Raypak 240692 manual Interior Jumper & Switches, Auto

Page 24
Off - Manual lead-lag selection On - Automatic lead-lag selection
Off - Outdoor Reset Enabled
On - Outdoor Reset Disabled. Use this setting for applications like Domestic Hot Water where outdoor air sensing is not required.

INTERIOR JUMPER & SWITCHES

J-2

The Last Stage Selector Jumper (J2) is comprised of an eight (8) position jumper block. A shunt bar jumper is placed in the position corresponding to the last active stage or boiler number. See table below for examples of Jumper (J2) settings.

Fig # 9242

S-2

S-3

Fig # 9246

The First Stage Selector (Stage #1 ID) (S2) Switch is an eight (8) position switch, each switch position corresponds to a Y-Series output stage. Turn ON the switch(s) that correspond(s) to the FIRST stage of EACH boiler. Turn OFF the switch(s) that correspond(s) to the second (or subsequent) stage(s), of EACH boiler.

(Switch #1 should always be on.) See the table below for examples.

Fig # 9245

The Mode Selector Switch (S3) is comprised of an eight (8) position dip switch with the following functions:

AUTO

Sw #1 - Manual/Auto Lead-lag Selection

OD off

Sw #2 - Outdoor Reset "OD off"

Note: The outdoor sensor must be connected in all modes, otherwise a sensor error will be displayed.

24

Image 24
Contents Electronic Boiler Sequencer & Outdoor Reset Controller Installation and Operating Instructions Series Electronic Boiler ControlTable of Contents Important Safety Instructions BasicsOptional Configurations IntroductionConcept of Operation Control Features Standard Indicator LightsInstallation and Mounting Mechanical InstallationElectrical Installation Install Conduit AS AppropriateWiring Power Source to Controller CheckyourpowersourceAIR Temperature Sensor Outdoor AIR Temperature SensorWater Temperature Sensor Installation Hydronic InstallationsTypical Water Sensor Domestic HOT Water Installations Domestic HOT Water Application Setup ProcedurePool Heating Installations Field Wiring Single-Stage On/Off BoilersInstallation Verification Procedure Power TestControl Familiarization Sequence of Operation Manual OverrideSeries Electronic Boiler Control Module Indicator Lights Reset Ratio Control FunctionsReset Ratio Chart Pump TURN-OFF DelayStage TURN-ON Delay Outdoor Cutoff TemperatureControl Band Outdoor Cutoff DeadbandMaximum Water Temperature SET PointCircuit Board Interior Jumper & Switches AutoSlave DHWManual LEAD-LAG Output OverrideOptional Controls Night Setback OptionDigital Display Option Replacement Parts List Call OUT DescriptionSystem START-UP Settings System Setting Entered on DateInterior Jumper & Switch Settings Troubleshooting Guide OFFLimited Warranty Litho in U.S.A