Raypak 240692 Water Temperature Sensor Installation, Hydronic Installations, Typical Water Sensor

Page 10

WATER TEMPERATURE SENSOR INSTALLATION

HYDRONIC INSTALLATIONS

Fig. #9496

TYPICAL WATER SENSOR

The water sensor should be installed in the system supply.

Locate the water temperature sensor in the system piping just prior to the first boiler connections, on the upstream side of the System Supply Loop.

Cable length must not exceed 300 feet.

Install in shielded conduit with no other wiring.

Observe wire colors.

10

Image 10
Contents Electronic Boiler Sequencer & Outdoor Reset Controller Installation and Operating Instructions Series Electronic Boiler ControlTable of Contents Important Safety Instructions BasicsIntroduction Optional ConfigurationsConcept of Operation Control Features Standard Indicator LightsElectrical Installation Installation and MountingMechanical Installation Install Conduit AS AppropriateWiring Power Source to Controller CheckyourpowersourceAIR Temperature Sensor Outdoor AIR Temperature SensorHydronic Installations Water Temperature Sensor InstallationTypical Water Sensor Domestic HOT Water Installations Domestic HOT Water Application Setup ProcedurePool Heating Installations Field Wiring Single-Stage On/Off BoilersInstallation Verification Procedure Power TestControl Familiarization Sequence of Operation Manual OverrideSeries Electronic Boiler Control Module Indicator Lights Reset Ratio Control FunctionsReset Ratio Chart Pump TURN-OFF DelayControl Band Stage TURN-ON DelayOutdoor Cutoff Temperature Outdoor Cutoff DeadbandMaximum Water Temperature SET PointCircuit Board Interior Jumper & Switches AutoManual LEAD-LAG SlaveDHW Output OverrideNight Setback Option Optional ControlsDigital Display Option Replacement Parts List Call OUT DescriptionSystem Setting Entered on Date System START-UP SettingsInterior Jumper & Switch Settings Troubleshooting Guide OFFLimited Warranty Litho in U.S.A