Parameter Name: | Default | Parameter Value Setting | Increment |
|
|
|
|
|
|
|
|
1st Stage Differential | 0.5ºF | 0.5 to 3ºF | .5ºF |
|
|
|
|
2nd Stage Differential | 1.5ºF | 0.5 to 8ºF | .5ºF |
|
|
|
|
3rd Stage Differential | 2.0ºF | 0.5 to 8ºF | .5ºF |
|
|
|
|
4th Stage Differential | 2.5ºF | 0.5 to 8ºF | .5ºF |
|
|
|
|
5th Stage Differential | 3.0ºF | 0.5 to 8ºF | .5ºF |
|
|
|
|
6th Stage Differential | 3.5ºF | 0.5 to 8ºF | .5ºF |
|
|
|
|
Stage Delay Timers | Enabled | Enabled, Disabled |
|
|
|
|
|
2nd Stage Delay | 20 Minutes | 5 to 120 Minutes | 5 Min |
|
|
|
|
3rd Stage Delay | 20 Minutes | 5 to 120 Minutes | 5 Min |
|
|
|
|
4th Stage Delay | 20 Minutes | 5 to 120 Minutes | 5 Min |
|
|
|
|
5thStage Delay | 20 Minutes | 5 to 120 Minutes | 5 Min |
|
|
|
|
6th Stage Delay | 20 Minutes | 5 to 120 Minutes | 5 Min |
|
|
|
|
Locked in 2nd Stage HP by Outdoor Temp | Off | Off, 40F (4C), 45F (7C), 50F (10C), 55F (13C), |
|
|
|
|
|
Balance Point Control | Disabled | Enabled, Disabled |
|
|
|
|
|
Defrost Target Discharge Temp | 55ºF | 50 to 60ºF | 1ºF |
|
|
|
|
Dehumidification Control Mode | Display Only | Display Only, Basic, Precision |
|
|
|
|
|
Humidification Control Mode | Display Only | Display Only, Basic, Precision, Dew Point Control |
|
|
|
|
|
Autochangeover Humidification Deadband | 5% | 5 to 10% | 1ºF |
|
|
|
|
Max Humidification Setpoint | 45% | 15 to 45% | 1ºF |
|
|
|
|
Max Dehumidification Setpoint | 40% | 40 to 60% | 1ºF |
|
|
|
|
OK/Humid Boundary | 50% | 45 to 60% | 1ºF |
|
|
|
|