Lennox International Inc Touch Screen Programmable Communicating Thermostat, P506052-01, 2P1109

Page 29

 

 

Value

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter Name

Default

Min.

 

Max.

Incr.

Dependency

Note

 

 

 

 

Cooling Airflow Setting

 

 

 

 

 

 

 

 

 

High Cooling Airflow

OU tons (OUNC) *

Min CFM

 

Max CFM

25

Outdoor Unit present

1/2 HP blower

(CFM @ 100% cool)

400CFM

 

 

 

 

 

 

Min CFM

 

Max CFM

25

 

1 HP blower

 

 

 

 

 

 

 

 

 

 

 

 

Low Cooling Airflow

See Note1 below

Min CFM

 

Max CFM

25

2+ stage Outdoor Unit present

1/2 HP blower

(CFM @ lowest cool stage)

 

 

 

 

 

 

 

 

Min CFM

 

Max CFM

25

 

1 HP blower

 

 

 

 

 

 

 

 

 

 

 

 

Airflow Profile − Cooling

DIP SW

0

 

3

1

Outdoor Unit present

0–Text ID 0x0105

 

 

 

 

 

 

 

(A:ON:50%/30s,82%/7.5min

 

 

 

 

 

 

 

OFF:50%/30s)

 

 

 

 

 

 

 

1–Text ID 0x0106 (B:ON:82%/7.5min;

 

 

 

 

 

 

 

OFF: No delays)

 

 

 

 

 

 

 

2–Text ID 0x0107 (C:ON: No delays;

 

 

 

 

 

 

 

OFF: 45sec delay)

 

 

 

 

 

 

 

3–Text ID 0x0108 (D:No delays)

 

 

 

 

 

 

 

 

 

 

 

Heat Pump Airflow Setting

 

 

 

 

 

 

 

 

 

High Heat Pump Airflow (CFM @

OU tons (OUNC) *

Min CFM

 

Max CFM

25

Heat Pump present

1/2 HP blower

100%)

400CFM

 

 

 

 

 

 

Min CFM

 

Max CFM

25

 

1 HP blower

 

 

 

 

 

 

 

 

 

 

 

 

Low Heat Pump Airflow (CFM @ lowest

See Note 2 below

Min CFM

 

Max CFM

25

2+ stage Heat Pump present

1/2 HP blower

stage)

 

 

 

 

 

 

 

 

Min CFM

 

Max CFM

25

 

1 HP blower

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Other Parameters

 

 

 

 

 

 

 

 

 

Equipment Name

Furnace

N/A

 

N/A

N/A

None

Up to 35 characters

 

 

 

 

 

 

 

 

Continuous Indoor Blower Airflow

DIP SW (See

Min CFM

 

Max CFM

25

None

1/2 HP blower

 

Note 3)

 

 

 

 

 

 

 

Min CFM

 

Max CFM

25

 

1 HP blower

 

 

 

 

 

 

 

 

 

 

 

 

Humidification Airflow

Same as above

Min CFM

 

Max CFM

25

Humidifier present

1/2 HP blower

 

 

 

 

 

 

 

 

 

 

Min CFM

 

Max CFM

25

 

1 HP blower

 

 

 

 

 

 

 

 

Dehumidification Airflow Percentage

140

120

 

160

2

OU present AND SC algorithm support

Percent of High Cooling Airflow

 

(=70%)

(=60%)

 

(=80%)

(=1%)

 

 

 

 

 

 

 

 

 

 

Note 1: Minimum Outdoor Unit Cooling Stage as a percentage of High Cooling Airflow (value is rounded up to the closest number on 25 CFM resolution

Note 2: Minimum Outdoor Unit Heating Stage as a percentage of High Heat Pump Airflow (value is rounded up to the closest number on 25 CFM resolution).

Note 3: All communicating Installer Parameters default CFM values based on DIP switch setting (non−communicating value) are calculated using the CFM conversion tables and rounded up to closest number on 25 CFM resolution.

Note 4: Parameter dependency − Certain parameters are dependent on others and may not be shown on the display.

Note 5: Default Values − Jumper/DIP switches impact the default value of some parameters.

Page 29

icomfortt Touch Screen 7−Day Programmable Thermostat

Image 29
Contents Shipping and Packing List1 Controls 506052−01Touch Screen Programmable Communicating Thermostat 11/09Table of Contents Icomfortt Thermostat Terms and Acronyms + I − C Icomfortt Technical DescriptionInstalling icomfortt thermostat Icomfortt Thermostat FeaturesOutdoor Temperature Sensor Thermostat TypeCritical alert Installer setup − Page 1Thepress here to contin- ue Thermostat Use this Thermostat? Press hereSome settings Installer setup − Page 2Up/down arrows Scroll through a Numeric range forSetting time and date Installer setup − Page 3Settings and return to previous settings screen Oct 2009Cancel Save Installer setup − Page 4Add/remove/modify non−communicating devices YesModify communicating device settings Installer setup − Page 5Setup System devices About Edit Reset ALL BackConfirmcancel Installer setup − Page 6Indoor air quality controls Installer setup − Page 7Only System 49W95 A109K00139Humidification modes Installer setup − Page 8Dehumidification modes MIN adj. − Indoor temp 2F below cooling setpointTests to run screen appears Press start to begin testingTests − Page 1 Single test example Current Test Blower Check Blower Operation Cancel nextCurrent Test Blower Check Blower Operation Cancel done Equipment details edit Equipment − Page 1Select type of device to run Diagnostics on Diagnostics − Page 1Run diagnostics on HP Diagnostics RemovestartAlert description Alerts − Page 1Active alerts Remind later Clear BackClearing alerts Alerts − Page 2Ingly If you press yes to ’was action taken?’,Alerts − Page 3 Using10 19 AM 12 19View cleared alerts Alerts − Page 4Qualified Lennox equipment installer warning Access installer program from Home screen − Page 1Setup Tests Equipment tests Reconfiguring a system − Page 1Setup Tests Equipment Start BackChanges tonext to advance to the next screen Reconfiguring a system − Page 2Table on next Editable Parameters Table User and InstallerInstaller settings Table on next AIR Handler Furnace Heat Pump Airflow Setting User settings Alarm ID Message Name Action required to Clear/Recover Alarm Codes and TroubleshootingIOM Alarm Codes and Troubleshooting Alarm Codes and Troubleshooting Alarm Codes and Troubleshooting Wiring Diagrams − Communicating Systems Optional DIS Charge AIR SEN SOR see DAS Discharge AIR Sensor Required for Even Heat Optional Accessories for use with any icomfortt systemFurnace or AIR Handlerstandard 1 or 2 Stage