York YCAL0041, YCAL0065 manual Electrical Data

Page 62

Electrical Data

NOTES:

1.Minimum Circuit Ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit, per N.E.C. Article 430-24. If the optional Factory Mounted Control Transformer is provided, add the following MCA values to the electrical tables for the system providing power to the transformer: -17, add 2.5 amps; -28, add 2.3 amps; -40, add 1.5 amps, -46, add 1.3 amps; -58, add 1 amps.

2.The minimum recommended disconnect switch is based on 115% of the rated load amps for all loads included in the circuit, per N.E.C. Article 440.

3.Minimum fuse size is based upon 150% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit to avoid nuisance trips at start-up due to lock rotor amps. It is not recommended in applications where brown outs, frequent starting and stopping of the unit, and/or operation at ambient temperatures in excess of 95ºF (35ºC) is anticipated.

4.Maximum fuse size is based upon 225% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit, per N.E.C. Article 440-22.

5.Circuit breakers must be UL listed and CSA certified and maximum size is based on 225% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit. Otherwise, an HACR-type circuit breakers must be used. Maximum HACR circuit breaker rating is based on 225% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit.

6.The “INCOMING WIRE RANGE” is the minimum and maximum wire size that can be accommodated by the unit wiring lugs. The (2) preceding the wire range indicates the number of termination points available per phase of the wire range specified. Actual wire size and number of wires per phase must be determined based on the National Electrical Code, using copper connectors only. Field wiring must also comply with local codes.

7.A ground lug is provided for each compressor system to accommodate a field grounding conductor per N.E.C. Table 250-95. A control circuit grounding lug is also supplied.

8.The supplied disconnect is a “Disconnecting Means” as defined in the N.E.C. 100, and is intended for isolating the unit for the available power supply to perform maintenance and troubleshooting. This disconnect is not intended to be a Load Break Device.

9.Field Wiring by others which complies to the National Electrical Code & Local Codes.

62

YORK INTERNATIONAL

Image 62
Contents AIR-COOLED Scroll Chillers Form 150.64-EG1Table of Contents Introduction Compressors SpecificationGeneral CoolerUnit ON/OFF switch Millennium Control CenterPower Panel SINGLE-POINT NON-FUSED Disconnect Switch Options and AccessoriesPower Options Control OptionsCondenser and Cabinet Options DX Cooler 300 Psig 21 bar DWP WatersideCompressor Acoustic Sound Blanket Each This page intentionally left blank Selection Rules Selection DataGuide to Selection Method of SelectionDetermine E.G. GPM Calculate GPMExample Brine Chilling SI Units Ycal Design ParametersEnglish Ycal Water Pressure Drop 1001000 Model YCAL0045EC Ratings R-22 60Hz English UnitsModel YCAL0041EC Model YCAL0051EC32.4 42.5 31.5 45.0 30.6 47.6 29.7 50.4 28.7 53.4 105 110.0 115.0 120.0 125.031.3 42.2 30.5 44.7 29.6 47.4 28.7 50.2 27.8 53.2 33.4 42.7 32.5 45.2 31.6 47.9 30.7 50.7 29.7 53.7Model YCAL0065EC Model YCAL0055ECModel YCAL0061EC 45.3 58.8 44.0 62.1 42.7 65.6 31.1 48.5 30.1 51.2 42.3 58.2 41.2 61.4 39.9 64.8 29.0 48.0 28.0 50.643.8 58.5 42.6 61.8 41.3 65.2 30.0 48.3 29.0 50.9 46.0 59.0 44.7 62.3 43.4 65.8 31.6 48.6 30.6 51.3Ratings R-22 60Hz SI Units 25.0 30.0 35.0 40.0 45.0 50.0172.2 43.1 166.0 47.5 159.3 52.3 152.2 57.7 Ratings R-22 50Hz English Units 44.0 34.7 27.5 36.9 26.7 39.4 25.9 42.0 24.9 44.8 40.0 34.3 25.7 36.5 25.0 39.0 24.1 41.6 23.2 44.442.0 34.5 26.6 36.7 25.8 39.2 25.0 41.8 24.1 44.6 45.0 34.8 28.0 37.0 27.2 39.5 26.3 42.1 25.4 44.940.0 10.6 33.8 13.135.7 12.2 34.0 13.544.0 48.0 37.4 50.9 36.3 53.8 35.2 57.0 34.0 60.3 40.0 47.5 35.0 50.3 33.9 53.3 32.8 56.4 31.7 59.742.0 47.8 36.2 50.6 35.1 53.6 34.0 56.7 32.8 60.0 45.0 48.2 38.1 51.0 36.9 54.0 35.8 57.1 34.6 60.5Ratings R-22 50Hz SI Units 146.1 34.7 140.9 38.4 135.3 42.5 129.3 47.1 Unit Part Load Ratings R-22 English UnitsFull Load Tons EER DisplYCAL055 Full Part Load Ratings R-22 SILoad COP Displ Load Scop DisplPhysical Data 87.0 Per Power ChillerSide Water 47400Sound Data 125 250 500 1000 2000 4000 8000 DBA50Hz Line Frequency Low Noise Fan R-22 Dimensions YCAL0041 English 45 5/16 DIA Mounting HOLEStyp90 9/16 13/160045 63.2 43.7 Dimensions YCAL0045 English0045 59.2 43.5 Copper 20 1/16 13/16 25 3/8 B 13 5/80051 64.3 42.9 Dimensions YCAL0051 English0051 59.2 42.6 Copper Front View 34 11/16 Dimensions YCAL0055EC English62 5/8 TYP 15/16 0055 57.9 43.0 Copper15 1/16 144 13/16 18 7/1628 9/16 43 1/8 Dimensions YCAL0061 English61 7/8 0061 56.6 45.2 Copper25 3/8 28 9/16 43 5/1616 11/16 0065 59.7 44.9 Copper Dimensions YCAL0065 English62 5/8 0065 65.2 44.9Cooler Coil END Dimensions YCAL0041 SI 249 23011150 5540045 1605.9 1109.7 Dimensions YCAL0045 SI0045 1503.5 1105.5 Copper 509 0051 1633.0 1090.8 Dimensions YCAL0051 SI0051 1504.6 1082.4 Copper Cooler END Dimensions -YCAL0055 SI 131 965 1151249 468 645 726Dimensions YCAL0061 SI 1100 249 4240065 1655.5 1141.1 Dimensions YCAL0065 SI0065 1517.6 1140.3 Copper TOP View ONE Inch Deflection Spring Isolator CROSS-REFERENCE Isolator SelectionsCIP-X For Units with ALL Point Loads Less Thatn 1404 LBS 637 KGUp to 751 lbs Up to 341 kg ND-XNeoprene Isolator CROSS-REFERENCE 751 to 1651 lbs 341 to 749 kg12 1/4 Isolator Details contdSlrs 215.9 34.9 355.6 311.2Intentionally Left Blank Electrical Data Voltage Range Electrical Data 60Hz RLA LUG Wire Range Electrical Data 50HzCOMPR. #1 COMPR. #2 Fans Power Wiring Standard Power Supply Wiring Ycal 0014York International York International Control Wiring Foundation Application DataUnit Location Chilled Liquid PipingInlet Quality Assurance Guide SpecificationsPart 1 General Delivery and HandlingControls Refrigerant Circuit ComponentsHeat Exchangers Power Connection and DISTRI- Bution Accessories and OptionsYork International Part 3 Execution Installation York International ALL Right