Lennox International Inc 2P1109, P506052-01 Installer setup − Page 8, Humidification modes

Page 13
HEAT SETPOINT+COOL SETPOINT
2

Installer setup − Page 8 of 8

setup

tests

equipment

HELP

SYSTEM

 

(to adjust a setting, highlight

 

it, then press edit)

 

 

 

 

Equipment Name

 

Current Value:

 

 

Filter 1 Timer

 

(Display Only)

 

 

 

Selection

 

 

 

.

 

 

 

.

 

 

 

(various)

 

 

 

.

 

edit

reset

.

 

 

 

 

Dehumidification

Control Mode

Humidificationback

Control Mode

Figure 16. SYSTEM adjustment screen

HUMIDIFICATION modes

BASIC & PRECISION modes allow user control of RH between

15 and 45%. These conditions must be met for either mode to operate:

Shumidification mode has been enabled, and

Sthe unit is in HEAT mode, and

Shumidification demand exists (24V present at H), and

SBASIC mode also requires heat demand exists (Y for HP heat, or W for gas heat [W may be energized with G de−energized]).

DEW POINT CONTROL

humidification setpoint based on the outdoor temperature and a user−de- fined dew point adjustment setting.

DEHUMIDIFICATION modes

In BASIC mode, dehumidification occurs if these conditions are met and signals are present at specific terminals:

Sdehumidification has been enabled on installer settings, and

Sthe unit is in COOL mode, and

Sdehumidification demand exists (RH above setpoint), and

Scooling demand exists (Y1 energized).

Dehumidification Control Mode

Display Only

Basic

Precision

Humiditrol

cancel

(or Auxiliary

 

Dehumidifier)

 

save

Humidification Control Mode

Display Only

 

Basic

 

Precision

 

Dew Point Control

cancel

save

In PRECISION mode, dehumidification occurs if all BASIC conditions are true, except cooling demand may or may not be present. Maximum overcool from cooling set point is 2ºF.

HUMIDITROL or AUX. DEHUMIDIFIER mode requires:

Soutdoor sensor must be installed and setup

Sdehumidification has been enabled on installer settings, and

Sthe unit is in COOL mode, (or if in AUTO, at least one thermostat cooling call made prior to the dehumidification demand), and

Sa dehumidification demand exists (RH above setpoint), and

Soutdoor temp. below 95°F; indoor temp. above 65°F, and

Sfor HUMIDITROL, Humiditrol comfort adjust parameters as follows:

MAX adj. − Indoor temp > 2°F above heating setpoint

MID adj. − Indoor temp >

Figure 17. Selecting Dehumidification/Humidification mode

MIN adj. − Indoor temp > 2°F below cooling setpoint

Page 13

icomfortt Touch Screen 7−Day Programmable Thermostat

Image 13
Contents Shipping and Packing List1 Controls 506052−01Touch Screen Programmable Communicating Thermostat 11/09Table of Contents Icomfortt Thermostat Terms and Acronyms + I − C Icomfortt Technical DescriptionInstalling icomfortt thermostat Icomfortt Thermostat FeaturesOutdoor Temperature Sensor Thermostat TypeCritical alert Installer setup − Page 1Thepress here to contin- ue Thermostat Use this Thermostat? Press hereSome settings Installer setup − Page 2Up/down arrows Scroll through a Numeric range forSetting time and date Installer setup − Page 3Settings and return to previous settings screen Oct 2009Cancel Save Installer setup − Page 4Add/remove/modify non−communicating devices YesModify communicating device settings Installer setup − Page 5Setup System devices About Edit Reset ALL BackConfirmcancel Installer setup − Page 6Indoor air quality controls Installer setup − Page 7Only System 49W95 A109K00139Humidification modes Installer setup − Page 8Dehumidification modes MIN adj. − Indoor temp 2F below cooling setpointTests − Page 1 Press start to begin testingTests to run screen appears Current Test Blower Check Blower Operation Cancel done Current Test Blower Check Blower Operation Cancel nextSingle test example Equipment details edit Equipment − Page 1Select type of device to run Diagnostics on Diagnostics − Page 1Run diagnostics on HP Diagnostics RemovestartAlert description Alerts − Page 1Active alerts Remind later Clear BackClearing alerts Alerts − Page 2Ingly If you press yes to ’was action taken?’,Alerts − Page 3 Using10 19 AM 12 19View cleared alerts Alerts − Page 4Qualified Lennox equipment installer warning Access installer program from Home screen − Page 1Setup Tests Equipment tests Reconfiguring a system − Page 1Setup Tests Equipment Start BackChanges tonext to advance to the next screen Reconfiguring a system − Page 2Installer settings Editable Parameters Table User and InstallerTable on next Table on next AIR Handler Furnace Heat Pump Airflow Setting User settings Alarm ID Message Name Action required to Clear/Recover Alarm Codes and TroubleshootingIOM Alarm Codes and Troubleshooting Alarm Codes and Troubleshooting Alarm Codes and Troubleshooting Wiring Diagrams − Communicating Systems Optional DIS Charge AIR SEN SOR see DAS Discharge AIR Sensor Required for Even Heat Optional Accessories for use with any icomfortt systemFurnace or AIR Handlerstandard 1 or 2 Stage