Raypak 240692 manual Outdoor AIR Temperature Sensor

Page 9

AIR TEMPERATURE SENSOR

 

Red (connect)

Fig. #9040

Red (spare)

Black (connect)

 

OUTDOOR AIR TEMPERATURE SENSOR

Outdoor Air Temperature Sensor Installation Notes:

Locate the sensor on the coldest side of building, usually the North or West side.

Install the sensor in a shaded area, out of direct sunlight.

Locate no higher than 2/3 up the side of the building, or between the 2nd and 3rd floor if the building is more than three stories tall.

Do not locate under an overhang, near wall corners, near drafts from stacks, air-moving devices, windows, doors, or balconies.

Shielded cable length run is not to exceed 300 feet.

Install with properly-sized conduit that contains no other wiring.

Observe proper wire colors.

The outdoor air temperature and water temperature sensors are identical and interchangeable. Both are equipped with dual sensing elements. Connect only one red wire and the black wire to the sensor connecting points. The second element is an installed spare.

9

Image 9
Contents Electronic Boiler Sequencer & Outdoor Reset Controller Series Electronic Boiler Control Installation and Operating InstructionsTable of Contents Basics Important Safety InstructionsOptional Configurations IntroductionConcept of Operation Standard Indicator Lights Control FeaturesMechanical Installation Installation and MountingElectrical Installation Install Conduit AS AppropriateCheckyourpowersource Wiring Power Source to ControllerOutdoor AIR Temperature Sensor AIR Temperature SensorWater Temperature Sensor Installation Hydronic InstallationsTypical Water Sensor Domestic HOT Water Application Setup Procedure Domestic HOT Water InstallationsPool Heating Installations Single-Stage On/Off Boilers Field WiringPower Test Installation Verification ProcedureControl Familiarization Manual Override Sequence of OperationSeries Electronic Boiler Control Module Indicator Lights Control Functions Reset RatioPump TURN-OFF Delay Reset Ratio ChartOutdoor Cutoff Temperature Stage TURN-ON DelayControl Band Outdoor Cutoff DeadbandSET Point Maximum Water TemperatureCircuit Board Auto Interior Jumper & SwitchesDHW SlaveManual LEAD-LAG Output OverrideOptional Controls Night Setback OptionDigital Display Option Call OUT Description Replacement Parts ListSystem START-UP Settings System Setting Entered on DateInterior Jumper & Switch Settings OFF Troubleshooting GuideLimited Warranty Litho in U.S.A