York YCAL0065, YCAL0041 Selection Data, Guide to Selection, Selection Rules, Method of Selection

Page 11

Selection Data

FORM 150.64-EG1

GUIDE TO SELECTION

Capacity ratings for YORK YCAL Packaged Air-Cooled Liquid Chillers, shown on pages 16 through 39 cover the majority of design applications for these units. For unusual applications or uses beyond the scope of this catalog, please consult your nearest YORK Office or representative.

SELECTION RULES

1.Ratings – Ratings may be interpolated, but must not be extrapolated. The Ratings given on pages 16 through 39 and the DESIGN PARAMETERS given on page 11 indicate the limits of application for these chillers.

2.Cooler Water – Ratings are based upon 2.4 GPM per ton which is equal to a 10°F chilled water range and a 0.0001 fouling factor for the cooler at sea level. Tables on pages 16 through 39 give capacity, com- pressor kW required, cooler GPM and unit EER.

3.Condenser – Ratings are given in terms of air on condenser in degrees Fahrenheit.

4.Copper Fin Condenser Ratings – Since the ther- mal conductivity of copper is slightly higher than aluminum, apply the following corrections to the standard ratings. Tons x 0.97 and compressor kW x 0.99.

5.Performance Data Correction Factors – Ratings are based on 0.0001 cooler fouling factor, 10°F chilled water range and at sea level. For operation at different conditions, apply the appropriate correction factor from the following table.

FOULING FACTOR

 

TEMP

0.0001

0.00025

ALTITUDE

TONS

COMPR

TONS

COMPR

SPLIT

 

kW

kW

 

 

 

 

 

8

0.990

0.998

0.979

0.996

SEA LEVEL

10

1.000

1.000

0.991

0.998

12

1.012

1.003

1.002

1.001

 

 

14

1.021

1.005

1.012

1.003

 

8

0.987

1.005

0.978

1.003

2000 FT.

10

0.997

1.008

0.988

1.006

12

1.009

1.010

1.000

1.008

 

 

14

1.018

1.012

1.009

1.010

 

8

0.983

1.014

0.975

1.012

4000 FT.

10

0.994

1.016

0.985

1.014

12

1.005

1.019

1.111

1.017

 

 

14

1.014

1.021

1.006

1.019

 

8

0.980

1.023

0.971

1.021

6000 FT.

10

0.990

1.025

0.982

1.023

12

1.002

1.028

0.993

1.026

 

 

14

1.011

1.030

1.002

1.028

6.Ethylene Glycol Correction Factors – The fol- lowing factors are to be applied to the standard ratings for units cooling ethylene glycol.

ETHYLENE GLYCOL

%

TONS

COMPR

GPM

PRESS

FREEZE

WEIGHT

KW

°F/TON

DROP

PT

 

10

0.996

0.999

24.3

1.049

26.2

20

0.991

0.998

25.1

1.124

17.9

30

0.984

0.997

25.9

1.258

6.7

40

0.976

0.995

26.9

1.430

-8.1

50

0.968

0.994

28.0

1.650

-28.9

7.Propylene Glycol Correction Factors – The fol- lowing factors are to be applied to the standard ratings for units cooling propylene glycol.

PROPYLENE GLYCOL

%

TONS

COMPR

GPM

PRESS

FREEZE

WEIGHT

KW

°F/TON

DROP

PT

 

10

0.995

0.999

24.0

1.014

26

20

0.984

0.997

24.3

1.104

19

30

0.973

0.994

24.9

1.234

9

40

0.960

0.992

25.6

1.399

-6

50

0.943

0.989

26.6

1.599

-28

METHOD OF SELECTION

To select of YORK Packaged Air-Cooled Liquid Chiller, the following data must be known:

1.Design Capacity in tons refrigeration (TR).

2.Entering and Leaving Liquid Temperatures.

3.Outside ambient air temperature in degrees F.

4.GPM of chilled liquid.

Determine capacity requirements from the following formula:

GPM =

TR x 24

RANGE (°F)

EXAMPLE – WATER CHILLING

1.Given: Provide a capacity of 50 tons at 42 F leav- ing water at 10 F range. 0.0001FF, 85 F air on the condenser, at sea level and 60 Hz.

2.Find: Unit Size, Compressor KW Output

3.From the ratings on page 18.

Select: YCAL0061 (English Units)

YORK INTERNATIONAL

11

Image 11
Contents Form 150.64-EG1 AIR-COOLED Scroll ChillersTable of Contents Introduction Cooler SpecificationGeneral CompressorsMillennium Control Center Unit ON/OFF switchPower Panel Control Options Options and AccessoriesPower Options SINGLE-POINT NON-FUSED Disconnect SwitchDX Cooler 300 Psig 21 bar DWP Waterside Condenser and Cabinet OptionsCompressor Acoustic Sound Blanket Each This page intentionally left blank Method of Selection Selection DataGuide to Selection Selection RulesDetermine E.G. GPM Calculate GPMExample Brine Chilling SI Units Ycal Design ParametersEnglish Ycal 100 Water Pressure Drop1000 Model YCAL0051EC Ratings R-22 60Hz English UnitsModel YCAL0041EC Model YCAL0045EC33.4 42.7 32.5 45.2 31.6 47.9 30.7 50.7 29.7 53.7 105 110.0 115.0 120.0 125.031.3 42.2 30.5 44.7 29.6 47.4 28.7 50.2 27.8 53.2 32.4 42.5 31.5 45.0 30.6 47.6 29.7 50.4 28.7 53.4Model YCAL0065EC Model YCAL0055ECModel YCAL0061EC 46.0 59.0 44.7 62.3 43.4 65.8 31.6 48.6 30.6 51.3 42.3 58.2 41.2 61.4 39.9 64.8 29.0 48.0 28.0 50.643.8 58.5 42.6 61.8 41.3 65.2 30.0 48.3 29.0 50.9 45.3 58.8 44.0 62.1 42.7 65.6 31.1 48.5 30.1 51.225.0 30.0 35.0 40.0 45.0 50.0 Ratings R-22 60Hz SI Units172.2 43.1 166.0 47.5 159.3 52.3 152.2 57.7 Ratings R-22 50Hz English Units 45.0 34.8 28.0 37.0 27.2 39.5 26.3 42.1 25.4 44.9 40.0 34.3 25.7 36.5 25.0 39.0 24.1 41.6 23.2 44.442.0 34.5 26.6 36.7 25.8 39.2 25.0 41.8 24.1 44.6 44.0 34.7 27.5 36.9 26.7 39.4 25.9 42.0 24.9 44.834.0 13.5 33.8 13.135.7 12.2 40.0 10.645.0 48.2 38.1 51.0 36.9 54.0 35.8 57.1 34.6 60.5 40.0 47.5 35.0 50.3 33.9 53.3 32.8 56.4 31.7 59.742.0 47.8 36.2 50.6 35.1 53.6 34.0 56.7 32.8 60.0 44.0 48.0 37.4 50.9 36.3 53.8 35.2 57.0 34.0 60.3Ratings R-22 50Hz SI Units 146.1 34.7 140.9 38.4 135.3 42.5 129.3 47.1 Load Tons EER Displ Part Load Ratings R-22 English UnitsFull UnitLoad Scop Displ Part Load Ratings R-22 SILoad COP Displ YCAL055 FullPhysical Data 47400 Per Power ChillerSide Water 87.0125 250 500 1000 2000 4000 8000 DBA Sound Data50Hz Line Frequency Low Noise Fan R-22 Dimensions YCAL0041 English 13/16 DIA Mounting HOLEStyp90 9/16 45 5/160045 63.2 43.7 Dimensions YCAL0045 English0045 59.2 43.5 Copper 13/16 25 3/8 B 13 5/8 20 1/160051 64.3 42.9 Dimensions YCAL0051 English0051 59.2 42.6 Copper Front View 0055 57.9 43.0 Copper Dimensions YCAL0055EC English62 5/8 TYP 15/16 34 11/1615 1/16 144 13/16 18 7/1628 9/16 0061 56.6 45.2 Copper Dimensions YCAL0061 English61 7/8 43 1/825 3/8 28 9/16 43 5/1616 11/16 0065 65.2 44.9 Dimensions YCAL0065 English62 5/8 0065 59.7 44.9 CopperCooler Coil END Dimensions YCAL0041 SI 554 23011150 2490045 1605.9 1109.7 Dimensions YCAL0045 SI0045 1503.5 1105.5 Copper 509 0051 1633.0 1090.8 Dimensions YCAL0051 SI0051 1504.6 1082.4 Copper Cooler END Dimensions -YCAL0055 SI 645 726 1151249 468 131 965Dimensions YCAL0061 SI 249 424 11000065 1655.5 1141.1 Dimensions YCAL0065 SI0065 1517.6 1140.3 Copper TOP View For Units with ALL Point Loads Less Thatn 1404 LBS 637 KG Isolator SelectionsCIP-X ONE Inch Deflection Spring Isolator CROSS-REFERENCE751 to 1651 lbs 341 to 749 kg ND-XNeoprene Isolator CROSS-REFERENCE Up to 751 lbs Up to 341 kg215.9 34.9 355.6 311.2 Isolator Details contdSlrs 12 1/4Intentionally Left Blank Electrical Data Voltage Range Electrical Data 60Hz RLA Electrical Data 50Hz LUG Wire RangeCOMPR. #1 COMPR. #2 Fans Standard Power Supply Wiring Ycal 0014 Power WiringYork International York International Control Wiring Chilled Liquid Piping Application DataUnit Location FoundationInlet Delivery and Handling Guide SpecificationsPart 1 General Quality AssuranceControls Refrigerant Circuit ComponentsHeat Exchangers Accessories and Options Power Connection and DISTRI- ButionYork International Part 3 Execution Installation York International ALL Right