SEQUENCE OF OPERATION
1.When the reset is enabled, the
2.Upon a call for the heat the control closes the lead unit's thermostat (TH) circuit, which the energizes the lead unit's circulating pump. After the flow switch has confirmed adequate flow, the ignition sequence is initiated and the unit ignites at stage 1. The Control then sequences the units/stages in response to changes in the system to target differen tial temperature, time away from target temperature, and temperature
3.Additional stages (and units) are activated or deactivated as required in order to maintain or restore target system water temperature. This Control uses "first on, last off" logic. As the system water temperature increases and begins to approach target temperature, the Control deactivates the stages and heaters in reverse order of firing until the first unit/stage fired is turned off. After the final stage of a given unit has been turned off, that unit's Economaster pump control will continue to power the unit's circulating pump until a
4.The Control stores firing command and system response data in the last five memory registers of the microprocessor. On the next call for heat, the Control will modify the stored P+I+D data to optimize its own responses.
5.When the outdoor temperature exceeds the outdoor cutoff temperature, the Control enters warm weather
MANUAL OVERRIDE
Internal Switch (S5) Output Override can be used to manually override the