The standard unit capabilities include remote startstop, remote water temperature reset via a PWM input signal or up to two steps of demand (load) limiting depending on model.) (The standard control panel can be directly connected to a YORK Building Automated System via the standard onboard RS485 communication port.)

LANGUAGE LCD AND KEYPAD DISPLAY – Spanish, French, and German unit LCD controls and keypad display available. Standard language is English.

DISCHARGE PRESSURE TRANSDUCERS AND READOUT CAPABILITY – The addition of pressure transducers allows models to sense and display dis- charge pressure. This is recommended for brine chilling applications. (This option is included with either the low or high ambient kits.) (Factory-Mounted.)

Suction Pressure Transducers: Permits unit to sense and display suction pressure. This capability is standard on YCAL0041-0065 models.

MOTOR CURRENT MODULE – Capable of monitoring compressor motor current. Provides extra protection against compressor reverse rotation, phase-loss and phase imbalance. Option consists of one module per electrical system. (Factory-Mounted.)

OPTIVIEW REMOTE CONTROL PANEL - Graphical interface panel to remotely control and monitor up to 8 different units. (Refer to form 201.18-SG4 for detailed information)

MULTI-UNIT SEQUENCING – A separate Sequencing Control Center is provided to handle sequencing control of up to eight chillers in parallel based on mixed liquid temperature (interconnecting wiring by others). (Only one of following options can be offered on a unit at a time: BAS, Remote Control Panel or Multi-unit Sequence Control.) (Factory-Mounted.)

COMPRESSOR, PIPING, EVAPORATOR OPTIONS:

LOW TEMPERATURE BRINE – Required for brine

YORK INTERNATIONAL

7

Image 7
Contents Form 150.64-EG1 AIR-COOLED Scroll ChillersTable of Contents Introduction Cooler SpecificationGeneral CompressorsMillennium Control Center Unit ON/OFF switchPower Panel Control Options Options and AccessoriesPower Options SINGLE-POINT NON-FUSED Disconnect SwitchDX Cooler 300 Psig 21 bar DWP Waterside Condenser and Cabinet OptionsCompressor Acoustic Sound Blanket Each This page intentionally left blank Method of Selection Selection DataGuide to Selection Selection RulesExample Brine Chilling Calculate GPMDetermine E.G. GPM English Ycal Design ParametersSI Units Ycal 100 Water Pressure Drop1000 Model YCAL0051EC Ratings R-22 60Hz English UnitsModel YCAL0041EC Model YCAL0045EC33.4 42.7 32.5 45.2 31.6 47.9 30.7 50.7 29.7 53.7 105 110.0 115.0 120.0 125.031.3 42.2 30.5 44.7 29.6 47.4 28.7 50.2 27.8 53.2 32.4 42.5 31.5 45.0 30.6 47.6 29.7 50.4 28.7 53.4Model YCAL0061EC Model YCAL0055ECModel YCAL0065EC 46.0 59.0 44.7 62.3 43.4 65.8 31.6 48.6 30.6 51.3 42.3 58.2 41.2 61.4 39.9 64.8 29.0 48.0 28.0 50.643.8 58.5 42.6 61.8 41.3 65.2 30.0 48.3 29.0 50.9 45.3 58.8 44.0 62.1 42.7 65.6 31.1 48.5 30.1 51.225.0 30.0 35.0 40.0 45.0 50.0 Ratings R-22 60Hz SI Units172.2 43.1 166.0 47.5 159.3 52.3 152.2 57.7 Ratings R-22 50Hz English Units 45.0 34.8 28.0 37.0 27.2 39.5 26.3 42.1 25.4 44.9 40.0 34.3 25.7 36.5 25.0 39.0 24.1 41.6 23.2 44.442.0 34.5 26.6 36.7 25.8 39.2 25.0 41.8 24.1 44.6 44.0 34.7 27.5 36.9 26.7 39.4 25.9 42.0 24.9 44.834.0 13.5 33.8 13.135.7 12.2 40.0 10.645.0 48.2 38.1 51.0 36.9 54.0 35.8 57.1 34.6 60.5 40.0 47.5 35.0 50.3 33.9 53.3 32.8 56.4 31.7 59.742.0 47.8 36.2 50.6 35.1 53.6 34.0 56.7 32.8 60.0 44.0 48.0 37.4 50.9 36.3 53.8 35.2 57.0 34.0 60.3Ratings R-22 50Hz SI Units 146.1 34.7 140.9 38.4 135.3 42.5 129.3 47.1 Load Tons EER Displ Part Load Ratings R-22 English UnitsFull UnitLoad Scop Displ Part Load Ratings R-22 SILoad COP Displ YCAL055 FullPhysical Data 47400 Per Power ChillerSide Water 87.0125 250 500 1000 2000 4000 8000 DBA Sound Data50Hz Line Frequency Low Noise Fan R-22 Dimensions YCAL0041 English 13/16 DIA Mounting HOLEStyp90 9/16 45 5/160045 59.2 43.5 Copper Dimensions YCAL0045 English0045 63.2 43.7 13/16 25 3/8 B 13 5/8 20 1/160051 59.2 42.6 Copper Dimensions YCAL0051 English0051 64.3 42.9 Front View 0055 57.9 43.0 Copper Dimensions YCAL0055EC English62 5/8 TYP 15/16 34 11/1628 9/16 18 7/1615 1/16 144 13/16 0061 56.6 45.2 Copper Dimensions YCAL0061 English61 7/8 43 1/816 11/16 43 5/1625 3/8 28 9/16 0065 65.2 44.9 Dimensions YCAL0065 English62 5/8 0065 59.7 44.9 CopperCooler Coil END Dimensions YCAL0041 SI 554 23011150 2490045 1503.5 1105.5 Copper Dimensions YCAL0045 SI0045 1605.9 1109.7 509 0051 1504.6 1082.4 Copper Dimensions YCAL0051 SI0051 1633.0 1090.8 Cooler END Dimensions -YCAL0055 SI 645 726 1151249 468 131 965Dimensions YCAL0061 SI 249 424 11000065 1517.6 1140.3 Copper Dimensions YCAL0065 SI0065 1655.5 1141.1 TOP View For Units with ALL Point Loads Less Thatn 1404 LBS 637 KG Isolator SelectionsCIP-X ONE Inch Deflection Spring Isolator CROSS-REFERENCE751 to 1651 lbs 341 to 749 kg ND-XNeoprene Isolator CROSS-REFERENCE Up to 751 lbs Up to 341 kg215.9 34.9 355.6 311.2 Isolator Details contdSlrs 12 1/4Intentionally Left Blank Electrical Data Voltage Range Electrical Data 60Hz RLA Electrical Data 50Hz LUG Wire RangeCOMPR. #1 COMPR. #2 Fans Standard Power Supply Wiring Ycal 0014 Power WiringYork International York International Control Wiring Chilled Liquid Piping Application DataUnit Location FoundationInlet Delivery and Handling Guide SpecificationsPart 1 General Quality AssuranceHeat Exchangers Refrigerant Circuit ComponentsControls Accessories and Options Power Connection and DISTRI- ButionYork International Part 3 Execution Installation York International ALL Right