York YCAL0041, YCAL0065 manual Power Connection and DISTRI- Bution, Accessories and Options

Page 76

liquid temperature cutout, low suction pressure cutout, high discharge pressure cutout, anti-re- cycle timer (compressor start cycle time), and anti-coincident timer (delay compressor starts).

6.Display Data: Return and leaving liquid tem- peratures, low leaving liquid temperature cut- out setting, low ambient temperature cutout set- ting, outdoor air temperature, English or metric data, suction pressure cutout setting, each system suction pressure,discharge pres- sure (standard on YCAL0041-0065 models), liquid temperature reset via a YORK ISN DDC or Building Automation System (by others) via PWM input as standard or a 4-20milliamp or 0- 10 VDC input or contact closure with optional BAS interface, anti-recycle timer status for each compressor, anti-coincident system start timer condition, compressor run status, no cooling load condition, day, date and time, daily start/ stop times, holiday status, automatic or manual system lead/lag control, lead system definition, compressor starts/operating hours (each), sta- tus of hot gas valves, evaporator heater and fan operation, run permissive status, number of compressors running, liquid solenoid valve status, load & unload timer status, water pump status.

7.System Safeties: Shall cause individual com pressor systems to perform auto shut down; manual reset required after the third trip in 90 minutes. Includes: high discharge pressure, low suction pressure, high pressure switch, and motor protector. Compressor motor protector shall protect against damage due to high input current or thermal overload of windings.

8.Unit Safeties: Shall be automatic reset and cause compressors to shut down if low ambi- ent, low leaving chilled liquid temperature, un- der voltage, and flow switch operation. Contrac- tor shall provide flow switch and wiring per chiller manufacturer requirements.

9.Alarm Contacts: Low ambient, low leaving chilled liquid temperature, low voltage, low battery, and (per compressor circuit): high dis- charge pressure, and low suction pressure.

D.Manufacturer shall provide any controls not listed above, necessary for automatic chiller operation. Mechanical Contractor shall provide field control wiring necessary to interface sensors to the chiller control system.

2.06POWER CONNECTION AND DISTRI- BUTION

A.Power Panels:

1.NEMA 3R/12 (IP55) rain/dust tight, powder painted steel cabinets with hinged, latched, and gasket sealed outer doors. Provide main power connection(s), control power connections, com- pressor and fan motor start contactors, current overloads, and factory wiring.

2.Power supply shall enter unit at a single loca- tion, be 3 phase of scheduled voltage, and connect to individual terminal blocks per com- pressor. Separate disconnecting means and/ or external branch circuit protection (by Con- tractor) required per applicable local or national codes.

B.Exposed compressor, control and fan motor power wiring shall be routed through liquid tight conduit.

2.07ACCESSORIES AND OPTIONS

Some accessories and options supercede standard product features. Your YORK representative will be pleased to provide assistance.

A.Microprocessor controlled, Factory installed Across- the-Line type compressor motor starters as stan- dard.

B.Outdoor Ambient Temperature Control

1.Low Ambient Control: Permits unit operation to 0°F ambient. .

2.High Ambient Control: Permits unit operation above 115°F ambient.

C.Power Supply Connections:

1.Single Point Power Supply: Single point Termi- nal Block for field connection and interconnect- ing wiring to the compressors. Separate exter- nal protection must be supplied, by others, in the incoming power wiring, which must comply with the National Electric Code and/or local codes. Standard unit controls to 25°F ambient. Low Ambient Control standard on YCAL0041-0065 models

2.Single Point Power Supply with individual Sys- tem Breakers: Single or Terminal Block(s) for field connection and factory interconnecting wiring to factory supplied system breakers . Available on YCAL0090-0134 models.

3.Single Point or Disconnect: Single or Dual point Non-Fused Disconnect(s) and lockable exter- nal handle (in compliance with Article 440-14

76

YORK INTERNATIONAL

Image 76
Contents AIR-COOLED Scroll Chillers Form 150.64-EG1Table of Contents Introduction Specification GeneralCompressors CoolerUnit ON/OFF switch Millennium Control CenterPower Panel Options and Accessories Power OptionsSINGLE-POINT NON-FUSED Disconnect Switch Control OptionsCondenser and Cabinet Options DX Cooler 300 Psig 21 bar DWP WatersideCompressor Acoustic Sound Blanket Each This page intentionally left blank Selection Data Guide to SelectionSelection Rules Method of SelectionExample Brine Chilling Calculate GPMDetermine E.G. GPM English Ycal Design ParametersSI Units Ycal Water Pressure Drop 1001000 Ratings R-22 60Hz English Units Model YCAL0041ECModel YCAL0045EC Model YCAL0051EC105 110.0 115.0 120.0 125.0 31.3 42.2 30.5 44.7 29.6 47.4 28.7 50.2 27.8 53.232.4 42.5 31.5 45.0 30.6 47.6 29.7 50.4 28.7 53.4 33.4 42.7 32.5 45.2 31.6 47.9 30.7 50.7 29.7 53.7Model YCAL0061EC Model YCAL0055ECModel YCAL0065EC 42.3 58.2 41.2 61.4 39.9 64.8 29.0 48.0 28.0 50.6 43.8 58.5 42.6 61.8 41.3 65.2 30.0 48.3 29.0 50.945.3 58.8 44.0 62.1 42.7 65.6 31.1 48.5 30.1 51.2 46.0 59.0 44.7 62.3 43.4 65.8 31.6 48.6 30.6 51.3Ratings R-22 60Hz SI Units 25.0 30.0 35.0 40.0 45.0 50.0172.2 43.1 166.0 47.5 159.3 52.3 152.2 57.7 Ratings R-22 50Hz English Units 40.0 34.3 25.7 36.5 25.0 39.0 24.1 41.6 23.2 44.4 42.0 34.5 26.6 36.7 25.8 39.2 25.0 41.8 24.1 44.644.0 34.7 27.5 36.9 26.7 39.4 25.9 42.0 24.9 44.8 45.0 34.8 28.0 37.0 27.2 39.5 26.3 42.1 25.4 44.933.8 13.1 35.7 12.240.0 10.6 34.0 13.540.0 47.5 35.0 50.3 33.9 53.3 32.8 56.4 31.7 59.7 42.0 47.8 36.2 50.6 35.1 53.6 34.0 56.7 32.8 60.044.0 48.0 37.4 50.9 36.3 53.8 35.2 57.0 34.0 60.3 45.0 48.2 38.1 51.0 36.9 54.0 35.8 57.1 34.6 60.5Ratings R-22 50Hz SI Units 146.1 34.7 140.9 38.4 135.3 42.5 129.3 47.1 Part Load Ratings R-22 English Units FullUnit Load Tons EER DisplPart Load Ratings R-22 SI Load COP DisplYCAL055 Full Load Scop DisplPhysical Data Per Power Chiller Side Water87.0 47400Sound Data 125 250 500 1000 2000 4000 8000 DBA50Hz Line Frequency Low Noise Fan R-22 Dimensions YCAL0041 English DIA Mounting HOLEStyp 90 9/1645 5/16 13/160045 59.2 43.5 Copper Dimensions YCAL0045 English0045 63.2 43.7 20 1/16 13/16 25 3/8 B 13 5/80051 59.2 42.6 Copper Dimensions YCAL0051 English0051 64.3 42.9 Front View Dimensions YCAL0055EC English 62 5/8 TYP 15/1634 11/16 0055 57.9 43.0 Copper28 9/16 18 7/1615 1/16 144 13/16 Dimensions YCAL0061 English 61 7/843 1/8 0061 56.6 45.2 Copper16 11/16 43 5/1625 3/8 28 9/16 Dimensions YCAL0065 English 62 5/80065 59.7 44.9 Copper 0065 65.2 44.9Cooler Coil END Dimensions YCAL0041 SI 2301 1150249 5540045 1503.5 1105.5 Copper Dimensions YCAL0045 SI0045 1605.9 1109.7 509 0051 1504.6 1082.4 Copper Dimensions YCAL0051 SI0051 1633.0 1090.8 Cooler END Dimensions -YCAL0055 SI 1151 249 468131 965 645 726Dimensions YCAL0061 SI 1100 249 4240065 1517.6 1140.3 Copper Dimensions YCAL0065 SI0065 1655.5 1141.1 TOP View Isolator Selections CIP-XONE Inch Deflection Spring Isolator CROSS-REFERENCE For Units with ALL Point Loads Less Thatn 1404 LBS 637 KGND-X Neoprene Isolator CROSS-REFERENCEUp to 751 lbs Up to 341 kg 751 to 1651 lbs 341 to 749 kgIsolator Details contd Slrs12 1/4 215.9 34.9 355.6 311.2Intentionally Left Blank Electrical Data Voltage Range Electrical Data 60Hz RLA LUG Wire Range Electrical Data 50HzCOMPR. #1 COMPR. #2 Fans Power Wiring Standard Power Supply Wiring Ycal 0014York International York International Control Wiring Application Data Unit LocationFoundation Chilled Liquid PipingInlet Guide Specifications Part 1 GeneralQuality Assurance Delivery and HandlingHeat Exchangers Refrigerant Circuit ComponentsControls Power Connection and DISTRI- Bution Accessories and OptionsYork International Part 3 Execution Installation York International ALL Right