Alarm Codes and Troubleshooting

 

 

 

Alarm ID

Message Name

Action required to Clear/Recover

 

 

 

410

Open Low Pressure Switch

Remove any blockages or restrictions from indoor coils and/or fans. Check refrigerant charge and system operation.

 

 

 

411

Low Pressure Switch Strikes Lockout

Check system charge using approach and sub cooling temperatures. Reset by putting outdoor board in test

 

 

mode or resetting low voltage power.

 

 

 

412

Open High Pressure Switch

Check system operating pressures and compare to unit charging charts.

 

 

 

413

High Pressure Switch Strikes Lockout

Check system charge using approach and sub cooling temperatures. Reset by putting outdoor board in test

 

 

mode or resetting low voltage power.

 

 

 

414

High Discharge Line Temperature

Check system operating pressures and compare to unit charging charts.

 

 

 

415

High Discharge Line Temperature Strikes Lock-

Check system charge using approach and sub cooling temperatures. Reset by putting outdoor board in test

 

out

mode or resetting low voltage power.

 

 

 

416

Outdoor Coil Sensor Faulty

Sensor being detected open or shorted or out of temperature range. Board will not perform demand or time/tem-

 

 

perature defrost operation. (System will still heat or cool).

 

 

 

417

Discharge Sensor Faulty

The board detects open sensor or out of temperature sensor range. This fault is detected by allowing the unit to

 

 

run for 90 seconds before checking sensor resistance. If the sensor resistances not within range after 90 sec-

 

 

onds, the board will count one fault. After 5 faults, the board will lockout.

 

 

 

418

W Output Hardware Fault

Replace the control board.

 

 

 

419

W Output Hardware Fault Lockout

 

 

 

 

420

Defrost Out of Control

Defrost longer than 20 minutes. Check HP operation.

 

 

 

421

W External Miswire Alarm

Check and correct the wiring.

 

 

 

530

Damper End Switch Failed to Close

Repair/replace damper.

 

 

 

531

Damper End Switch Failed to Open

Repair/replace damper.

 

 

 

532

Damper Control Module Alarm

Check/replace if needed.

 

 

 

594

Discharge Air Temperature Sensor Problem

Check wiring. Ohm out sensor and check to temperature/resistance chart.

 

 

 

700

Comfort Sensor Temperature Sensor Problem

Recalibrate stat to clear, replace thermostat if needed.

 

 

 

701

Comfort Sensor Temperature Too High

Recalibrate stat to clear, cool down stat, adjust setpoint, replace thermostat if needed.

 

 

 

702

Comfort Sensor Temperature Too Low

Recalibrate stat to clear, warm up stat, adjust setpoint, replace thermostat if needed.

 

 

 

703

Comfort Sensor Humidity Sensor Problem

Recalibrate stat to clear, adjust setpoint, replace thermostat if needed.

 

 

 

704

Comfort Sensor Humidity Too High

Recalibrate stat to clear, replace thermostat if needed.

 

 

 

705

Comfort Sensor Humidity Too Low

Recalibrate stat to clear replace thermostat if needed.

Page 35

icomfortt Touch Screen 7−Day Programmable Thermostat

Image 35
Contents 11/09 Controls 506052−01Shipping and Packing List1 Touch Screen Programmable Communicating ThermostatTable of Contents Icomfortt Thermostat Terms and Acronyms + I − C Icomfortt Technical DescriptionThermostat Type Icomfortt Thermostat FeaturesInstalling icomfortt thermostat Outdoor Temperature SensorThermostat Use this Thermostat? Press here Installer setup − Page 1Critical alert Thepress here to contin- ueScroll through a Numeric range for Installer setup − Page 2Some settings Up/down arrowsOct 2009 Installer setup − Page 3Setting time and date Settings and return to previous settings screenYes Installer setup − Page 4Cancel Save Add/remove/modify non−communicating devicesAbout Edit Reset ALL Back Installer setup − Page 5Modify communicating device settings Setup System devicesConfirmcancel Installer setup − Page 6System 49W95 A109K00139 Installer setup − Page 7Indoor air quality controls OnlyMIN adj. − Indoor temp 2F below cooling setpoint Installer setup − Page 8Humidification modes Dehumidification modesTests to run screen appears Press start to begin testingTests − Page 1 Single test example Current Test Blower Check Blower Operation Cancel nextCurrent Test Blower Check Blower Operation Cancel done Equipment details edit Equipment − Page 1HP Diagnostics Removestart Diagnostics − Page 1Select type of device to run Diagnostics on Run diagnostics onClear Back Alerts − Page 1Alert description Active alerts Remind laterIf you press yes to ’was action taken?’, Alerts − Page 2Clearing alerts Ingly12 19 UsingAlerts − Page 3 10 19 AMView cleared alerts Alerts − Page 4Qualified Lennox equipment installer warning Access installer program from Home screen − Page 1Start Back Reconfiguring a system − Page 1Setup Tests Equipment tests Setup Tests EquipmentChanges tonext to advance to the next screen Reconfiguring a system − Page 2Table on next Editable Parameters Table User and InstallerInstaller settings Table on next AIR Handler Furnace Heat Pump Airflow Setting User settings Alarm ID Message Name Action required to Clear/Recover Alarm Codes and TroubleshootingIOM Alarm Codes and Troubleshooting Alarm Codes and Troubleshooting Alarm Codes and Troubleshooting Wiring Diagrams − Communicating Systems Optional DIS Charge AIR SEN SOR see DAS Discharge AIR Sensor Required for Even Heat Optional Accessories for use with any icomfortt systemFurnace or AIR Handlerstandard 1 or 2 Stage