Selection Data
FORM
GUIDE TO SELECTION
Capacity ratings for YORK YCAL Packaged
SELECTION RULES
1.Ratings – Ratings may be interpolated, but must not be extrapolated. The Ratings given on pages 16 through 39 and the DESIGN PARAMETERS given on page 11 indicate the limits of application for these chillers.
2.Cooler Water – Ratings are based upon 2.4 GPM per ton which is equal to a 10°F chilled water range and a 0.0001 fouling factor for the cooler at sea level. Tables on pages 16 through 39 give capacity, com- pressor kW required, cooler GPM and unit EER.
3.Condenser – Ratings are given in terms of air on condenser in degrees Fahrenheit.
4.Copper Fin Condenser Ratings – Since the ther- mal conductivity of copper is slightly higher than aluminum, apply the following corrections to the standard ratings. Tons x 0.97 and compressor kW x 0.99.
5.Performance Data Correction Factors – Ratings are based on 0.0001 cooler fouling factor, 10°F chilled water range and at sea level. For operation at different conditions, apply the appropriate correction factor from the following table.
FOULING FACTOR
| TEMP | 0.0001 | 0.00025 | |||
ALTITUDE | TONS | COMPR | TONS | COMPR | ||
SPLIT | ||||||
| kW | kW | ||||
|
|
|
| |||
| 8 | 0.990 | 0.998 | 0.979 | 0.996 | |
SEA LEVEL | 10 | 1.000 | 1.000 | 0.991 | 0.998 | |
12 | 1.012 | 1.003 | 1.002 | 1.001 | ||
| ||||||
| 14 | 1.021 | 1.005 | 1.012 | 1.003 | |
| 8 | 0.987 | 1.005 | 0.978 | 1.003 | |
2000 FT. | 10 | 0.997 | 1.008 | 0.988 | 1.006 | |
12 | 1.009 | 1.010 | 1.000 | 1.008 | ||
| ||||||
| 14 | 1.018 | 1.012 | 1.009 | 1.010 | |
| 8 | 0.983 | 1.014 | 0.975 | 1.012 | |
4000 FT. | 10 | 0.994 | 1.016 | 0.985 | 1.014 | |
12 | 1.005 | 1.019 | 1.111 | 1.017 | ||
| ||||||
| 14 | 1.014 | 1.021 | 1.006 | 1.019 | |
| 8 | 0.980 | 1.023 | 0.971 | 1.021 | |
6000 FT. | 10 | 0.990 | 1.025 | 0.982 | 1.023 | |
12 | 1.002 | 1.028 | 0.993 | 1.026 | ||
| ||||||
| 14 | 1.011 | 1.030 | 1.002 | 1.028 |
6.Ethylene Glycol Correction Factors – The fol- lowing factors are to be applied to the standard ratings for units cooling ethylene glycol.
ETHYLENE GLYCOL
% | TONS | COMPR | GPM | PRESS | FREEZE | |
WEIGHT | KW | °F/TON | DROP | PT | ||
| ||||||
10 | 0.996 | 0.999 | 24.3 | 1.049 | 26.2 | |
20 | 0.991 | 0.998 | 25.1 | 1.124 | 17.9 | |
30 | 0.984 | 0.997 | 25.9 | 1.258 | 6.7 | |
40 | 0.976 | 0.995 | 26.9 | 1.430 | ||
50 | 0.968 | 0.994 | 28.0 | 1.650 |
7.Propylene Glycol Correction Factors – The fol- lowing factors are to be applied to the standard ratings for units cooling propylene glycol.
PROPYLENE GLYCOL
% | TONS | COMPR | GPM | PRESS | FREEZE | |
WEIGHT | KW | °F/TON | DROP | PT | ||
| ||||||
10 | 0.995 | 0.999 | 24.0 | 1.014 | 26 | |
20 | 0.984 | 0.997 | 24.3 | 1.104 | 19 | |
30 | 0.973 | 0.994 | 24.9 | 1.234 | 9 | |
40 | 0.960 | 0.992 | 25.6 | 1.399 | ||
50 | 0.943 | 0.989 | 26.6 | 1.599 |
METHOD OF SELECTION
To select of YORK Packaged
1.Design Capacity in tons refrigeration (TR).
2.Entering and Leaving Liquid Temperatures.
3.Outside ambient air temperature in degrees F.
4.GPM of chilled liquid.
Determine capacity requirements from the following formula:
GPM = | TR x 24 |
RANGE (°F) |
EXAMPLE – WATER CHILLING
1.Given: Provide a capacity of 50 tons at 42 F leav- ing water at 10 F range. 0.0001FF, 85 F air on the condenser, at sea level and 60 Hz.
2.Find: Unit Size, Compressor KW Output
3.From the ratings on page 18.
Select: YCAL0061 (English Units)
YORK INTERNATIONAL | 11 |