CONTROL FAMILIARIZATION
The System is configured using the circuit board jumpers and switches, and the front panel control potentiometers.
Open the front cover of the Boiler Control Box for access to the front panel. Remove the front panel to gain access to the jumpers and switches on the
Refer to the Interior Jumper and Switches section of this manual (pg. 24) for detailed configuration instructions.
1.Last Stage Selector. Install the jumper pot (J2) shunt bar in the position that corresponds to the total number of stages to be controlled.
2.First Stage Selector. Switch (S2); Place switches in the ON position corresponding to the first stage of each boiler in the system. Switch position #1 should always be in the ON position.
3.Mode Selector. Switch (S3) determines the following:
A.Switch #1, R/M
OFF - Manual
B.Switch #2, 70°F OFF
OFF - Outdoor Reset Enabled
ON - 70°F Defeat Enabled, Outdoor Reset
C.Switches #3 Master/Slave Option
OFF - Designates the
ON - Designates the unit as a slave (used for ganged
D.Switch #4, No Min Set Point Switch
OFF - Minimum allowable Set Point of 105°F to reduce potential of condensing the boiler.
ON - Set Point can be reduced to 40°F for special applications (i.e. water source heat pumps, etc.)
E.Switch #5 (reserved)
F.Switch #6 (reserved)
G.Switch #7 (reserved)
H.Switch #8 (reserved)
4.
5.Output
6.System Test Switch (S1) is a momentary switch which will cause status indicators to blink five times then revert to normal indications. This tests the functions status of the
Reinstall the panel above indicator lights that cover the
Refer to the CONTROL POTENTIOMETERS (KNOBS) section of this manual to set the initial system operating param- eters. Set knobs to default values and fine tune if necessary.
15