Alarm Codes and Troubleshooting

 

 

 

Alarm ID

Message Name

Action required to Clear/Recover

 

 

 

313

Indoor/Outdoor Unit Capacity Mismatch

Incorrect indoor/outdoor capacity code selected. Check for proper configuring in installation instructions. Alarm

 

 

is just a warning. The system will operate, but might not meet efficiency and capacity parameters and alarm

 

 

would clear when commissioning is exited.

 

 

 

345

Relay O Failure

O relay / Stage 1 failed (Pilot relay contacts did not close or the relay coil did not energize),

 

 

 

346

HP Jumper not Removed

Configuration jumper(s) not removed on control board cut O−R. Applicable with non communicating outdoor unit

 

 

with communicating indoor system.

 

 

 

347

Relay Y1 Failure

Y1 relay / Stage 1 failed (Pilot relay contacts did not close or the relay coil did not energize),

 

 

 

348

Relay Y2 Failure

Y2 relay / Stage 2 failed (Pilot relay contacts did not close or the relay coil did not energize),

 

 

 

349

IFC Error Check Jumper O to R

Configuration link R to O needs to restored Applicable in non communicating mode,

 

 

 

350

Electric Heat not Configured

Heat call with no configured or mis−configured electric heat. Check for proper configuring under Configuring

 

 

Electric Heat Stages in the air handler installation instructions.

 

 

 

351

Electric Heat Stage 1 Problem

Heat section / Stage 1 failed (Pilot relay contacts did not close or the relay coil in the electric heat section did

 

 

not energize).

 

 

 

352

Electric Heat Stage 2 Problem

Heat section / Stage 2 failed (Same as Code 351).

 

 

 

353

Electric Heat Stage 3 Problem

Heat section / Stage 3 failed (Same as Code 351).

 

 

 

354

Electric Heat Stage 4 Problem

Heat section / Stage 4 failed (Same as Code 351).

 

 

 

355

Electric Heat Stage 5 Problem

Heat section / Stage 5 failed (Same as Code 351).

 

 

 

400

LSOM Compressor Internal Overload Tripped

Compressor protector is open. Check for high head pressure, check compressor supply voltage.

 

 

Outdoor unit power disconnect is open.

 

 

Compressor circuit breaker or fuse(s) is open.

 

 

Broken wire or connector is not making contact.

 

 

Low or high pressure switch open if present in the system.

 

 

Compressor contactor has failed to close.

 

 

 

401

LSOM Compressor Long Run Cycle

Compressor ran over 18 hours on one room thermostat demand.

 

 

 

402

LSOM Outdoor Unit System Pressure Trip

Outdoor unit pressure trip. Check dirty coil, fan motor, refrigerant charge.

 

 

 

403

LSOM Compressor Short−Cycling

Compressor short cycling (Running less than 4 minutes).

 

 

 

404

LSOM Compressor Rotor Locked

Check capacitor, wiring, hard−start kit, replace compressor.

 

 

 

405

LSOM Compressor Open Circuit

 

 

 

Check compressor for hot (cool down), check pressures, fan motor etc. Replace compressor if unable to get

406

LSOM Compressor Open Start Circuit

circuit to close and compressor to operate.

 

 

407

LSOM Compressor Open Run Circuit

 

 

 

 

408

LSOM Compressor Contactor Welded

Replace contactor.

 

 

 

409

LSOM Compressor Voltage Low

Check power to unit.

 

 

 

table continued on next page

506052−01 11/09

Page 34

Image 34
Contents Touch Screen Programmable Communicating Thermostat Controls 506052−01Shipping and Packing List1 11/09Table of Contents Icomfortt Thermostat Terms and Acronyms Icomfortt Technical Description + I − COutdoor Temperature Sensor Icomfortt Thermostat FeaturesInstalling icomfortt thermostat Thermostat TypeThepress here to contin- ue Installer setup − Page 1Critical alert Thermostat Use this Thermostat? Press hereUp/down arrows Installer setup − Page 2Some settings Scroll through a Numeric range forSettings and return to previous settings screen Installer setup − Page 3Setting time and date Oct 2009Add/remove/modify non−communicating devices Installer setup − Page 4Cancel Save YesSetup System devices Installer setup − Page 5Modify communicating device settings About Edit Reset ALL BackInstaller setup − Page 6 ConfirmcancelOnly Installer setup − Page 7Indoor air quality controls System 49W95 A109K00139Dehumidification modes Installer setup − Page 8Humidification modes MIN adj. − Indoor temp 2F below cooling setpointTests − Page 1 Press start to begin testingTests to run screen appears Current Test Blower Check Blower Operation Cancel done Current Test Blower Check Blower Operation Cancel nextSingle test example Equipment − Page 1 Equipment details editRun diagnostics on Diagnostics − Page 1Select type of device to run Diagnostics on HP Diagnostics RemovestartActive alerts Remind later Alerts − Page 1Alert description Clear BackIngly Alerts − Page 2Clearing alerts If you press yes to ’was action taken?’,10 19 AM UsingAlerts − Page 3 12 19Alerts − Page 4 View cleared alertsAccess installer program from Home screen − Page 1 Qualified Lennox equipment installer warningSetup Tests Equipment Reconfiguring a system − Page 1Setup Tests Equipment tests Start BackReconfiguring a system − Page 2 Changes tonext to advance to the next screenInstaller settings Editable Parameters Table User and InstallerTable on next Table on next AIR Handler Furnace Heat Pump Airflow Setting User settings Alarm Codes and Troubleshooting Alarm ID Message Name Action required to Clear/RecoverIOM Alarm Codes and Troubleshooting Alarm Codes and Troubleshooting Alarm Codes and Troubleshooting Wiring Diagrams − Communicating Systems Optional DIS Charge AIR SEN SOR see DAS Optional Accessories for use with any icomfortt system Discharge AIR Sensor Required for Even HeatFurnace or AIR Handlerstandard 1 or 2 Stage