Lennox International Inc P506052-01, 2P1109 setup guide Alarm Codes and Troubleshooting

Page 33

 

Alarm Codes and Troubleshooting

 

 

 

Alarm ID

Message Name

Action required to Clear/Recover

 

 

 

241

Flame Out of Sequence − Still Present

Shut off gas, check for gas valve leak.

 

 

 

250

Primary Limit Switch Open

Check firing rate on furnace, blockage in heater, and air flow.

 

 

 

252

Discharge Air Temperature High

Check temperature rise, air flow and input rate.

 

 

 

270

Watch Guard − Flame Failure on Ignite

Check for gas flow, ignitor lighting burner, flame sensor current.

 

 

 

271

Watch Guard − Low Pressure Switch Open

Check inches of water column closing pressure of low pressure switch on heat call, measure inches of water

 

 

column of operating pressure, inspect vent and combustion air inducer for correct operation and restriction.

 

 

 

272

Watch Guard − Low Pressure Switch Open Run

Check operation of low pressure switch for stuck closed on heat call, measure inches of water column of oper-

 

Mode

ating pressure, inspect vent and combustion air inducer for correct operation and restriction. Check inches of

 

 

water column closing pressure of high pressure switch on heat call, measure inches of water column of operat-

 

 

ing pressure, inspect vent and combustion air inducer for correct operation and restriction.

 

 

 

273

Watch Guard − Flame Fail in Run Mode

Check micro amperes of flame sensor in board diagnostics or field installed mode; clean or replace sensor.

 

 

Measure voltage of neutral to ground for good unit ground.

 

 

 

274

Watch Guard − Primary Limit Switch Open

Check why limit is tripping, over fired, low air flow.

 

 

 

275

Watch Guard − Flame Out of Sequence. No

Shut off gas, check for gas valve leak.

 

Flame

 

 

 

 

276

Watch Guard − Calibration Failure

Unable to perform pressure switch calibration. Check vent system and pressure switch wiring connections.

 

 

 

290

Ignition Circuit Problem

Measure resistance of Hot Surface Ignition ignitor, replace if open or not within specification; otherwise replace

 

 

control.

 

 

 

291

Heat Airflow Restricted Below Min.

Check for dirty filter, unit air flow restriction, blower performance.

 

 

 

292

Indoor Blower Motor Start Problem

Indoor blower motor unable to start (seized bearing, stuck wheel, etc.). Replace motor or wheel if assembly

 

 

does not operate or meet performance.

 

 

 

294

Inducer Motor Over current

Check combustion blower bearings, wiring, amps. Replace if does not operate or meets performance.

 

 

 

295

Indoor Blower Over Temperature

Indoor blower motor over temperature (motor tripped on internal protector). Check motor bearings, amps; re-

 

 

place if necessary.

 

 

 

310

Discharge Air Sensor Problem

Compare outdoor sensor resistance to temperature/resistance charts in installation instructions. Replace sensor

 

 

if necessary.

 

 

 

311

Heat Rate Reduced to Match Airflow

Furnace blower in cutback mode due to restricted airflow. Check filter and ductwork. To clear, replace filter if

 

 

needed or repair/add ductwork.

 

 

 

312

Reduced Airflow − Indoor Blower Cutback

Restricted airflow − Indoor blower is running at a reduced CFM (Cutback Mode − The variable speed motor has

 

 

pre−set speed and torque limiters to protect the motor from damage caused by operating out of its designed

 

 

parameters (0 to 0.8" w.g. total external static pressure). Check filter and ductwork. To clear, replace filter if

 

 

needed or repair/add ductwork.

 

 

 

 

 

table continued on next page

Page 33

icomfortt Touch Screen 7−Day Programmable Thermostat

Image 33
Contents Shipping and Packing List1 Controls 506052−01Touch Screen Programmable Communicating Thermostat 11/09Table of Contents Icomfortt Thermostat Terms and Acronyms + I − C Icomfortt Technical DescriptionInstalling icomfortt thermostat Icomfortt Thermostat FeaturesOutdoor Temperature Sensor Thermostat TypeCritical alert Installer setup − Page 1Thepress here to contin- ue Thermostat Use this Thermostat? Press hereSome settings Installer setup − Page 2Up/down arrows Scroll through a Numeric range forSetting time and date Installer setup − Page 3Settings and return to previous settings screen Oct 2009Cancel Save Installer setup − Page 4Add/remove/modify non−communicating devices YesModify communicating device settings Installer setup − Page 5Setup System devices About Edit Reset ALL BackConfirmcancel Installer setup − Page 6Indoor air quality controls Installer setup − Page 7Only System 49W95 A109K00139Humidification modes Installer setup − Page 8Dehumidification modes MIN adj. − Indoor temp 2F below cooling setpointPress start to begin testing Tests − Page 1Tests to run screen appears Current Test Blower Check Blower Operation Cancel next Current Test Blower Check Blower Operation Cancel doneSingle test example Equipment details edit Equipment − Page 1Select type of device to run Diagnostics on Diagnostics − Page 1Run diagnostics on HP Diagnostics RemovestartAlert description Alerts − Page 1Active alerts Remind later Clear BackClearing alerts Alerts − Page 2Ingly If you press yes to ’was action taken?’,Alerts − Page 3 Using10 19 AM 12 19View cleared alerts Alerts − Page 4Qualified Lennox equipment installer warning Access installer program from Home screen − Page 1Setup Tests Equipment tests Reconfiguring a system − Page 1Setup Tests Equipment Start BackChanges tonext to advance to the next screen Reconfiguring a system − Page 2Editable Parameters Table User and Installer Installer settingsTable on next Table on next AIR Handler Furnace Heat Pump Airflow Setting User settings Alarm ID Message Name Action required to Clear/Recover Alarm Codes and TroubleshootingIOM Alarm Codes and Troubleshooting Alarm Codes and Troubleshooting Alarm Codes and Troubleshooting Wiring Diagrams − Communicating Systems Optional DIS Charge AIR SEN SOR see DAS Discharge AIR Sensor Required for Even Heat Optional Accessories for use with any icomfortt systemFurnace or AIR Handlerstandard 1 or 2 Stage